Sie sind auf Seite 1von 1

Shri G.S. Institute of Technology and Science, Indore (M.

P)
Department of Electrical Engineering Course M.E. Specialization Power Electronics
Poster Presentation (Session 2016 2017)
Control Techniques for Power Quality Improvement Using DSTATCOM

Abstract Power Quality Issues Methodology


Modern power system comprises of complex networks, where
Category Spectrum Duration Magnitude
many generating stations and load center are interconnected
1.0 Transients The controller tracks the reference current generated by
1.1 Impulsive 50 ns1 ms 6 kV control algorithms.
through long power transmission and distribution networks.
1.2 Oscillatory 5 ls0.3 ms 04 p.u Configuration used is bank of three single-phase VSC and
Utility distribution networks, critical commercial operations and
2.0 Short duration variations connected to the network through an isolating transformer.
sensitive industrial loads all suffers from various type of
2.1 Interruptions 10 ms3 min 1%
outages and interruptions which can lead to significant financial Isolation prevents the dc storage capacitor from being
2.2 Sag 10 ms1 min 190%
loss, loss of production idle work forces etc. Power electronics shorted through switches in different converters.
2.3 Swell 10 ms1 min 110180%
based equipments are rapidly emerging as key components in 2.4 Rapid voltage changes Not defined 5% The iron losses of the transformer is neglected
the present modern power system. Power processing utilizing 3.0 Long duration variations Stationary 90%-106%[
these devices offer vast advantages such as flexible control, cost 3.1 Undervoltages 1 min 8090%
reduction, overall size optimization, etc. On the other hand,
Outcomes and Industrial Impact
3.2 Overvoltages 1 min 106120%
operation of these devices gives rise to some of the serious 4.0 Voltage unbalance Stationary Stationary 0.52%
power quality problems, such as the reactive power requirement 5.0 Curve distortion
These control scheme is to generate the reference current
and generation of harmonics that pollutes the power distribution 5.1 DC offset n=0 Stationary 00.1% waveforms which are to be injected to serve the required
system. Moreover, modern equipments are becoming highly 5.2 Harmonics n = 240 Stationary 020% objective.
sensitive to the voltage supplied to them. Increasing the 5.3 Interharmonics 06 kHz Stationary 02% The compensator would produce desired results as long as its
generation capacities of existing power stations is difficult and 5.4 Notches Stationary bandwidth is sufficient to follow the fluctuations in the load.
expensive due to environmental constraints. 5.5 Noise Broadband Stationary 01% There is contents of harmonics in currents and voltages and
5.6 Signal transmission 148 kHz Stationary 0.09 faults like flicker, increase in voltage fluctuations. The
For the mitigation of the power quality issues in the distribution
6.0 Voltage fluctuations 25 Hz Intermittent 0.27% telecommunication, industries, and semiconductor
system, DSTATCOM is one of the custom power device used manufacturing industries are more sensitive to power quality
7.0 Net frequency variations 50 Hz 10 s 1%
in distribution system for power conditioning. DSTATCOM problems as they need high quality of power.
can correct voltage sag, swell, unbalance by injecting the Block Diagram of SRF Theory Block Diagram of IRP Theory
reactive current into the system. References

[1]G. Arindhum, M. K. Mishra, Operation of a DSTATCOM


Objective of Project in voltage control mode, IEEE Trans. on Power Del., vol. 18,
no. 1, pp. 258264, Jan.2003.
The objective of the compensating scheme is to supply the [2]S. Bhattacharya, D.M. Divan, B. Banerjee, "Synchronous
oscillating component of power such that the dc component Reference Frame Harmonic Isolator Using Series Active
can be supplied by the source. The performance of Filter", Proc. 4th EPE, Florence, 1991, vol. 3, pp 030-035.
DSTATCOM depends on the control algorithm used for
[3]B.Singh,K.Al-haddad, A.Chandra ,Anuradha and
extraction of reference current components. This poster
D.P.Kpthari,Three-phase compensator for load balancing and
presents comparative study between Instantaneous Reactive
reactive power compensation in three-phase ,four-wire
Power (IRP) and Synchronous Reference Frame (SRF) theory
Electrical power distribution systems, Electric Machines and
for harmonic mitigation, reactive power compensation and load
Power systems , Taylor & Francis , pp.27-35, 1998.
balancing in delta connected load using voltage source
converter based DSTATCOM. The solution, even though [4] B.Singh,K.Al-haddad, A.Chandra ,Anuradha and
aesthetically pleasing has been carried out only for sinusoidal D.P.Kpthari,Three-phase compensator for load balancing and
steady state conditions reactive power compensation in three-phase ,four-wire
Electrical power distribution systems, Electric Machines and
Power systems , Taylor & Francis , pp.27-35, 1998

Name of The Student Anil Kumar Patel Enrollment Number 0801EE15ME29 Name of The Guide- Mr. R. S. Mandloi

Das könnte Ihnen auch gefallen