CSC-2000(V2)

Substation Automation System


Main Content
1 Overview of SAS CSC2000
2 Local SCADA(HMI)
3 Gateway CSC-1320
4 BCU CSI-200E
5 Protection IED and network
1 Overview of CSC2000 SAS
 System Architecture
 System Feature
 Communication Network and Protocol
http://www.sifang-electric.com
1 Overview of CSC2000 SAS
1.1 System Architecture
Satellite
Remote Control
Center
Network/
PLC/
Microwave

GPS Clock
Operator Operator Engineer
Workstation 1 Workstation 2 Workstation
PPS/ SNTP Printer
IRIG-B

Gateway1 Gateway2

Ethernet 1
 Station level IEC61850 Ethernet 2

 HMI
 Engineer WS
 Gateway Protection
Gateway

 Bay level HV/MV Line Transformer LV Line


 Protection IED
Bus
HV/MV BCU Protection Protection Protection IEC103,DNP,MODBUS
Protection

 BCU: Measurement/Control
 Network and communication standard
 Fast industry Ethernet(100/1000M) Protection from other venders

 IEC61850 and non- IEC61850 protocol


1 Overview of CSC2000 SAS

1.2 System Feature (1)


 The first distributed SAS in China.
 Over 3000 CSC2000 systems installed and running in
China and other countries, the voltage level range from
35kV to 1000kV.
 It was awarded Chinese SSTPA (State Scientific and
Technological Progress Award, the highest award by
Chinese government) in 2003.
 All the IED get the IEC 61850 certificate of KEMA in Jan.
2008. include CSI-200EA, CSC-101, CSC-161, CSC-326, CSC-
150, CSC-211.
1 Overview of CSC2000 SAS
1.2 System Feature (2)

Medal of SSTPA
1 Overview of CSC2000 SAS
1.2 System Feature (3)

CSI-200EA
CSC- 101
CSC-161
CSC-326
CSC-150
CSC-211

IEC 61850 certificate of KEMA


Products & Solutions
1 Overview of CSC2000 SAS

1.2 System Feature (4)


 Distributed system, bay oriented
 Maintain conveniently, high reliability, easy to extend
 Support IEC61850 and non-IEC61850 at the same time
 Gateway of station level based on embedded hardware
and real-time OS
 HMI on station level can support Windows/LINUX/UNIX
OS and 32/64 bit hardware
 Device of bay level based on common modular hardware
which can be configured freely according to the
requirement
 Redundancy technology is used in the system:
mainframe (SCADA server, gateway), network,
 Advanced application: Sequence control, AVQC
1 Overview of CSC2000 SAS

1.3 Communication Network and Protocol


 Fast Industry Ethernet 100/1000M
 Double bus (star) topology for electronic and optical
Ethernet
 IEC 61850 and CSC 2000 protocol
 Other protocol (IEC 60870-5-103, DNP, Modbus/TCP,
Modbus/RTU) connect to SAS via gateway
2 Local SCADA (HMI)
 Composition of Local SCADA
 Multiple Platform (OS, hardware)
 IEC 61850
 SCADA
 Protection Relay Management
 AVQC
CSC-2000 Substation Automation
Scada system(V2)
2 Local SCADA (HMI)

 Composition of Local SCADA


 Data Server
 Operation Workstation
 Engineer Workstation
 Protection Engineer Workstation
 Advanced Application Workstation: AVQC
2 Local SCADA (HMI)

 Support multiple OS
 UNIX(Solaris/AIX)
 Linux(RedHat/Suse/RedFlag, etc)
 Windows
 Support multiple hardware platform
 SUN/IBM 64 bit UNIX workstation /server
 DELL 、HP、IBM 32 bit PC workstation/server
 Advantech、SIEMENS 32bit Industrial computer
 Support multiple database
 Oracle, MS SQL Server, PostgreSQL
2 Local SCADA (HMI)

 Support IEC61850 and compatible with non-IEC61850 protocol


 CSC2000
 Single line diagram (SLD)
 Topology analysis and dynamic color
 Distributed real time database
 Event and alarm
 alarm text (flash)
 human voice
 printing
 beep or ring
 sending short message (SMS) to cell phone
 Report and trend
 Printing report automatically
 Real time trend
2 Local SCADA (HMI)

 Control
 Authorized operation
 Select before operate (SBO)
 Interlocking function (Station level and bay level)
 Sequence control
 Two-seat control mode: monitor and operator
 Card verifying mode
 Finger print verifying mode (must record 2 finger’s print at least)
 Protection relay management
 Relay setting
 Disturbance recording analysis (COMTRADE file)
2 Local SCADA (HMI)

 AVQC: voltage and reactive power control.


 No restriction to the number of controllable equipment
 Automatic topology
 Configurable parameter
Database
drawing
History report
3 Gateway CSC-1320

 Main Feature
 Hardware
 Scope of Application
 Other Type of Gateway
3 Gateway CSC-1320
3 Gateway CSC-1320
3.1 Main Feature
 4U, 19 inches device / IEC60297-3 standard.
 Based on 32-bit CPU, embedded hardware platform, no
hard disk, no cooling fan, low power consumption.
 Based on embedded real time OS.
 Distributed architecture, multiple plug-in, connected with
industry Ethernet and CAN field bus.
 Communication interfaces can be expanded with plug-in.
 Class 4 of EMC for main items of IEC 61000-4.
 IEC 61850 standard as the station level protocol, also
support private protocol of CSC2000
 Friendly HMI with key and LCD, tools for configuration
and debug.
3 Gateway CSC-1320
3.2 Hardware
 Main CPU, 32 bit CPU
 Ethernet, 32 bit CPU
 Serial port, 32 bit CPU
 DIO, 16 bit CPU
 Synchronize, 16 bit CPU MMI

 Extend, switch Ethernet

 MMI, 16 bit CPU, 4 arrow CAN

key, 3 function key, LCD,


5 indication lamp

synchronize
Main CPU

Serial Port
Ethernet

Extend
DIO
 Networked
 Distributed
 Modularized
Block diagram of system hardware
 Extensible and open
3 Gateway CSC-1320
3.3 Scope of application
 The goal of the CSC-1320 serial product: general protocol
process.
 Gateway of station level: CSC-1321, data exchange with
RCC (Remote Control Center), protocol: IEC 60870-5-101,
IEC 60870-5-104, SC 1801, DNP. Typical Configuration:
 1 main CPU
 1 Ethernet for IEC 61850 to connect IED
 1 Ethernet for IEC 60870-5-104 to RCC
 1 Serial port for IEC 60870-5-101 to RCC
 1 Synchronize for GPS
 Gateway of bay level: CSC-1322, integrate IED from 3rd
part, we can also use other type of gateway include: CSC
1312B, CSM320E, protocol: IEC 60870-5-103, Modbus,
IEC 60870-5-101, IEC 60870-5-104.
3 Gateway CSC-1320
3.4 Other type of bay level gateway

CSC 1312B

CSM 320E
4 BCU CSI-200E
 Hardware
 Main Function
4 BCU CSI-200E
Sifang CSI-200E
4 BCU CSI-200E
4.1 Hardware architecture
 Modular design
 Intelligent HMI

 Data bus within device MASTER COM


Data Bus

CPU CPU
DI DO
A/D A/D

PT/CT signal trip


4 BCU CSI-200E
4.2 Main Function
 Data acquisition: AI, DI, Tap Position
 Remote control and Local control: DO
 Hardware module can be configured freely
 PLC: Interlock, CB synchronization
 Large LCD MMI with bay diagram
 Communication with HMI and Gateway, support
IEC61850, IEC60870-5-103 and CSC2000 protocol.
5 CSC Serial Protection IED
5 CSC Serial Protection IED

 CSC-100 Series High Voltage Line Protection Relay


 CSC-160 Series M/L Voltage Line Protection Relay
 CSC-326 Series Transformer Protection Relay
 CSC-150 Series Bus bar Protection Relay
 CSC-330 Series Reactor Protection Relay
 CSC-300 Series Generation Protection Relay

 Communication with HMI and Gateway, support


IEC61850, IEC60870-5-103, CSC2000 protocol
overcurrent protection
protection backboard of map
6 Typical Configuration of SAS
 Concentric Configuration
 Distributed Configuration
6 Typical Configuration of SAS
6.1 Concentric Configuration

RCC

satellite
WAN

Channel Switch
GPS
OWS 1 OWS 2 Protection WS VQC Fail Safe WS
Station Level
Gateway

Ethernet 1
PPM/ IEC 61850 / CSC2000
PPM/
Ethernet 2
IRIG-B

Gateway Gateway Gateway

IEC60870-5-103 IEC60870-5-103 IEC60870-5-103


BCU Protection BCU BCU BCU & Protection BCU & Protection BCU
Protection Protection IED from 3rd part
Protection from 3rd part from 3rd part
Bay Level

Bay 1 Bay 2 Bay 3 Bay 1 Bay 2 Bay 3 Common Bay …

H/MV Bay LV Bay Common Bay

Concentrical SAS Configuration


6 Typical Configuration of SAS
6.2 Distributed Configuration

RCC
satellite
WAN

Channel Switch
GPS Control Room
OWS1 OWS2 Protection WS Engineer WS M/B SCADA Server VQC Fail Safe
Station Level Gateway

Ethernet 1
Ethernet 2 IEC 61850 / CSC2000

E/O E/O

Fiber Fiber Fiber Fiber

E/O E/O
GPS Extend GPS Extend

Ethernet 1 Ethernet 1
PPM/
Ethernet 2 Ethernet 2 PPS/
IRIG-B

Gateway Gateway Gateway

PPM/ IEC60870-5-103 IEC60870-5-103


PPS/ BCU Protection BCU Protection BCU Protection
IEC60870-5-103 BCU & Protection BCU & Protection
IRIG-B from 3rd part from 3rd part
Protection PPM/
from 3rd part PPS/
Bay Level IRIG-B

Bay 1 Bay 2 Bay 1 Bay 2 Bay 3 Common Bay …

H/MV room LV room Common Bay

Distributed SAS Configuration


7 Network Topology Compare
 Double Bus (Star) Topology
 Double Ring Topology
 Single Ring with Double Net in Station Level
7 Network Topology Compare
7.1 Double Bus (Star) Topology

HMI

Gateway

IED (BCU & Protection)

Double Bus (Star) Topology


7 Network Topology Compare
7.2 Double Ring Topology

HMI
Gateway

IED (BCU & Protection)

Double Ring Topology


7 Network Topology Compare
7.3 Single Ring with Double Net in Station Level

HMI
Gateway

IED (BCU & Protection)

Single Ring with Double Net in Station Level


Thank you,best wishes