Beruflich Dokumente
Kultur Dokumente
Superheater
Convection bank
Membrane
Furnace Wall
Outer Casing
Water
Wind Box
Burner Drum
GAS FIRED FM BOILER
Water Circulation circuit
GAS FIRED FM BOILER
P&ID DESCRIPTION:
Steam & Water:
Components:
Boiler Feed Water Control Station
Drum Coil Pre-heater
Economizer
Boiler (Steam Drum, Evaporator, Water Drum)
Superheaters (HP & MP Superheaters)
De-super heater
Main Steam Piping
GAS FIRED FM BOILER
Boiler is provided with a drum coil heater inside the water drum. The
heater is a heat exchanger in which the feed water from the feed
water control station passes through the tubes picking up heat from
the drum water
Heat that is picked up from the coil heater ensures that the feed
water temperature at the inlet to the economizer leads to a flue gas
temperature greater than the sulphur dew point temperature.
GAS FIRED FM BOILER
GAS FIRED BOILER
Economizer:
To recover economically feasible heat from the flue gas.
Steam Drum:
Steam drum Accommodates
Feed pipe
Continuous blow down line
H.P. dosing pipe
Cyclone Separators
Primary and Secondary Scrubbers
GAS FIRED FM BOILER
Convection Bank :
Convection section consists of Convection Banks . Each Convection
bank consists of set of SA 210 Gr A1 plain tubes (50.8 mm OD &
3.66 mm Thk.), with their ends fitted duly to the bottom and top
drums of the Evaporator (twin drum type)
Water drum:
The Water or the Mud drum is provided with the intermittent blow
down (IBD) connection.
Water drum accommodates:
Intermittent Blow down Connection MOV
Drum coil Pre-heater
GAS FIRED BOILER
HP Superheater:
TheSuper heater section is divided into five passes:
HPSH pass I (SA 210M Gr A1 T22 & 50.8 mm OD / 4.5 mm Thk)
HPSH pass II &IV (SA 213M T11 & 50.8 mm OD / 4.5 mm Thk)
HPSH pass III &V (SA 213M T22 & 50.8 mm OD / 4.5 mm Thk)
GAS FIRED BOILER
De-Superheater (Attemperator):
Spray type Attemperator assembly is provided Between PSH &
SSH to control final stem temperature.
Water is sprayed through the spray nozzle along the steam flow
direction.
Construction of the sleeve along with the spray nozzle facilitates
proper mix up of water with steam.
Spray water through temperature control valve.
GAS FIRED BOILER
FD Fan:
One Motor driven FD Fan with 100% capacity provided.
Supply of combustion air to the boiler.
Forcing product of combustion through the boiler, economizer & to
the stack.
GAS FIRED BOILER
Air Ducts:
FD fan Discharge connected wind box through air duct.
One Para flow modulating damper provided at wind box inlet
A pressure Transmitter is provided in Air duct and wind box to
measure the pressure.
One Aerofoil is provided to measure the combustion air flow.
Air flows into furnace through Air sleeve damper mounted on
burners.
GAS FIRED BOILER