Beruflich Dokumente
Kultur Dokumente
Fire Fighting
Water system discussion
Prepared by Eng / Ahmed Elgazar.
إهداء
إلي جروب
#Arab_mep_engineer
Content
1- ul Underwriters Laboratories
2- c-ul ( CSA ) Underwriters’ Laboratories of Canada
3-FM Factory Mutual Research Corporation
4-LPS Loss Prevention Standards
5- VDS Verband der Schadenversicherer
Fire fighting systems
1- water systems
2- gas systems ( Co2 , FM200 , aresol , novac, …
3- foom system
Water systems
Sprinkler system
1- wet system
2- dry system
3- pre action system
4- deluge system
5- anti freeze system
Standpipe system
System component
1- water tank
2- pump
3- control valve
4- water discharge element ( sprinkler , hose )
Wet system
Is the most common system
Wet system
General information
Gauges on both sides of the main valve, register pressure on the supply
and system sides,
An alarm check valve detects water flow and activates the alarm system,
Wet system
Control valve
Wet system
Control valve
• Wet system is common System in sprinkler
systems.
• Water fill all pipe from pump to sprinkler.
• When fire happen sprinkler bulb broken water
begin in dropped the pressure in the system
side reduce and the gate (clapper ) open to
supply the system with pressurized water.
• After clapper open water through alarm
outlet forward to fill retard chamber then run
the conge
Wet system
Control valve retard chamber
• Alarm check valve have
retard chamber
to accumulate leakage
water before the gong
• Retard chamber have
automatic drain to drain little leakage
Wet system
Control valve animation
Control valve animation
Dry system
Dry system
General information
• Pipes are not filled with water (but with pressurized
gas or air),
• Heat from a fire opens a sprinkler head,
• Air pressure drops in the piping and opens a water
valve (the dry-pipe valve)
• Gas, air shall have compressor to keep the pressure.
• System shall have two pressure gauge one in the side
of gas and other in the side of water
Dry system
General information
• Pipes are not filled with water (but with pressurized gas
or air),
• Heat from a fire opens a sprinkler head,
• Air pressure drops in the piping and opens a water valve
(the dry-pipe valve)
• Gas, air shall have compressor to keep the pressure and
Air maintenance devices
• System shall have two pressure gauge one in the side of
gas and other in the side of water
• Pressure of gas shall be accordance of dry pipe valve
datasheet
Dry system
General information
• Pipes are not filled with water (but with pressurized
gas or air),
• Heat from a fire opens a sprinkler head,
• Air pressure drops in the piping and opens a water
valve (the dry-pipe valve)
• Gas, air shall have compressor to keep the pressure
and Air maintenance devices
• System shall have two pressure gauge one in the side
of gas and other in the side of water
Dry system
Air supply
• You can use air or other approved gas (
nitrogen,….)
• The compressed air supply shall be from a source
available at all times
• Pressure of air shall be 20 psi (1.4 bar )
• Check valve shall be installed in air supply line to
prevent water ,air flow from one system to
other.
• Quick-Opening Devices shall be installed
• Air Maintenance devise
Dry system
Air supply
• Quick-Opening Devices shall be installed
7.2.3.3 A system size of not more than 500 gal (1893 L) shall
be permitted without a quick-opening device and shall not be
required to meet any specific water delivery requirement to
the inspection test connection.
7.2.3.4 A system size of not more than 750 gal (2839 L) shall
be permitted with a quick-opening device and shall not be
required to meet any specific water delivery requirement to
the inspection test connection.( quotation from NFPA 13 , 2013 )
Dry system
Air supply
• Quick-Opening Devices shall be installed
Dry system
Air supply
• Quick-Opening Devices important
• Its
reduce the time delay between the
1- Thermal sensitivity
• STANDARD RESPONSE
– 3 Min. 51 Sec. Room Fire Test
– 100 Sec. Plunge Test
• QUICK RESPONSE
– 75 Sec. Room Fire Test
– 14 Sec. Plunge Test
• RESIDENTIAL
– 14 Sec. Plunge
Sprinkler
Sprinkler type : (3.6.4) as thermal sensitivity
We can divided sprinkler by time of response
3.6.4.1 Control Mode Specific Application (CMSA) Sprinkler. A type of spray
sprinkler that is capable of producing characteristic large water droplets and
that is listed for its capability to provide fire control of specific high-challenge
fire hazards.
3.6.4.2 Early Suppression Fast-Response (ESFR) Sprinkler. A type of fast-
response sprinkler that has a thermal element with an RTI of 50 (meters-
seconds)1/2 or less and is listed for its capability to provide fire suppression of
specific high-challenge fire hazards.
2- Temperature rating.
Sprinkler
2- Temperature rating.
8.3.2.2 Where maximum ceiling temperatures exceed 100°F (38°C), sprinklers
with temperature ratings in accordance with the maximum ceiling
temperatures of Table 6.2.5.1 shall be used.
Ex :
Standard sprinkler ,1/2 “ , k- 5.6 , pendant , glass bulb
Sprinkler system
classification of system based on occupancy :
1- light hazard
2- ordinary hazard
3- extra hazard
Sprinkler system
classification of system based on occupancy :
1- light hazard كيمة المواد قليله وقوة الحرق ضعيفه
Light hazard occupancies shall be defined as occupancies or portions of other occupancies where the
quantity and/or combustibility of contents is low and fires with relatively low rates of heat release are
expected
Ex : A.5.2 Light hazard occupancies include occupancies having uses and conditions similar to the following:
(1) Animal shelters (2) Churches
(3) Clubs
(4) Educational (5) Hospitals, including animal hospitals and veterinary facilities
(6) Institutional (7) Kennels
(8) Libraries, except large stack rooms (9) Museums
(10) Nursing or convalescent homes
(11) Offices, including data processing
(12) Residential
(13) Restaurant seating areas
(14) Theaters and auditoriums, excluding stages and prosceniums
Sprinkler system
classification of system based on occupancy :
2- ordinary hazard
Ordinary hazard contained two group ( ordinary 1 , ordinary 2 )
Ordinary 1 : كمية المواد قليله وقوه الحريق متوسطه
5.3.1.1 Ordinary hazard (Group 1) occupancies shall be defined as
occupancies or portions of other occupancies where combustibility is low,
quantity of combustibles is moderate, stockpiles of combustibles do not
exceed 8 ft (2.4 m), and fires with moderate rates of heat release are expected
Ordinary 2: كمية المواد متوسطه وقوه الحريق متوسطه او عاليه
5.3.2.1 Ordinary hazard (Group 2) occupancies shall be defined as
occupancies or portions of other occupancies where the quantity and
combustibility of contents are moderate to high, stockpiles of contents with
moderate rates of heat release do not exceed 12 ft (3.66 m), and stockpiles of
contents with high rates of heat release do not exceed 8 ft (2.4 m)
Sprinkler system
classification of system based on occupancy :
Ordinary 1 :
A.5.3.1 Ordinary hazard (Group 1) occupancies include occupancies
having uses and conditions similar to the following:
(1) Automobile parking and showrooms
(2) Bakeries المخابز
(3) Beverage manufacturing مصانع المشروبات
(4) Canneries مصانع التعليب
(5) Dairy products manufacturing and processing منتجات االلبان
(6) Electronic plants
(7) Glass and glass products manufacturing
(8) Laundries المغاسل
(9) Restaurant service areas
Sprinkler system
classification of system based on occupancy :
Ordinary 2 :
A.5.3.2 Ordinary hazard (Group 2) occupancies include occupancies having
uses and conditions similar to the following: (1)Agricultural facilities
(2) Cereal mills (3) Confectionery products (4) Distilleries
(5) Dry cleaners (6) Feed mills (7) Horse stables (8) Leather goods
manufacturing
(9) Libraries — large stack room areas (10) Machine shops
(11) Metal working (12) Mercantile (13) Paper and pulp mills
(14) Paper process plants (15) Piers and wharves
(16) Plastics fabrication (17) Post offices (18) Printing and publishing (19)
Repair garages (20) Stages (21) Textile manufacturing
(22) Tire manufacturing (23) Tobacco products manufacturing
(24) Wood machining (25) Wood product assembly
Sprinkler system
classification of system based on occupancy :
Extra Hazard Occupancies
Extra hazard contained two group:
5.4.1 Extra Hazard (Group 1). Extra hazard (Group 1) occupancies shall
be defined as occupancies or portions of other occupancies where the
quantity and combustibility of contents are very high and dust, lint, or
other materials are present, introducing the probability of rapidly
developing fires with high rates of heat release but with little or no
combustible or flammable liquids.
5.4.2 Extra Hazard (Group 2). Extra hazard (Group 2) occupancies
shall be defined as occupancies or portions of other occupancies with
moderate to substantial amounts of flammable or combustible liquids
or occupancies where shielding of combustibles is extensive.
Sprinkler system
classification of system based on occupancy :
Extra Hazard (Group 1).
A.5.4.1 Extra hazard (Group 1) occupancies include occupancies
having uses and conditions similar to the following
(1) Aircraft hangars (except as governed by NFPA 409)
(2) Combustible hydraulic fluid use areas
(3) Die casting
(4) Metal extruding
(5) Plywood and particleboard manufacturing
(6) Printing [using inks having flash points below 100°F (38°C)]
(7) Rubber reclaiming, compounding, drying, milling, vulcanizing
(8) Textile picking, opening, blending, garneting, or carding, combining of
cotton, synthetics, wool shoddy.
(10) Upholstering with plastic foams.
Sprinkler system
classification of system based on occupancy :
Extra Hazard (Group 2).
A.5.4.2 Extra hazard (Group 2) occupancies include occupancies
having uses and conditions similar to the following:
(1) Asphalt saturating
(2) Flammable liquids spraying
(3) Flow coating
(5) Open oil quenching
(6) Plastics manufacturing
(7) Solvent cleaning
(8) Varnish and paint dipping
Sprinkler system
3-6.3.1.4 Nonmetallic
4-6.3.1.5 Brass pipe
6.3.6 Brass Pipe. Brass pipe specified in Table 6.3.1.1 shall be
permitted in the standard weight in sizes up to 6 in. (150mm)for
pressures up to 175 psig (12 bar) and in the extra strong weight
in sizes up to 8 in. (200mm)for pressures up to 300 psig (20 bar).
Sprinkler system
Net work
Pipe and fitting : ( 6.3 )
Sprinkler system
Net work
Pipe and fitting : ( 6.3 )
Limitation for using nonmetallic pipes.
6.3.7.2* When nonmetallic pipe is used in combination systems
utilizing steel piping internally coated with corrosion inhibitors
and nonmetallic piping, the steel pipe coating shall be investigated for
compatibility with the nonmetallic piping by a testing laboratory.
6.3.7.4 When nonmetallic pipe is used in combination systems
utilizing steel pipe, cutting oils and lubricants used for fabrication of the
steel piping shall be compatible with the nonmetallic pipe materials.
𝒃𝒖𝒊𝒍𝒅𝒊𝒏𝒈 𝒂𝒓𝒆𝒂
Number of sprinkler =
𝒂𝒓𝒆𝒂 𝒑𝒆𝒓 𝒔𝒑𝒓𝒊𝒏𝒌𝒍𝒆𝒓
Sprinkler system
Net work
Sprinkler distribution.
1- area of building plane
1-1 know if the building ( area ) need sprinkler protection or not
Area limitation as nfpa 101 all next case shall not need sprinkler
1- Assembly occupancies consisting of a single multipurpose room of less than 12,000
ft2 (1115 m2) that are not used for exhibition or display and are not part of a mixed
occupancy
2- Locations in unenclosed stadia and arenas as follows:
(a) Press boxes of less than 1000 ft2 (93 m2)
(b) Storage facilities of less than 1000 ft2 (93 m2) if enclosed with not less than 1-hour
fire resistance–rated construction
3-Sprinklers shall not be required for stages 1000 ft2 (93 m2) or less in area and 50 ft
(15 m) or less in height.
4-Automatic sprinklers shall not be required in closets not exceeding 24 ft2 (2.2 m2)
and in bathrooms not exceeding 55 ft2 (5.1 m2), provided that such spaces are
finished with lath and plaster or materials providing a 15-minute thermal barrier
Sprinkler system
Net work
Sprinkler distribution.
1- building plane area
Number of riser per area
8.2.1 The maximum floor area on any one floor to be protected
by sprinklers supplied by any one sprinkler system riser
or combined system riser shall be as follows:
(1) Light hazard — 52,000 ft2 (4831 m2)
(2) Ordinary hazard — 52,000 ft2 (4831 m2)
(3)*Extra hazard — Hydraulically calculated — 40,000 ft2 (3716 m2)
A.8.2.1(3) Pipe schedule — 25,000 ft2 (2323 m2).
Sprinkler system
Net work
Sprinkler distribution.
3- ( protection area for sprinkler (As))
As = S x L
S = distance between sprinkler in the branch
L = distance between branches
4.7.5* Hose connections shall be located so that there is at least 3 in. (76.2 mm)
clearance between any adjacent object and the handle of the valve when the valve is
in any position ranging from fully open to fully closed.
Standpipe system
4.8 Fire Department Connections.
4.8.1 Fire department connections shall be listed for a working pressure equal to or
greater than the pressure requirement of the system demand.
4.8.2 Each fire department connection shall have at least two 21⁄2 in. (65 mm) internal
threaded swivel fittings having NHS
threads
Standpipe system
4.8 Fire Department Connections.
6.4.1 shutoff valves shall not be installed between the fire department connection and
the system.
6.4.2 A listed check valve shall be installed in each fire department connection,
including the connection in manual-dry systems, and located as near as practicable to
the point where it joins the system.
6.4.3 The fire department connection shall be installed as follows:
(1) Automatic Wet and Manual Wet Standpipe Systems. On the system side of the
system control valve, check valve, or any pump, but on the supply side of any
isolating valves
(2) Automatic Dry Standpipe Systems. On the system side of the control valve and
check valve and the supply side of the dry pipe valve
(3) Semiautomatic Dry Standpipe Systems. On the system side of the deluge valve
(4) Manual Dry Standpipe Systems. Directly connected to system piping with a check
valve in the piping.
Standpipe system
4.8 Fire Department Connections.
7.12.1 One or more fire department connections shall be provided for each zone of
each Class I or Class III standpipe system.
7.12.1.1 The high zone fire department connection(s) shall not be required to be
provided where 7.9.3 applies.
7.12.2 High-rise buildings shall have at least two remotely located fire department
connections for each zone.
7.12.2.1 A single connection for each zone shall be permitted where acceptable to the
fire department.
7.12.3 Fire department connection sizes shall be based on the standpipe system
demand and shall include one 21⁄2 in. (65 mm) inlet per every 250 gpm (946 L/min)
Standpipe system
Design.
7.1* General. The design of the standpipe system is governed by
1- building height.
2- area per floor occupancy classification,
3- egress system design,
4- required flow rate and residual pressure, and
5- the distance of the hose connection from the source(s) of the water supply
Standpipe system
Design.
7.2* Pressure Limitation.
7.2.1 The maximum pressure at any point in the system at any time shall not exceed
350 psi (24 bar).
7.2.3* Maximum Pressure at Hose Connections.
7.2.3.1 Where the residual pressure at a 11⁄2 in. (40 mm) outlet on a hose connection
available for trained personnel use exceeds 100 psi (6.9 bar), an approved pressure-
regulating device shall be provided to limit the residual pressure at the flow required
by Section 7.10 to 100 psi (6.9 bar).
7.2.3.1.1 Paragraph 7.2.3.1 shall not apply to the 11⁄2 in. (40 mm) outlet on a 21⁄2 in.
× 11⁄2 in. (65mm× 40 mm) reducer as allowed by 5.3.3.2 and 7.3.4.1.
7.2.3.2* Where the static pressure at a 21⁄2 in. (65 mm) hose connection exceeds 175
psi (12.1 bar), an approved pressure regulating device shall be provided to limit static
and residual pressures at the outlet of the hose connection to 175 psi (12.1 bar).
7.2.3.3 The pressure on the inlet side of the pressure regulating device shall not
exceed the rated working pressure of the device.
Standpipe system
Design.
Residual pressure:
7.8.1a minimum residual pressure of 100 psi (6.9 bar) at the outlet of the hydraulically
most remote 21⁄2 in. (65 mm) hose connection and 65 psi (4.5 bar) at the outlet of the
hydraulically most remote 11⁄2 in. (40 mm) hose station..
7.8.1.2* Manual standpipe systems shall be designed to provide 100 psi (6.9 bar) at
the topmost outlet with the calculations terminating at the fire department
connection
Standpipe system
Design.
7.3 Locations of Hose Connections
7.3.2* Class I Systems. Class I systems shall be provided with 21⁄2 in. (65 mm) hose
connections in the following locations:
(1) At the main floor landing in exit stairways
(2) On each side of the wall adjacent to the exit openings of horizontal exits
(3) In other than covered mall buildings, in each exit passageway at the entrance from
the building areas into the passageway
(4) In covered mall buildings, at the entrance to each exit passageway or exit corridor,
and at the interior side of public entrances from the exterior to the mall
(5)*At the highest landing of stairways with stairway access to a roof, or on roofs with
a slope of less than 4 in 12 where stairways do not access the roof.
7.3.2.3* Hose connections on one side of a horizontal exit shall not be required where
another outlet on that side of the horizontal exit can reach the portions of the building
on the other side of the horizontal exit within the distances required by 7.3.2.3.1 that
would have been protected by the outlet that was omitted.
7.3.1.1 Hose connections and hose stations shall be unobstructed and shall be located
not less than 3 ft (0.9 m) or more than 5 ft (1.5 m) above the floor
Standpipe system
Design.
Travel distance
7.3.2.2* Where the most remote portion of a non sprinklered floor or story is located
in excess of 150 ft (45.7 m) of travel distance from a hose connection in or adjacent to
a required exit or the most remote portion of a sprinklered floor or story is located in
excess of 200 ft (61 m) of travel distance from a hose connection in or adjacent to a
required exit, additional hose connections shall be provided.
7.3.2.3.1 This travel distance shall be 200 ft (61 m) for sprinklered buildings and 130 ft
(39.7 m) for non sprinklered buildings.
7.3.3* Class II Systems.
7.3.3.1 Class II systems shall be provided with 11⁄2 in. (40 mm) hose stations so that all
portions of each floor level of the building are within 130 ft (39.7 m) of a hose
connection provided with 11⁄2 in. (40 mm) hose or within 120 ft (36.6 m) of a
hose connection provided with less than 11⁄2 in. (40 mm) hose.
Standpipe system
Design.
7.4 Number of Standpipes. Separate standpipes shall be provided in each required
exit stairway.
7.9.3* For systems with two or more zones in which any portion of the higher zones
cannot be supplied by means of fire department pumpers through a fire department
connection, an auxiliary means of supply in the form of high-level water storage with
additional pumping equipment
A.7.9.3 An auxiliary means can also be in the form of pumping through the fire
department connection in series with the low- or mid-zone fire pump
Standpipe system
Design.
7.10 Flow Rates.
7.10.1 Class I and Class III Systems.
A.7.10.1.1 If a water supply system supplies more than one building or more than one
fire area, the total supply can be calculated based on the single building or fire area
requiring the greatest number of standpipes.
7.10.1.1.1 For Class I and Class III systems, the minimum flow rate for the hydraulically
most remote standpipe shall be 500 gpm (1893 L/min), through the two most remote
21⁄2 in. (65 mm) outlets.
7.10.1.1.2* Where a horizontal standpipe on a Class I or Class III system supplies three
or more hose connections on any floor, the minimum flow rate for the hydraulically
most demanding horizontal standpipe shall be 750 gpm (2840 L/min)
Standpipe system
Design.
7.10 Flow Rates.
7.10.1 Class I and Class III Systems.
7.10.1.1.3 The minimum flow rate for additional standpipes shall be 250 gpm (946
L/min) per standpipe for buildings with floor areas that do not exceed 80,000 ft2 (7432
m2) per floor. For buildings that exceed 80,000 ft2 (7432m2) per floor, the minimum
flow rate for the additional standpipes shall be 500 gpm (1893 L/min) for the second
standpipe and 250 gpm (946 L/min) for the third standpipe if the additional flow is
required for an un sprinklered building.
7.10.1.1.5 The maximum flow rate shall be 1000 gpm (3785 L/min) for buildings that
are sprinklered throughout, in accordance with NFPA 13, Standard for the Installation
of Sprinkler Systems, and 1250 gpm (4731 L/min) for buildings that are not sprinklered
throughout, in accordance with NFPA 13.
Standpipe system
Design.
7.10 Flow Rates.
7.10.2 Class II Systems.
7.10.2.1 Minimum Flow Rate.
7.10.2.1.1 For Class II systems, the minimum flow rate for the hydraulically most
remote hose connection shall be 100 gpm (379 L/min).
7.10.2.1.2 Additional flow shall not be required where more than one hose connection
is provided.
Design.
Standpipe system
Hydraulic calculation:
7.10.1.2.1 Hydraulic calculations and pipe sizes for each standpipe shall be based on
providing 250 gpm (946 L/min) at the two hydraulically most remote hose connections on
the standpipe and at the topmost outlet of each of the other standpipes at the minimum
residual pressure required by Section 7.8.
7.10.1.2.1.1* Where a standpipe system has risers that terminate at different floor levels,
separate hydraulic calculations shall be performed for the standpipes that exist on each
level. In each case, flow shall be added only for standpipes that exist
on the floor level of the calculations.
7.10.1.2.2 Where a horizontal standpipe on a Class I and Class III system supplies three or
more hose connections on any floor, hydraulic calculations and pipe sizes for each
standpipe shall be based on providing 250 gpm (946 L/min) at the three hydraulically most
remote hose connections on the standpipe and at the topmost outlet of each of the other
standpipes at the minimum residual pressure required by Section 7.8.
7.10.1.2.3* Common supply piping shall be calculated and sized to provide the required
flow rate for all standpipes connected to such supply piping, with the total not to exceed
the maximum flow demand in 7.10.1.1.5.
7.10.1.2.4 Flows from additional standpipes as required by 7.10.1.1 shall not be required to
be balanced to the higher pressure at the point of connection
Design.
Standpipe system
Hydraulic calculation: class II
7.10.2.2.1 Hydraulic calculations and pipe sizes for each standpipe shall be based on
providing 100 gpm (379 L/min) at the hydraulically most remote hose connection on
the standpipe at the minimum residual pressure 4.5 bar
Design.
Standpipe system
Hydraulic calculation:
7.10.1.3 Combined Systems
7.10.1.3.1.1 In a building protected in accordance with NFPA 13, Standard for the
Installation of Sprinkler Systems, or NFPA13R, Standard for the Installation of Sprinkler
Systems in Low- Rise Residential Occupancies, the water supply for the combined
sprinkler and automatic standpipe system shall be based on the sprinkler system
demand (including any hose stream demand) or the standpipe demand, whichever is
greater.
7.10.1.3.1.2 A separate sprinkler demand shall not be required.
7.10.1.3.2 For a combined system in a building equipped with partial automatic
sprinkler protection, the flow rate required by 7.10.1 shall be increased by an amount
equal to the hydraulically calculated sprinkler demand or 150 gpm (568 L/min) for light
hazard occupancies, or by 500 gpm (1893 L/min) for ordinary hazard occupancies,
whichever is less.
Design.
Standpipe system
9.2 Minimum Supply for Class I and Class III Systems. The water supply shall be
capable of providing the system demand established by Sections 7.8 and 7.10 for at
least 30 minutes.
9.3 Minimum Supply for Class II Systems. The minimum supply for Class II systems
shall be capable of providing the system demand established by Sections 7.8 and 7.10
for at least 30 minutes
Drain and the test
Standpipe system
7.11.2 Drains. All standpipe systems shall be equipped with drain connections.
7.11.2.1 A main drain shall be provided on the standpipe system side of the system
control valve
7.11.2.4 The main drain connection shall be provided at a location that permits the
valve to be opened wide without causing water damage.
Design.
Standpipe system
Example :
Design.
Standpipe system
Example :
A.7.10.1.2.1.1 For example, consider the standpipe system shown in Figure
A.7.10.1.2.1.1 with two risers that terminate at the 15th floor and two risers that
terminate at the 10th floor of this fully sprinklered high-rise building. In this case, two
separate hydraulic calculations need to be performed. The first would verify that the
system can deliver 100 psi (6.9 bar) to the top of the risers on the 15th floor with a
total of 750 gpm (2840 L/min) flowing [250 gpm (946 L/min) each at points A, B, and
C]. The second would need to prove that the system can deliver 100 psi (6.9 bar) to the
10th floor with a total of 1000 gpm (3785 L/min) flowing [250 gpm (946 L/min) each
at points D, E, F, and G]. Note that since the building is sprinklered, there is no flow
required from the fourth riser in this second calculation.
.
Fire pump
Fire pump
Type of fire pump.
1- Horizontal Split-Case Pump
2-Vertical Line shaft Turbine Pump.
3- In-Line Pump.
4-End Suction Pump
Fire pump
Source of water.
4.6.2.1 Any source of water that is adequate in quality, quantity, and
pressure shall be permitted to provide the supply for a fire pump.
4.6.2.2 Where the water supply from a public service main is not
adequate in quality, quantity, or pressure, an alternative water source
shall be provided.
4.6.4.1 A stored supply plus reliable automatic refill shall be sufficient to
meet the demand placed upon it for the design duration.
Fire pump
Centrifugal Pumps.
6.1.1.1 Centrifugal pumps shall be of the overhung impeller design and
the impeller between bearings design.
6.1.1.3 The impeller between bearings design shall be separately
coupled single-stage or multistage axial (horizontal) split-case-type
6.1.2* Application. Centrifugal pumps shall not be used where a static suction
lift is required.
A.6.1.2 The centrifugal pump is particularly suited to boost the pressure
from a public or private supply or to pump from a storage tank where
there is a positive static head.
Fire pump
Types of Centrifugal Pumps.
Fire pump
Types of Centrifugal Pumps. Page 74 NFPA 20 edition 2013
1-end suction
2- inline
3- horizontal spilt case.
4- vertical spilt case.
Fire pump
Characteristic of Centrifugal Pumps.
6.2.1 Pumps shall furnish not less than 150 percent of rated capacity at not
less than 65 percent of total rated head
6.2.2 The shutoff head shall not exceed 140 percent of rated head for any type
pump.
Fire pump
Centrifugal Pumps.
6.3 Fittings.
6.3.1* Where necessary, the following fittings for the pump shall be provided
by the pump manufacturer or an authorized representative:
(1) Automatic air release valve
(2) Circulation relief valve
(3) Pressure gauges
6.3.2 Where necessary, the following fittings shall be provided:
(1) Eccentric tapered reducer at suction inlet
(2) Hose valve manifold with hose valves
(3) Flow measuring device
(4) Relief valve and discharge cone
(5) Pipeline strainer
Fire pump
Centrifugal Pumps.
6.3 Fittings. Hose valve manifold with hose valves & flow meter
Fire pump
Centrifugal Pumps.
6.3 Fittings. Air release valve 6.3.3
Fire pump
Centrifugal Pumps.
6.3 Fittings. Relief valve with cone.
Fire pump
Centrifugal Pumps.
Connection between drive and pump by coupling.
6.5.1.1 Separately coupled–type pumps with electric motor drivers shall
be connected by a flexible coupling or flexible connecting shaft.
2.4.5 Mechanical Seals FM FMDS0307
2.4.5.1 Only use pumps that have been specifically FM Approved for use with
mechanical shaft seals.
2.4.5.2 Only use pumps equipped with mechanical seals in systems that meet the
following criteria:
1) The suction source water is clean. Do not use pumps with mechanical seals in
systems where any water source is an open body of water (e.g., retention pond, lake,
or river).
2) The suction pressure is positive under all conditions of pump flow.
3) A spare split mechanical seal set is maintained on site.
4) Weekly testing of the pump is conducted.
Fire pump
Centrifugal Pumps. Performance curve.
Fire pump
Centrifugal Pumps. Performance curve.
Fire pump
Centrifugal Pumps. Suction line.
1- vortex plate.
4.14.10* Anti-Vortex Plate. Where a tank
is used as the suction source for a fire
pump, the discharge outlet of the tank
Shall be equipped with an assembly
that controls vortex flow in accordance
with NFPA 22.
Fire pump
Centrifugal Pumps. Suction line.
4.14.8* Suction Screening.
4.14.8.1 Where the water supply is obtained from an open source such as a pond or
wet pit, the passage of materials that might clog the pump shall be obstructed.
4.14.8.4 Below minimum water level, these screens shall have an effective net area of
opening of 1 in.2 for each 1 gpm (170 mm2 for each 1 L/min) at 150 percent of rated
pump capacity.
4.14.8.6 Mesh screens shall be brass, copper, Monel, stainless steel, or other
equivalent corrosion-resistant metallic material wire screen of 0.50 in. (12.7 mm)
maximum mesh and No. 10 B&S gauge.
4.14.8.11 Screens shall have at least 62.5 percent open area
Fire pump
Centrifugal Pumps. Suction line.
2- OS&Y Gate Valve – 4.14.5.1
The OS&Y gate valve in the suction piping of a fire pump serves two purposes. As
liquid flows into a fire pump, it needs to be as free of turbulence as possible, to avoid
introducing air pockets into the impeller and to avoid imbalanced loads on the
impeller. When a gate valve is in the fully open position, the clapper is retracted into
the body of the valve, leaving the liquid passageway clear of any obstruction and
effectively enabling laminar flow. The OS&Y Valve also provides a way to isolate the
fire pump from the liquid supply so a repair(s) can be made to the fire pump.
Fire pump
Centrifugal Pumps. Suction line.
2. Eccentric Reducer (Pump Suction) – 4.14.6.4
An eccentric reducer is used on the suction side of a fire pump assembly to reduce the
likelihood of air pockets entering the pump impeller. In most pump installations, the
suction pipe is larger than the pump suction opening; an eccentric reducer installed
with the flat side on the top is used to reduce the suction size pipe to match the pump
suction opening. If the suction pipe is the same as the pump suction opening, a
reducer is not required.
3. Pressure Gauge – 4.10.1
When there is a possibility of a suction pressure below 20 psi, the suction pressure
gauge is required to be a compound gauge capable of registering negative pressures.
This gauge provides the pump operator the ability to monitor the suction pressure to
assure that operating pressures comply with Section 4.14.3.1, which — except when
taking suction from a tank — does not permit the suction pressure to drop below 0 psi
while the pump is operating at 150 percent of its rated capacity. If a fire pump starts
to draw a negative suction pressure, there is a possibility that both the fire pump and
the suction piping could cavitate.
Fire pump
Centrifugal Pumps. Discharge line.
1- check valve
2- os & y gate valve.
3-relief valve in diesel pump
4.20.2.5 For non hydraulically sized piping, the minimum size meter for a given
pump capacity shall be permitted to be used where the meter system piping
does not exceed 100 ft (30.5 m) equivalent length.
4.20.2.6 For non hydraulically sized piping, where meter system piping exceeds
100 ft (30.5 m), including length of straight pipe plus equivalent length in
fittings, elevation, and loss through meter, the next larger size of piping shall
be used to minimize friction loss.
Fire pump
Centrifugal Pumps.
4.20.3 Hose Valves.
A.4.20.3.1 The hose valves should be attached to a header or manifold and connected
by suitable piping to the pump discharge piping. The connection point should be
between the discharge check valve and the discharge gate valve. Hose valves should
be located to avoid any possible water damage to the pump driver or controller
4.20.3.1.2 The number and size of hose valves used for pump testing shall be
as specified in Section 4.26.
4.20.3.3.1 A listed indicating butterfly or gate valve shall be located in the pipeline to
the hose valve header
(1) Where the pipe between the hose valve header and the connection to the pump
discharge pipe is over 15 ft (4.5 m) in length, the next larger pipe size than that requir
ed by 4.20.3.1.3 shall be used.
Fire pump
Centrifugal Pumps.
4.25* Pressure Maintenance (Jockey or Make-Up) Pumps.
4.25.1.1* The pressure maintenance pump shall be sized to replenish the fire
protection system pressure due to allowable leakage and normal drops in pressure.
***For situations where the pressure maintenance pump serves only aboveground
piping for fire sprinkler and standpipe systems, the pressure maintenance pump
should be sized to provide a flow less than a single fire sprinkler.
The main fire pump should start and run (providing a pump running signal) for any
water flow situation where a sprinkler has opened, which will not happen if the
pressure maintenance pump is too large. One guideline that has been successfully
used to size pressure maintenance pumps is to select a pump that will make up the
allowable leakage rate in 10 minutes or 1 gpm (3.8 L/min), whichever is larger
4.25.2 Pressure maintenance pumps shall have rated capacities not less than any
normal leakage rate.
4.25.3 Pressure maintenance pumps shall have discharge pressure sufficient to
maintain the desired fire protection system pressure.
Fire pump
Centrifugal Pumps.
4.25* Pressure Maintenance (Jockey or Make-Up) Pumps.
RULE OF thumb : stationary fire pump , 2013 page 134
A general rule of thumb for sizing jockey pumps supplying underground piping has
been to use 1 percent of the fire pump rated capacity and add 10 psi (0.7 bar) to the
pressure rating of the fire pump.
For example, a fire pump with a rated capacity of 1000 gpm at 100 psi (3785 L/min at
6.9 bar) should be provided with a jockey pump of 10 gpm at 110 psi (37.8 L/min at 7.6
bar) rated capacity.
An exception to this general rule is when older underground systems leak excessively.
In such a case, the jockey pump capacity should be increased further, based on the
leakage rate of the underground system
Fire pump
Centrifugal Pumps.
4.25* Pressure Maintenance (Jockey or Make-Up) Pumps.
4.25.5 Piping and Components for Pressure Maintenance Pumps.
4.25.5.3 An isolation valve shall be installed on the suction side of the pressure
maintenance pump to isolate the pump for repair.
4.25.5.4 A check valve and isolation valve shall be installed in the discharge pipe.
Fire pump
Centrifugal Pumps.
Sensing line . Page 73
4.30* Pressure Actuated Controller Pressure Sensing Lines
4.30.1 For all pump installations, including jockey pumps, each
controller shall have its own individual pressure sensing line.
4.30.2 The pressure sensing line connection for each pump, including
jockey pumps, shall be made between that pump’s discharge check
valve and discharge isolation valve.
4.30.3* The pressure sensing line shall be brass, rigid copper pipe Types
K, L, or M, or Series 300 stainless steel pipe or tube, and the fittings shall
be of 1⁄2 in. (15 mm) nominal size.
Fire pump
Centrifugal Pumps.
Control.
10.5.2.5.3 If water requirements call for more than one pumping unit to operate, the units
shall start at intervals of 5 to 10 seconds.
Pump starting.
NFPA 14 , 2013 page 98 A.14.2.6 (4)
Jockey stop = churn + static
Jockey start less jockey stop by 10 psi
Fire pump start less jockey start 5 psi
Use 10 psi increment for any additional pump
FM FMDS0307 page 14 2.6.4.5
1. The jockey pump start point equals the pump pressure at churn (zero flow) plus the maximum
static pump suction pressure plus 5 psi. Jockey start = churn + sattic + 5
2. The jockey pump stop point is 10 psi (70 kPa) more than the jockey pump start point.
Jockey stop mor jockey start by 10 psi
3. The fire pump start point is 5-10 psi (35-70 kPa) less than the jockey pump start point. Use 10
psi (70 kPa) decrements for each additional pump start.
Fire pump start 5- 10 psi less than jockey start
Fire pump
Centrifugal Pumps.
Control.
Example pump have 1000 gpm 80 psi churn pressure 95 psi , suction static pressure 60 psi
NFPA FM
Jockey start 145 160
Jockey stop 155 170
1st fir pump start 135 155
2nd fire pump start 125 145
FIRE TANK
Vent pipe
14.4.2 The means to fill the tank shall be sized to fill the tank in a maximum time of 8 hours
13.4.2.2 The filling pipe shall be of at least 50 mm (2 in.) and, except as noted in 13.4.3,
shall be connected directly into the tank discharge pipe, in which case a listed indicating
control valve and a check valve shall be placed in the filling pipe near the tank discharge
pipe, with the check valve located on the pump side of the listed indicating valve.
FIRE TANK
Over flow
13.5.1 Size. The overflow pipe shall be of adequate capacity for the operating conditions
and shall be of not less than 75 mm (3 in.) throughout
13.5.2.1 The inlet of the overflow pipe shall be located at the top capacity line or high
waterline.
13.5.2.2 The inlet also shall be located at least 25 mm (1 in.) below the bottom of the flat
cover joists in a wood tank, but shall never be closer than 50 mm (2 in.) to the top of the tank.
13.5.2.3 Unless the maximum fill capacity is known and the overflow capacity is calculated
to be at least equal to the fill capacity, the overflow pipe shall be at least one pipe size
larger than the fill line and shall be equipped with an inlet such as a concentric reducer, or
equivalent, that is at least 50 mm (2 in.) larger in diameter.
13.5.2.4 The inlet shall be arranged so that the flow of water is not retarded by any
obstruction.
FIRE TANK
Riser Drain.
13.6.4.1 A drain pipe of at least 50 mm (2 in.) that is fitted with a controlling valve and a
12-mm (½-in.) drip valve shall be connected into the tank discharge pipe near its base and,
where possible, on the tank side of all valves.