V4+ System

Trouble-shooting
Troubleshooting procedure

Outdoor Error Code Explanation

Indoor Error Code Explanation

System trouble analysis


Outdoor unit Error Code

Midea VRF system has self Diagnosis function, which main purpose is to
help the Service Engineer to find out fault fast and easily.

When the system in error status, the outdoor unit or indoor unit can
display the error code:
On the indoor PCB, the LED s would show the error code.
And on the outdoor unit, the LCD display will display the error code.

E1
Outdoor unit Error Code

23 23: when in standby mode,


it display the quantity of indoor units in the
system;

70: when outdoor unit is running,


70 For DC Inverter System,
It display the frequency of inverter
compressor(70Hz);

dF: when in defrost mode,


dF it display dF.
Outdoor unit Error Code

d0 d0: when in oil return program,


it display d0;

when system is in error or protection mode,


E it display Error code or protection code.
H
Error code: (E1, E2,.E9), (H1,H2...H9)
P
Protection code: (P1,P2...P9)
Outdoor unit Error Code

Code Malfunction or Protection Remark


E0 Communication error between outdoor units Only displays on slave units
E1 Phase sequence error
E2 Communication error between ODU and IDU Only displays on master unit
Ambient temperature or pipe temperature sensor
E4
error
E8 Outdoor unit address setting error
E9 Power Voltage error
H0 Communication between 780034 and IR341error The two chips on outdoor PCB
H1 Communication between 780034 and 0537error The two chips on outdoor PCB
H2 Auxiliary outdoor unit decrease error Only displays on master unit
H3 Auxiliary outdoor unit increase error Only displays on master unit
H4 If P6 occurs 3 times in half an hour, it will display H4.
H7 Indoor unit decrease error Only displays on master unit
H8 Discharge pressure sensor error
Outdoor unit Error Code
Code Malfunction or Protection Remark
P0 Top temp. protection of Dc inverter comp.
P1 High pressure protection
P2 Low pressure protection
P3 Current protection of inverter compressor Current of phase A >16 A, system stops
P4 discharge temp. protection of compressor Temperature > 125, system stops
P5 Condenser high temperature protection T > 65 for 3s, stops; T < 52, restarts
P6 Inverter module protection
P7 Current protection of fixed compressor 1 Current of phase A >16 A, system stops
P8 Current protection of fixed compressor 2 Current of phase A >16 A, system stops
P9 Fan motor protection
L0 Inverter module protection
L1 DC supply wire low voltage protection
L2 DC supply wire high voltage protection After P6 displaying for 60s, they will
L4 MCE failure display
L8 Frequency protection
L9 Frequency protection
Outdoor unit trouble shooting
E0: Communication error between outdoor units

Check address code Yes


More than 3 is invalid setting of outdoor units Reset address

No
H1 to H1, H2 to H2?
Check the connection of
Open or short circuit? communication wire Yes Reconnect or change
between outdoor units: communication wire.
Shielding wire?
No
Correct direction?
Check chip in the outdoor Yes Reinstall or replace the
Well touch?
PCB chip
Any pin broken?
No

Component damaged? Check PCB Replace PCB

Wet?
Outdoor unit trouble shooting

E1: Phase-sequence reverse or lose

Check Phase-sequence Yes Change sequence of


Must be same with (Auto-check is only valid any two phase line
compressor requirement when first powered on.)

No

power wire is not well Yes


Check if the power Fix the wire with
touched with the
supply lose phase terminal
terminals

Correct direction? No

Well touch? Yes Reinstall or replace


Check chip in the outdoor
the chip
PCB
Any pin broken?
No OK

Component damaged? Check PCB Replace PCB

Wet?
Outdoor unit trouble shooting
Three-phase power protector

The bad power supply may cause the


compressor badly damaged by frequent
start/stop, over/under voltage, over
current, phase reverse, phase imbalance,
phase no. reduction ,etc.

Key parameter

Rated Voltage: 380V, 50/60Hz


Over-voltage and under-voltage: +20%, -10% fluctuation
Imbalance protection function: 10%
Phase lost, phase reverse
Outdoor unit trouble shooting

From Power Supply

To low pressure switch

Connect to the
transferring cable of
lower pressure switch,
i.e. the original port
of low pressure switch. Plug to here
To Port
95, 98
The logic is: Note:
RPhase A
Serial in the protector output signal to the Low pressure switch,
SPhase B
When phase sequence error or lack of phase, the Outdoor PCB will display E1 TPhase C
or P2.
Outdoor unit trouble shooting

E2: Communication Error between Outdoor Displayed quantity of


Unit and Indoor Units indoor units is not stable

Check communication Yes


Short or Open circuit? wire between indoor Fix the wire
and outdoor unit
Address code is repeated
No
All the indoor units are Check the signal wire
powered on? Yes Correct the
layout and address
setting: setting
Hand in hand connection?

Too closed to the strong power? No

Too many lamps? Remove


Check if theres any Yes
interference interference
Power transforms?
No
The wire is too long?
Check chip or Fix or replace
outdoor PCB damaged part
Outdoor unit trouble shooting

E4: Outdoor ambient temperature sensor(T4) error

Check the connection Error well Connected the


between the sensor sensor with the
and PCB. PCB
OK

Check if sensor is Error


Open or short circuit damaged Change a new
sensor
Temp. Resistor value
() (K ) OK

25 10
35 6.4 Check chip or
outdoor PCB
Outdoor unit trouble shooting

E8: outdoor unit address error

Check the outdoor unit


Error Change the address
Address number is more
address < 4. (0,1,2,3)
than 3?

OK

Check chip or outdoor


PCB
Outdoor unit trouble shooting

H2,H3: Error of reduction in the number of outdoor units

Check signal wire between Error


Well connected the
The signal wire between outdoor outdoor units signal wire
unit is loosed during running?

OK

Check the power supply


Error
The power wire is loosed? for each outdoor unit Well connected the
power wire

OK

Check chip or
outdoor PCB
Outdoor unit trouble shooting
P0, P4,H6: High discharge temp.(P0 Display H6,outdoor unit
only for inverter compressor Must Repeat power on.
Charge additional refrigerant
correctly? Refrigerant leakage? Repair the leakage &
Error Charge refrigerant;
Too close between outdoor units? Lack of refrigerant
Outdoor fan is broken?
Short circuit between discharge OK
Clear the coil and
Error
air and suction air? High ambient temp or Heat- revise the wrong points
Too dirty of outdoor coil? exchanger of outdoor unit is bad
OK
Too many indoor units? Error Reduce the quantity or
Check if the cooling load is total capacity of indoor
too big
Total capacity of indoor unit is too units
big? OK
Error
Discharge refrigerant,
High temp. of discharge and There is Air or N2
vacuum, recharge
suction, big operation current? in the system
refrigerant.
OK

High temp. of discharge and Jam in the low pressure Error


Clean the system,
suction, low operation current, low side of outdoor unit
remove the dirty
pressure is low? OK

Check sensor, chip or


outdoor PCB
Outdoor unit trouble shooting
P0, P4,H6: High discharge temp.(P0 Display H6,outdoor unit
only for inverter compressor Must Repeat power on.
Charge additional refrigerant
correctly? Refrigerant leakage? Repair the leakage &
Error Charge refrigerant;
Too close between outdoor units? Lack of refrigerant
Outdoor fan is broken?
Short circuit between discharge OK
Clear the coil and
Error
air and suction air? High ambient temp or Heat- revise the wrong points
Too dirty of outdoor coil? exchanger of outdoor unit is bad
OK
Too many indoor units? Error Reduce the quantity or
Check if the cooling load is total capacity of indoor
too big
Total capacity of indoor unit is too units
big? OK
Error
Discharge refrigerant,
High temp. of discharge and There is Air or N2
vacuum, recharge
suction, big operation current? in the system
refrigerant.
OK

High temp. of discharge and Jam in the low pressure Error


Clean the system,
suction, low operation current, low side of outdoor unit
remove the dirty
pressure is low? OK

Check sensor, chip or


outdoor PCB
Outdoor unit trouble shooting
P1: High-pressure Protection
Too close between outdoor
units? Outdoor fan is broken? Error
Heat exchange of outdoor
Short circuit between discharge Check and repair
unit is not good
air and suction air? one by one
Too dirty of outdoor coil?
OK

Liquid pipe is blocked? Error


Check the liquid side of Remove the dirty;
system Open the valve
Have not opened the valve?
OK
Error

There is Air or N2 Discharge refrigerant,


High temp. of discharge and vacuum, recharge
suction, big operation in the system
refrigerant.
current?
OK
Error
low temp. of discharge, low Too many refrigerant in the Discharge some
pressure and high pressure is system refrigerant from system
high? Big current?
OK

Check sensor,
chip or PCB
Outdoor unit trouble shooting

Display H5,outdoor unit


Must Repeat power on. P2(H5): Low-pressure Protection

Charge additional refrigerant Lack refrigerant Error Repair the leakage &
correctly? Refrigerant leakage? Charge refrigerant;

OK
Gas pipe is blocked?
Gas valve is not opened

High temp. of discharge and Check gas side of system Error Remove the dirty;
suction, low operation current, Open the valve
low pressure is low?
OK

Heat exchange of indoor Error Improve the heat


Indoor fan doesnt run? exchange of indoor
Indoor coil or filter is too dirty? unit is not good
unit
Air outlet is blocked?
OK

Check chip
or PCB
Outdoor unit trouble shooting
P3,P7,P8: current protection of compressor

Heat exchange of outdoor


unit is not good

OK

Check the liquid side of


system
OK

There is Air or N2
in the system
These two possible causes
OK could only happen while
commissioning
Short circuit of strong power Too much refrigerant in the
part? system
OK

Compressor or strong Error Replace the


Compressor malfunction? power part is abnormal compressor or other
The normal resistance between damaged part.
any two terminals of OK

compressor is 1~3 Check chip or PCB


Outdoor unit trouble shooting

P5: High temp. protection of outdoor condenser

Check the connection, Error Well connected the wire;


sensor and terminal Replace the sensor or
terminal
OK

This possible cause will not happen if design


Check if the cooling load is according to the load, or if use Midea VRF
too big selection software
OK

Heat exchanging of
outdoor unit is not good

OK

There is Air or N2 This possible cause only could happen while


in the system commissioning
OK

Check the liquid side of ok


Check outdoor fan motor Check chip or PCB
system, jam?
Outdoor unit trouble shooting

Display H4,outdoor unit


P6,H4: Inverter module protection
Must Repower on.

Heat exchange is not High temp. Error Improve the heat


good? exchange
Ambient temp. is too high? OK

Compressor
malfunction? over current Error Check strong power
part & compressor
Short circuit happens
OK
to strong power

Module is broken Error Replace the module


Use this module in
another outdoor unit to
check OK

Check chip or PCB


Outdoor unit trouble shooting
L0 Check module and inverter
compressor

L1 Check rectifier bridge

L2 Check rectifier bridge and


capacitor

P6.
Check the compressor
L4 And direction of DC current
wire

L5 Check the inverter


compressor

L7 Check the phase-


sequence of the inverter
compressor
L8/L9
Change the chip or change
the compressor
Outdoor unit trouble shooting

P9: inverter fan module protection

Error Improve the heat


Heat exchange is not good? High temp.
exchange; block the
Ambient temp. is too high?
sunshine.
OK

Fan feedback single wire


Well connect
Communication or Error
communication wire and
Wire between Fan module feedback single problem feedback single wire
and main PCB board.
OK

Error
Check the voltage between Replace the power
No Power supply for the
P and N on the module PCB module
module
OK

Error
Use this module in another Inverter Module is broken Replace the module
outdoor unit to check
Indoor unit trouble shooting

All lamps off: indoor unit is in standby mode

DEF lamp is on: TIMER lamp is on:


Anti cold air or in defrosting mode Timer function is on
Indoor unit trouble shooting
Defrost lamp flash
Mode conflict :
For the Inverter Smart system( 2 Pipe), cooling
or heating can be not realized by the
same system at the same time. Heating
mode has priority:
Rules
Outdoor unit is running in cooling mode, when received heating requirement, outdoor unit
change to heating mode and the indoor units which are in cooling mode will display mode
conflict;
When the outdoor unit is running in heating mode, If cooling or fan only is required from any
indoor unit , the outdoor unit does not acknowledge the requirement, and the indoor units will
display this conflict mode.
Cooling Heating Fan only OFF
Cooling mode No Conflict No No
Heating mode Conflict No Conflict No
Fan only mode No Conflict No No
OFF No No No No
Indoor unit trouble shooting
The four LED lamp display board :
The error display as below
Lamp Meaning
ON Indoor unit is normally operation.
OFF Indoor unit is OFF
OPERATION
4 Flash Indoor unit is Standby
3 Flash rapidly Temperature sensor malfunction

2 ON Timer function is on
1 TIMER Communication malfunction between
Flash rapidly
indoor and outdoor unit
Indoor unit is in anti-cold model or system
ON
is defrosting
DEF./FAN
Flash rapidly Mode confliction
Flash EEPROM malfunction
Flash rapidly Water-level switch abnormal
ALARM
Flash Outdoor unit malfunction
Operation Flash
There is no address
&Timer simultaneously
Indoor unit trouble shooting
Hi-wall indoor units

Digital display

Code Operation status


E0 Outdoor power supply malfunction (phase loss, phase sequence error, etc.)
E1 Communication malfunction between indoor and outdoor unit
E2 Room temperature (T1) sensor malfunction
E3 Middle evaporator temperature (T2) sensor malfunction
E4 Evaporator outlet temperature (T2B) sensor malfunction
Condenser temperature (T3) or ambient temperature (T4) sensor, or digital
E5
(or inverter) compressor discharge temperature (T7) sensor malfunction
E6 Mode confliction
EE Water level alarm
Indoor unit trouble shooting
Digital display
4-way cassette indoor units

Code Operation status LED lights


Communication malfunction between indoor and outdoor
E1 LED2 Flash rapidly
unit
E2 Room temperature (T1) sensor malfunction LED1 Flash rapidly

E3 Middle evaporator temperature (T2) sensor malfunction LED1 Flash rapidly

E4 Evaporator outlet temperature (T2B) sensor malfunction LED1 Flash rapidly

EE Water level alarm LED4 Flash rapidly

E7 EEPROM malfunction LED1 Flash

E0 Mode confliction LED3 Flash rapidly

ED Outdoor unit malfunction LED4 Flash


Indoor unit trouble shooting

Operation lamp flashes


code: E2,E3,E4

Room temp. sensor T1


Indoor temp. sensor
Indoor coil middle temp. abnormal
sensor T2

Indoor coil outlet temp. Check the connection port Error


Well connected the
sensor T2B between sensor and PCB is sensor and PCB
loose or not connected
No

Sensor is open circuit?


Check the sensor is good Error Replace the bad
or not? sensor
Sensor is short circuit
No

Component damaged? Check IU Replace IU chip or


chip or PCB PCB
Wet?
Indoor unit trouble shooting

If the drainage pipe is Alarm lamp flashes Code: EE


blocked?

The lift height of drainage


pipe is more than the
limitation ? Condensate Water Revise the mistake
lever is higher

Check the connection between switch Well connected the


Error
and PCB is loose or not in place switch and PCB

No

Check the float switch is Error Replace the bad


good or not? switch

No
Check IU chip or PCB Error Replace IU chip or
PCB
Indoor unit trouble shooting

Code: E7

EEPROM installation Well install the


Check the pin of the Error EEPROM.
EEPROM.

EEPROM is broken Error Replace the EEPROM

NO
Component damaged?
Error Replace the PCB
Check PCB
Wet?
System trouble analysis

Poor performance wrong selection of refrigerant pipe, indoor EXV or branch joint,
the refrigerant distribution among the indoor units is quite
imbalance;

1.Low designed load


2.Long refrigerant pipe and big height difference
3.The match ratio is more than 130%

1.Leakage in the system;


2.Additional refrigerant is not charged enough
Poor performance
in cooling or Address code of indoor units is repeated or incorrect, check
heating the quantity of indoor units with CCM or check button on
outdoor PCB

Heat exchange of indoor or outdoor unit is not good. E.g.:


dirty, bad ventilation..

1.Indoor (EXV) doesnt work, are there noise and temp.


difference?
2.Some indoor units have no power
System trouble analysis
How to set indoor unit address

lock

Push the cover down ,then use a pin press the lock button for 5 seconds,
Press ON/OFF button one time, press up/down button can select the address
Number, then press the FAN mode button can send the address number.
System trouble analysis

How to inquire indoor unit address

lock

Push the cover down ,then use a pin press the lock button for 5 seconds,
Press ON/OFF button one time, then press the MODE button can inquire
The address number.
System trouble analysis

How to Check indoor capacity code Quickly

Capacity code 0 1 2 3 4 5 6 7 8 9

Capacity (x
22 28 36 45 56 71 80 90 112 140
100W)

Horsepower
0.8 1.0 1.2 1.6 2.0 2.5 3.0 3.2 4.0 5.0
(HP)

Continue pressing the


manual button of indoor
unit for 10s, the capacity
8 4 2 1 code of this indoor unit will
display.

In the below example:


Operation and Alarm lamp
are constant-on.

The capacity code = 8+1=9


System trouble analysis

How to set indoor capacity code

Rotary
Power Capacity of indoor units
Switch
setting

0 0.8hp (2200W)

1 1.0hp (2800W)

2 1.2 hp (3600W)

3 1.7hp (4500W)

4 2.0 hp (5600W)

5 2.5 hp (7100W)

6 3.0hp (8000W)

7 3.2 hp (9000W)

8 4.0hp (11200W)

9 5.0hp (14000W)
power_s
System trouble analysis
The suction pipe Frost

Outdoor ambient temp. is low


or high? Frost volume is much Check ambient temp. and Error Find the root cause
or little? frost volume
OK

Indoor EXV jammed?


Indoor fan doesnt run?
Check low pressure Error Clean the indoor unit;
Filter or coil of indoor unit is too Fix the broken part
dirty?
OK

When the indoor units are Error Resume the power for
running, if power failure Check Power supply of
indoor units these indoor units
happen, the indoor EXV will
keep open.
OK

When system running in cooling


Discharge
mode, if ambient is low, the Check refrigerant
refrigerant can not be unwanted
volume refrigerant
evaporated absolutely