Software Installation
1. Download software from the extranet
2. Install using Winload (how to ? See instruction on extranet)
3. Put unit parameters correct using the parameter list (extranet)

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 2
TOP SECRET
SECRET
INTERNAL USE ONLY

Menu controller PUBLIC

< A L A R M
< V I E W
< S E T T I N G S
< M A I N T

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 3
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

< A C T I V E
< L O G

< U N I T
< C O M P R E S S O R
< I / O

< A L A R M
< V I E W
< S E T T I N G S
< M A I N T
< U N I T
< C O M P R E S S O R
< U S E R
< A L A R M S
Previous menu:

< V I E W
< S E T T I N G S
< D E B U G

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 4
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Alarms  Active N o a l a r m
d e t e c t e d

1. Here you can find an active alarm


A L : 1 0 3 U : 1 A L : 1 1 3 U : 1
H i g h p r e s s u r e T r a n s i t i o n o r
s w i t c h a l a r m # 1 S o l i d S t a t e
A l a r m c o m p # 1

Alarms  Log
< A C T I V E
< L O G

• Here you can find the alarm log (last 10 alarms)


• With up and down you see which alarm occured at a certain
time 0 6 / 0 2 / 0 8 1 0 : 3 7

P D # 2 T i m e r E x p i r e d
0 4 / 0 2 / 0 8 1 3 : 2 4

E x p a n s i o n E r r o r
0 6 / 0 2 / 0 8 1 1 : 4 7

H i g h P r e s s . S w i t c h #
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ &1EWYD-BZ Service Training: 06 April 2018 5
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Alarms  Log
< A C T I V E 1 2 / 0 6 / 0 8 1 1 : 4 8
< L O G
E x p a n s i o n E r r o r

I n . W a t . T . 0 1 8 . 9 ° C
O u t W a t . T . 0 2 2 . 3 ° C

C o m p r e s s o r # 1 C o m p r e s s o r # 2
S u c t . P r e s 0 0 2 . 2 b a r S u c t . P r e s 0 0 1 . 2 b a r
D i s c . P r e s 0 1 0 . 2 b a r D i s c . P r e s 0 0 9 . 8 b a r
O i l P r e s 0 0 9 . 8 b a r O i l P r e s 0 1 0 . 0 b a r
C o m p r e s s o r # 1 C o m p r e s s o r # 2
E v a p . T e m p 0 0 3 . 2 ° C E v a p . T e m p - 0 0 6 . 9 ° C
S u c t . T e m p 0 0 0 . 0 ° C S u c t . T e m p 0 0 0 . 0 ° C

C o m p r e s s o r # 1 C o m p r e s s o r # 2
C o n d . T e m p 0 4 3 . 6 ° C C o n d . T e m p 0 4 2 . 2 ° C
D i s c . T e m p 0 7 8 . 7 ° C D i s c . T e m p 0 8 6 . 6 ° C

C o m p r e s s o r # 1 C o m p r e s s o r # 2
E X V S t e p s 0 0 0 0 E X V S t e p s 0 0 0 0
C o m p . L o a d 0 0 0 % C o m p . L o a d 0 0 0 %
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 6
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

View  Unit  Status 0 6 / 0 2


U n i t
/
S
0
t
8
a t u
W
s
e d
: X
1 0 : 2 4
X
N o C o m p A v a i l a b l e
S t p S o u r c e : L o c a l
1. Unit status
2. Actual setpoint 0
U
6
n
/ 0 2 /
i t S
0 8 W
t a t u s
e d
:
1 0 : 2 6

C o o l i n g S t a g i n g 0 3 0 %
3. Compressor 1 S t p S o u r c e : L o c a l

4. Compressor 2
C o m p r e s s o r # 1
5. Bios & Boot info
S t a t e M A N U A L
c o m p . # 1 l o a d 0 0 0 %

AUTO / MANUAL / OFF


Note: you can allways access Password: 02001
this menu by pressing enter

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 7
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC
W a t e r T e m p e r a t u r e s
View  Unit  Water E n t
L V G
E v a p
E v a p
0 1 7 . 0 ° C
0 1 3 . 0 ° C

1. Entering evaporator water temperature (B9)


2. Leaving evaporator water temperature (B10)

View  Unit  Evap


• Approach of circuit 1 and circuit 2

V i e w E v a p o r a t o r ( 0 1 ) V i e w E v a p o r a t o r ( 0 2 )
C i r c u i t # 1 C i r c u i t # 2
S u c t S H = S u c t S H =
A p p r o a c h = 0 1 1 . 3 ° C A p p r o a c h = 0 1 2 . 2 ° C

Approach = outlet water temp – evaporator saturated temp


All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 8
TOP SECRET
SECRET
C o m p . # 0 1 INTERNAL USE
C ONLY
PUBLIC

View  Compressor S t a t u s : A u t o 1 0 0 %

Change with  and  between compressor 1 and 2

Frequency and current


I n v e r t e r # 1

F r e q u e n c y 6 0 H z
C u r r e n t 0 9 5 A

Evaporator pressure & saturated temperature


Condensor pressure & saturated temperature
E v a p P r e s s 0 0 1 . 9 b a r g
E v a p T e m p 0 0 0 . 5 ° C
C o n d P r e s s 0 1 0 . 5 b a r g
C o n d T e m p 0 4 4 . 6 ° C

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 9
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

View  Compressor
Suction temperature, Suction SH, Discharge SH
S u c t i o n T e m p
S u c t S u p H e a t
D i s c S u p H e a t 0 2 5 . 4 ° C

Oil pressure & discharge temperature

O i l P r e s s 0 0 9 . 4 b a r
D i s c h . T . 0 0 7 1 . 9 ° C

Staging Up, Down, Fixed or compressor off


S t a g i n g U P
S t a g i n g D o w n
S t a g i n g F i x e d
C o m p r e s s o r O f f

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 10
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Compressor hour count & Number of starts


C o m p r e s s o r
H o u r c o u n t e r 0 0 0 0 0 0
N u m b e r o f
s t a r t s 0 0 0 0 0

Last compressor start & stop


L a s t c o m p . s t a r t
0 3 / 0 3 / 0 8 1 0 : 0 7
L a s t c o m p . s t o p
0 3 / 0 3 / 0 8 1 0 : 2 9

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 11
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC
D i g i t a l i n p u t s
View  I/O C
D
O
i
C
g
C
i
C
t
C
a
C C C C
l o u
C
t
C
p
C
u
C C C C C
t s
C C O O C C O O O O O C O O O O O O

A n a l o g I n p u t s :
1. Digital inputs
B 1 : O i l P r 1 0 0 9 . 0 b a r
2. Digital outputs B 2 : O i l P r 2 0 0 8 . 9 b a r

3. Analog inputs A n a l o g I n p u t s :
B 3 : L o w P r . 1 0 0 1 . 9 b a r
4. Analog outputs B 4 : D i s c h . T 1 0 6 9 . 3 ° C
B 5 : D i s c h . T 2 0 6 7 . 8 ° C
A n a l o g I n p u t s :
B 6 : C o n d P r 1 0 0 9 . 8 b a r
B 7 : C o n d P r 2 0 0 9 . 4 b a r
B 8 : L o w p r . 2 0 0 2 . 1 b a r
A n a l o g I n p u t s :
B 9 : I n W t r 0 1 7 . 2 ° C
B 1 0 : O u t W t r 0 1 3 . 6 ° C

A n a l o g O u t p u t s

Y 1 : 1 0 . 0 V
Y 2 : 0 6 . 7 V

A n a l o g O u t p u t s

Y 4 : 0 0 . 0 V
All Seasons °
CLIMATE COMFORT Y 5Service
Daikin EWAD-BZ & EWYD-BZ : Training: 0 060April
. 2018
0 V 12
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

View  I/O  1x right


I / O e x p B
B 1 : O A T 0 1 2 . 8 ° C
B 2 :
B 3 : C u r r . # 1 0 9 0 A

1. B1: ambient temperature


2. B2: none (not used)
3. B3: Current inverter #1

The current comes as a 0-5V signal from the inverter.


0V = min. absorbed current probe limit
5V = max. absorbed current probe limit

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 13
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

View  I/O  1x right


I / O e x p B
B 4 : C u r r . # 2 0 8 4 A
D I 1 : H / C S w i t c h H
D I 2 : O v b o o s t N

1. B4: Current inverter #2


2. DI1: Heating / Cooling switch (only visible in EWYD)
3. DI2: Overboost function for the inverter

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 14
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Overboost
Maximum
capacity

150 % 90 Hz

100 % 60 Hz
Ambient
-10 °C 6 °C

I / O e x p B I n v e r t e r o v e r b o o s t
B 1 : O A T 0 0 5 . 6 ° C O v e r b o o s t
B 2 : O v e r b . b y T a m b
B 3 : C u r r . # 1 0 2 2 A M a x C a p a c i t y 1 0 2 %
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 15
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

View  I/O  1x right


I / O e x p B

D I 3 : M a x V F D 1 O
D I 4 : M a x V F D 2 O

1. DI3: Max VFD Inverter #1


2. DI4: Max VFD Inverter #2

This is a limitation signal from the inverters

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 16
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

View  I/O  1x right


I / O e x p B
D O 1 : 4 W v a l v e # 1 Y
D O 2 : S . L i q i n j # 1 N
D O 3 : 4 W v a l v e # 2 Y

1. DO1: 4-way valve signal (cooling – heating) #1


2. DO2: Liquid injection #1
3. DO3: 4-way valve signal (cooling – heating) #2

4. Settings  Unit  Setpoint

L I . D i s c s t p 0 8 5 . 0 ° C
L I . D i s c D i f 0 1 0 . 0 ° C
L I . S u c t s t p 0 3 5 . 0 ° C
L I . S u c t d i f 0 0 5 . 0 ° C

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 17
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

View  I/O  1x right


I / O e x p B
D O 4 : S . L i q i n j # 2 Y
A O 1 : H P V a l v e 0 0 . 0 V

1. DO4: Liquid injection #2


2. AO1: not used

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 18
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Configuration


1. Expansion valve (simulation board: Thermostatic) + Gas type
2. Number of compressors
3. Number of fan steps
4. Low pressure transducer limits
5. Absorbed current probe limits
A b s o r b e d c u r r e n t
p r o b e l i m i t s I n v . # 1
M i n . 0 0 0 . 0 A
M a x . 2 3 0 . 0 A

1. B3 and B4 on the expansion board react on a analog signal of 0-5V.


2. 0V is set to 0A
3. 5V is set to 230A (or 300A)

230A for compressors 3118 and 3120


300A for compressors 3121, 3122 & 3123
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 19
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Configuration


Condensation:
C o n d e n s a t i o n
C o n t r o l v a r . P R E S .
T y p e F A N T R

• Control variable is always Pressure


• Type:
• Speedtr: 1 phase cut fan, rest normal on/off fans
• VSD: all phase cut fans
• Fantr: all on/off fans (every fan = step)

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 20
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Configuration


1. Oil heating (Y)  must be on 12h before commissioning !!!
2. No fault apears when oil heating is not OK
3. Check at compressor status screen
E n a b l e O i l H e a t i n g C o m p . # 0 1
c o n t r o l Y
S t a t u s : O i l H e a t i n g

Measured to check oil filter

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 21
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Configuration


1. Delay between cooling & heating
2. RS485
3. Expansion board configuration (if connected)
4. Autorestart after power failure
5. Switch off unit on external alarm (expansion board 4, DI 2)
6. Reset all parameters to default values (allways do this after
replacing the controller)
7. Password technician (don’t change !!!)

01331 07211

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 22
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Setpoint


Temperature regulation: Derivation time (60s)

Prepurge
L i q u i d L i n e C l o s e
T i m e ( P r e p u r g e )
C o o l i n g 0 1 0 s
H e a t i n g 0 1 0 s

The Electronic Expansion Valve stays closed for the first 10 sec

Downloading time (time to bring the compressor to minimum


capacity before compressor stop).

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 23
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Setpoint


Pump down (all refrigerant in condenser after unit stop)

P u m p d o w n r e g i m e
V S D s p e e d 4 5 . 0 %

Pump off delay (180 sec)

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 24
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Liquid injection
1. Liquid injection when discharge temperature becomes too
high

L I . D i s c s t p 0 8 5 . 0 ° C
L I . D i s c D i f 0 1 0 . 0 ° C

°C

On 85°C

Off 75°C = 85 - 10

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 25
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Setpoint


Low ambient start procedure
L o w A m b i e n t P a r a m .
C o n d . T t h r 0 1 5 . 5 ° C
L . A m b . T i m e r 1 2 0 s e c

If the condensor T is lower then 15,5°C, the


compressor stays at minimum capacity the
first 120 sec.

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 26
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Liquid injection
L I . D i s c s t p 0 8 5 . 0 ° C
L I . D i s c D i f 0 1 0 . 0 ° C

Liquid injection

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 27
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Setpoint


D e f r o s t p a r a m e t e r s
S t a r t u p T 0 0 1 8 0 s
D e f r . I n t . 0 1 8 0 0 s
D e f r . P a r a m . 1 0 ° C

1. If Suction Temperature < 0,7 x Ambient – 10°C


for 180s  DEFROST
1. 10 °C = design approach temperature

Min 1800s = 30min between 2 Defrost cycles

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 28
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Setpoint


D e f r o s t p a r a m e t e r s
S s h T H R 0 1 0 . 0 ° C
A M B T T H R 0 2 0 . 0 ° C
S u c t T T H R 0 0 0 . 0 ° C

1. If the Suction SuperHeat is lower then 10°C


2. And the Ambient Temperature is lower then 20°C
3. And the Suction Temperature is lower then 0°C
4. DEFROST is possible

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 29
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Setpoint


D e f r o s t p a r a m e t e r s
L W T f a i l T 0 1 2 . 0 ° C
C o o l M o d e t i m e 6 0 0 s
H P l i m i t 0 0 1 4 . 0 b a r

1. If the Leaving Water Temperature goes below 12°C,


the defrost stops immediately.
2. Cool mode Defrost can take 600s maximum
3. The HP limit is 14 bar (55°C): When this is reached,
the unit starts 2 fans. When the condensing
temperature drops to 45°C, the fans stop again.

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 30
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Setpoint


D e f r o s t p a r a m e t e r s
C o o l i n g m o d e
R e g i m e s p e e d 6 0 . 0 %
M i n E n d u r a n c e 0 6 0 s

1. Circuit in defrost runs at 60% of 90Hz = 54Hz


2. The minimum endurance is the time that the defrost
stays at maximum capacity: 60 sec.

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 31
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Setpoint


D e f r o s t P a r a m e t e r s
C o m p r e s s o r p a u s e
S t a r t i n g 0 6 0 s
E n d i n g 0 6 0 s

1. 60s pause for the changeover of the 4-way valve


2. After defrost, the compressor stops for 60s.

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 32
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Condensation


C o n d e n s a t i o n
S e t p o i n t 0 4 0 . 0 ° C
1. Condensation setpoint (40°C)
2. Fantroll setpoint
F a n t r o l l S e t P s

S t a g e U P E r r . 1 0 . 0 ° C
S t a g e D W E r r . 1 0 . 0 ° C

Stage up when 10,0°C . sec


Stage down when 10,0°C . sec

example 10°C in 1 sec


5°C in 2 sec
1°C in 10 sec

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 33
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Condensation


F a n t r o l l S e t P s
D e a d b a n d n . 1 40 + 3 = 43 °C
S t a g e U p 0 0 3 . 0 ° C
S t a g e D o w n . 0 1 0 . 0 ° C 40 – 10 = 30 °C
F a n t r o l l S e t P s
D
S
e
t
a
a
d
g e
b a n d
U p
n . 2
0 0 6 . 0 ° C
40 + 6 = 46 °C
S t a g e D o w n . 0 0 6 . 0 ° C
40 – 6 = 34 °C
F a n t r o l l S e t P s
D e a d b a n d n . 3
S t a g e U p 0 1 0 . 0 ° C 40 + 10 = 50 °C
S t a g e D o w n . 0 0 3 . 0 ° C
40 – 3 = 37 °C

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 34
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Condensation Condensation


set-point

Step 3

Step 2

Step 1

30 34 37 40 43 46 50 °C

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 35
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Condensation

1°C in 2°C in 5
10 sec sec
10°C .
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 36
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Condensation


1. VSD configuration (inverter)
V S D c o n f i g .
M a x . s p e e d 1 0 . 0 V
M i n . s p e e d 0 0 . 0 V
S p e e d u p t i m e 0 0 s

2. Condensation regulation VSD 01 sec


!!!
C o n d . R e g u l a t i o n V S D

R e g . B a n d 0 2 0 . 0 ° C
N e u t . B a n d 0 0 1 . 0 ° C

C o n d . R e g u l a t i o n V S D
I n t . T i m e 1 5 0 s
D e r . T i m e 0 0 1 s

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 37
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Unit  Condensation  Evaporation

E v a p o r a t i o n
S e t p o i n t 0 1 0 . 0 ° C

Similar as condensation

< C O N D E N S A T I O N
< E V A P O R A T I O N

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 38
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Compressor
– Antirecycling timer (minimum time between the starts of the same compressor).

1. Timers – Mininimum time between 2 different compressors starts.


– Minimum operating time compressor.
– Guard timer of compressor (minimum compressor OFF time).

2. Interstage timer: thermostat control (120s)


3. Evaporator temperature hold, down

L o w p r e s s u r e
H o l d T . - 0 0 3 . 0 ° C
D o w n T . - 0 0 4 . 0 ° C
D o w n d e l a y 0 2 0 s

4. High pressure hold, down

H i g h p r e s s u r e
H o l d T . 0 6 0 . 0 ° C
D o w n T . 0 6 5 . 0 ° C

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 39
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Compressor
C o m p r e s s o r s m i n .
s p e e d 2 5 . 0 %

The compressor minimum speed is 33% => 30Hz.

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 40
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Compressor
I n v e r t e r n o m i n a l
s p e e d
S u m m e r 6 7 . 0 %
W i n t e r 6 7 . 0 %

1. Nominal inverter speed: 67% of 90 Hz = 60 Hz


2. Faster then normal 50 Hz to achieve more capacity

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 41
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Compressor
I n v e r t e r F L A m a x
( O A T < 4 0 ° C )
I n v . # 1 1 0 5 . 0 A
I n v . # 2 1 0 5 . 0 A

1. When the ambient temperature is lower then 40 C, the


inverters are limited to 105A / 140A / 170A.

105A for compressors 3118 and 3120


140A for compressors 3121 and 3122
170A for compressors 3123

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 42
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Compressor
F L A a m b . t e m p c o m p .
f a c t o r 9 5 . 0 %

1. The compressor is limited to 105A or 140A if the


ambient temperature is lower then 40°C
2. If the ambient temperature is higher then 40°C, the
compressor is limited to 95% of 105A or 140A, so 100A
or 133A

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 43
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Compressor
S t a g e h o l d d i f f . %
t o s t a r t r e l o a d i n g
D i f f . 1 0 . 0 %

1. If the ambient temperature is higher then 40°C, the inverter


current is limited to 95%.
2. The current has to drop 10%, before the compressor reloads

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 44
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Compressor
S t a g e d o w n % o f f s e t
F L A m i n .
C o m p r e s s o r # 1 5 . 0 %
C o m p r e s s o r # 2 5 . 0 %

1. If the ambient temperature is lower then 40°C, the inverter


current is limited to 105A or 140A
2. If the current is higher then 105A + 5,0% or 140A + 5,0%
the compressor loads down

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 45
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Compressor
Discharge SH protection:

D i s . S H T H R 0 0 1 . 0 ° C
d i s c h S H T 0 3 0 s e c

1. Condition:
– Only control during start up of compressor.
– If Discharge superheat is < then 1°C for 30 sec.

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 46
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Compressor
L o a d / U n l o a d s p e e d
v a r i a t i o n p e r c .
L o a d 2 . 0 %
U n l o a d 2 . 0 %

1. Instead of different solenoid steps, the inverter uses


frequency steps of 2,0%
2. 2,0% of 90 Hz = 1,8 Hz

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 47
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Compressor
L o a d i n g

M i n p u l s e p e r . 0 1 0 s
M a x p u l s e p e r . 1 5 0 s

U n l o a d i n g

M i n p u l s e p e r . 0 0 1 s
M a x p u l s e p e r . 1 5 0 s

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 48
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Compressor management control


Pulse time
L
P
o
u
a d i n g
l s e t i m e 0 0 . 1 s
A pure proportional logic, will load
M
M
i
a
n
x
p u l s e
p u l s e
p e r . 0 3 0 s
p e r . 1 5 0 s
or unload with a frequence related
to the set-point distance.
Minimum loading pulse
time

Max loading pulse


time

No pulse,
stand-by
Evap water leaving
Max unloading pulse Set Point
time

Minimum unloading
pulse time Dead band

Regulation band

U n l o a d i n g
P u l s e t i m e 0 0 . 3 s
M i n p u l s e p e r . 0 0 1 s
M a x Seasons
All p u ° l s eCOMFORT
CLIMATE p e r . 1 5 0 s Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 49
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

PID control

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 50
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

PID control
1. P: Measures the difference between setpoint and actual
value (error value)
2. The bigger the error value, the more the controller reacts

3. I: Measures the duration of the error value


4. The longer the error takes, the more the controller reacts

5. D: Fast reaction on error variatons (for instance because of a


sudden load change)

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 51
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

PID control
1. Example: setpoint = 7 & LWT = 16

P: 16 – 7 = 9 big difference: all compressors to 100%

P: Measures the difference between setpoint and actual value


(error value)
The bigger the error value, the more the controller reacts
The bigger the error value, the smaller the pulse interval

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 52
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

PID control
1. Example: setpoint = 7 & LWT = 8

P: 8 – 7 = 1 small difference: compressors at 25%


(example)
(not at startup >9,7)
LWT stays at 8 for 2 minutes (example)
I: long duration of error value compressors load up (>25%)

I: Measures the duration of the error value


The longer the error takes, the more the controller reacts
The longer the error takes, the smaller the pulse interval

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 53
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

PID control
1. Example: setpoint = 7 & LWT = 18

P: 18 – 7 = 11 big difference: all compressors to 100%

after 1 min: LWT = 10

D: fast error variation (18  10 in 1 min) (example)

D reduces compressors to 50% (example) to avoid LWT to drop


below setpoint of 7

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 54
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Compressor management control


1. Principal

Shut down DT Start up DT

This value can be changed


All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 55
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Compressor management control


1. Principal

Regulation band

This value can be changed


All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 56
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Compressor management control


Dead
1. Principal
band

This value can be changed


All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 57
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Compressor management control


1. Principal

DT DT
reloadunlo
ad

This DT can be changed


All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 58
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Compressor management control


1. Maximum pull down rate:

1. Water can only drop a certain °C per minute.

1. For example 0.7°C / minute

2. If decrease of water is higher, compressor will limit capacity

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 59
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Compressor management control


1. Inter-stage timer (120 s):
1. Time required to decide if second compressor will start.
2. Area where inter-stage timer is active

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 60
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Compressor management control


1. Compressor rotation management
1. 2 possibilities:
1. Automatic rotation
2. Manual rotation

C o m p r e s s o r s
s e q u e n c i n g
M A N U A L

S e t c o m p . s t a g e
C # 1 1 s t C # 2 2 n d

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 61
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Compressor stopping sequence


1. Pump down control:
1. Activation of the pump down function can be selected in the set point
menu.
2. Active when temperature reached or stop the unit with ON / OFF bottom.

2. How:
1. Electronic expansion valve: close valve.
2. Thermostatic expansion valve: close liquid valve.

3. Result:
1. Pump down finished
2. Pump down failed P u m p d o w n c o n f i g .
E n a b l e Y
M a x t i m e 1 2 0 s
M i n P r e s s 0 1 . 0 b a r g

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 62
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Compressor management control


1. Manual control
1. Can be used to operate the compressor in a certain capacity step.
2. No temperature control available
3. All safeties are active
4. If safety activated unit returns to automatic mode
5. If safety on one circuit, this circuit goes in safety. The other circuit
remains in manual

VIEW  UNIT  STATUS


2/3 x
ENTER
Manager password: 02001
Set to MANUAL (also possible: set to OFF)
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 63
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  User  Setpoints


C o o l i n g s e t p o i n t
0 0 7 . 0 ° C
H e a t i n g s e t p o i n t
0 0 4 5 . 0 ° C

When the unit is in heating

E n a b l e D o u b l e
s e t p o i n t Y

C o o l i n g d o u b l e
s e t p o i n t 0 1 2 . 0 ° C
H
s
e
e
a
t
t
p
i
o
n
i
g
n t
d o u b l e
- - - - ° C
Change double setpoint with
DI 5

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 64
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  User  Setpoints


L v g W a t e r T e m p .
s e t p o i n t r e s e t

N O N E

1. None (standard outlet control)


2. Return (inlet control by formula)
3. 4-20mA (analog input)
4. OAT (floating setpoint => ambient)

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 65
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Set point management


1. 4 – 20 mA setpoint control L v g W a t e r
s e t p o i n t
T e m p .
r e s e t

4 - 2 0 m A

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 66
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Set point management


L v g W a t e r T e m p .
1. Floating set point s e t p o i n t r e s e t

O A T

10°

35°

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 67
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Set point management


1. Floating set point

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 68
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  User  Setpoints


W o r k i n g m o d e
C o o l i n g

• Ice mode:
1. Cooling Cooling ice during the night.
2. Glycol Compressor 100 %  0 % in 1 step.
3. Ice 0 %  100 % in steps. (overheating protection)

• Glycol mode:
Normal operation with glycol (LWT down to -8).
Standard compressor load-up and load-down.

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 69
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Operation modes

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 70
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  User  Setpoints


E n a b l e S o f t l o a d N

E n a b l e S o f t l o a d Y
M a x s t a g e 0 5 0 %
M a x T i m e 0 2 0 m i n

The compressors stay at 50% for 20 min after startup

E n . A m b . L o c k o u t
Y
S e t p o i n t 0 0 5 . 0 ° C
D i f f 0 0 1 . 0 ° C

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 71
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  User  Setpoints


E n a b l i n g S u p e r v i s o r
D e m a n d L i m i t i n g N

E n a b l i n g S u p e r v i s o r
D e m a n d L i m i t i n g Y
T y p e : U n i t

E n a b l i n g S u p e r v i s o r
D e m a n d L i m i t i n g Y
T y p e : C i r c u i t

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 72
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  User  Setpoints


C o m p r e s s o r s
s e q u e n c i n g
A U T O

C o m p r e s s o r s
s e q u e n c i n g
M A N U A L

S e t c o m p . s t a g e
C # 1 1 s t C # 2 2 n d

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 73
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  User  Setpoints


P r o t o c o l : M O D B U S
S u p e r v . C o m . S p e e d
1 9 2 0 0 ( R S 4 8 5 O N L Y )
I d e n t i f . N o . : 0 0 1

1. Modbus / Remote / Local / BacNet / ModSHZ / LonWorks


2. 19200 / 9600 / 4800 / 2400 / 1200
3. No.: 001 – 200

S u p e r v i s o r y r e m o t e
o n / o f f N
S u p e r v i s o r y R e m o t e
C o o l / H e a t N

4. Units / Language / Password change

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 74
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  User  Time Sched.


< S e t p o i n t s
< T i m e S c h e d .
< F S M S c h e d .
< C l o c k

E n a b l e t i m e
S c h e d u l i n g
Y

S t a r t S t o p
M o - F r 0 0 : 0 0 2 3 : 5 9
S a t 0 0 : 0 0 2 3 : 5 9
S u n 0 0 : 0 0 2 3 : 5 9

H o l i d a y s ( 1 )
0 0 / 0 0 0 0 / 0 0 0 0 / 0 0
0 0 / 0 0 0 0 / 0 0 0 0 / 0 0
0 0 / 0 0 0 0 / 0 0 0 0 / 0 0

H o l i d a y s ( 2 )
0 0 / 0 0 0 0 / 0 0 0 0 / 0 0
0 0 / 0 0 0 0 / 0 0 0 0 / 0 0
0 0 / 0 0 0 0 / 0 0 0 0 / 0 0

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 75
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  User  FSM Sched.


F a n S i l e n t M o d e Y

M a x I n v . O u t . 0 6 . 0

F S M M o n d a y - F r i d a y
S t a r t S t o p
1 s t 0 0 : 0 0 0 6 : 0 0
2 n d 1 8 : 0 0 2 3 : 5 9

F S M S a t u r d a y
S t a r t S t o p
1 s t 0 0 : 0 0 0 6 : 0 0
2 n d 1 4 : 0 0 2 3 : 5 9

F S M S u n d a y
S t a r t S t o p
1 s t 0 0 : 0 0 2 3 : 5 9
2 n d 0 0 : 0 0 0 0 : 0 0

F S M F o r c e O n D a y s ( 1 )
0 0 / 0 0 0 0 / 0 0 0 0 / 0 0
0 0 / 0 0 0 0 / 0 0 0 0 / 0 0
0 0 / 0 0 0 0 / 0 0 0 0 / 0 0
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 76
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  User  Clock


C l o c k c o n f i g .
T i m e 1 3 : 3 4
D a t e 0 7 / 0 2 / 0 8
W e e k D a y 4

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 77
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Alarms
A n t i f r e e z e a l a r m

S e t p o i n t 0 2 . 0 ° C
D i f f . 0 1 . 4 ° C

F r e e z e p r e v e n t

S e t p o i n t 0 3 . 0 ° C
D i f f . 0 1 . 0 ° C

O i l l o w p r e s s u r e
a l a r m d e l a y s
S t a r t u p d e l a y 3 0 0 s
R u n d e l a y 0 9 0 s

S a t u r a t e d d i s c h .
T e m p e r a t u r e a l a r m
S e t p o i n t 0 6 8 . 5 ° C
D i f f . 0 1 2 . 0 ° C

S a t u r a t e d s u c t i o n S a t u r a t e d s u c t i o n
T e m p a l a r m T e m p a l a r m h e a t m o d e
S e t p o i n t - 0 0 8 . 0 ° C S e t p o i n t - 0 3 2 . 0 ° C
D i f f . 0 0 2 . 0 ° C D i f f . 0 0 2 . 0 ° C
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 78
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Settings  Alarms
S a t u r a t e d s u c t i o n
T e m p a l a r m d e l a y s
S t a r t i n g 1 2 0 s
R u n n i n g 0 4 0 s

H i g h D i s c h a r g e
T e m p e r a t u r e A l a r m
S e t p o i n t 1 1 0 . 0 ° C

P r e s s R a t i o a l
T h r e s h o l d s
@ 2 5 % 1 . 1
@ 1 0 0 % 1 . 3

O i l P r e s s D i f f

A l a r m S e t p 0 0 2 . 5 b a r

S e l e c t P V M o r G P F S e l e c t P V M o r G P F
a l a r m t y p e : U n i t a l a r m t y p e : C o m p

E v a p . F l o w S w i t c h
a l a r m d e l a y s
S t a r t u p d e l a y 0 2 0 s
All Seasons °
CLIMATE COMFORT
R u n d e l a y 0 0 5 s
Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 79
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Maint  View
H o u r c o u n t e r
P u m p E v a p . 0 0 0 0 0 0

C o o l i n g P I D E r r o r s
P r o p . 0 0 1 . 8 ° C
D e r . 0 0 0 . 0 ° C / m i n

C o o l . P I D A c t . 0 9 0 0
P r o p o r t i o n a l 0 9 0 0
D e r i v a t i v e 0 0 6 0

C o o l i n g R e g .
D i s a b l e s t o p N
I n c r e a s e s t o p N

G l o b a l P I D r e q u e s t
L o a d Y
U n l o a d N
S t a n d b y N
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 80
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Maint  View
A v a i l a b l e B o a r d s

X X X X
X X

C o m p r e s s o r 1 H o l d
L P N H P N A m p N
H R N V F D N D S H N
H W N N T W N

C o m p r e s s o r 1 U n l o a d
L P N H P N A m p N
F R N
H W N N T W N

C o m p r e s s o r 2 H o l d
L P N H P N A m p N
H R N V F D N D S H N
H W N N T W N

C o m p r e s s o r 2 U n l o a d
L P N H P N A m p N
F R N
H W N N T W N
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 81
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Maint  View
N u m . D e f r o s t c y c l e
1. 10x down C i r c .
C i r c .
1 :
2 :
0 0 0
0 0 0

D e f r o s t C o n d . C # 1
2. 11x down A 1 A 2 A 3
A 2 A 5 A 6
T s < 0 4 . 1 ° C ( )

3. 12x down E
c
n
i
d d e f r o s t
r c 1
c o n d .

c o o l f a n
h p r e s s t e m p

4. 15x down I n v e r t e r o v e r b o o s t
O v e r b o o s t
O v e r b . b y T a m b
M a x C a p a c i t y 1 1 5 %

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 82
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Maint  Settings
E v a p . P u m p h . C o u n t .
T h r e s h . 0 1 0 x 1 0 0 0
R e s e t N
A d j u s t 0 0 0 0 0 0

C o m p . # 1 h . C o u n t C o m p . # 2 h . C o u n t
T h r e s h o l d 0 1 0 x 1 0 0 0 T h r e s h o l d 0 1 0 x 1 0 0 0
R e s e t N R e s e t N
A d j u s t 0 0 0 0 0 0 A d j u s t 0 0 0 0 0 0

C o m p . # 1 s t a r t s C o m p . # 2 s t a r t s
R e s e t N R e s e t N
A d j u s t 0 0 0 0 0 A d j u s t 0 0 0 0 0

R e g u l . b a n d 0 0 4 . 0 ° C
N e u t r . b a n d 0 0 0 . 1 ° C
M a x P u l l D o w n R a t e
0 0 . 7 ° C / m i n

S t a r t u p D T 0 0 2 . 6 ° C
S h u t d n D T 0 0 1 . 7 ° C

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 83
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Maint  Settings
H i g h C h L W T s t a r t
L W T 0 2 5 . 0 ° C
M a x C o m p . S t a g e 0 7 0 %

L o a d f o r C o m p s
M i n L o a d 0 4 0 %
F u l l L o a d 1 0 0 %
E n S l i d e V a l v e N

C h L W T e m p e r a t u r e
s e t p o i n t l i m i t s
L o w 0 0 4 . 0 ° C
H i g h 0 1 5 . 0 ° C

P r o b e s e n a b l e
B 1 : Y B 2 : Y B 3 : Y B 4 : Y
B 5 : Y B 6 : Y B 7 : Y B 8 : Y
B 9 : Y B 1 0 : Y

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 84
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Maint  Settings
E x p p r o b e s e n a b l e 1
B 1 0 1 : N B 1 0 2 : N
B 1 0 3 : N B 1 0 4 : N
B 2 0 1 : Y B 2 0 2 : N

E x p p r o b e s e n a b l e 2
B 2 0 3 : Y B 2 0 4 : Y
B 3 0 1 : N B 3 0 2 : N

E x p . D i g . I n p u t E n a b l e

I n p u t s P r o b e s o f f s
B 1 : 0 . 0 B 2 : 0 . 0
B 3 : 0 . 0 B 4 : 0 . 0
B 5 : 0 . 0

I n p u t s P r o b e s o f f s
B 6 : 0 . 0 B 7 : 0 . 0
B 8 : 0 . 0 B 9 : 0 . 0
B 1 0 : 0 . 0
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 85
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Maint  Settings
D T t o r e l o a d a n d
r e u n l o a d c o m p

0 0 0 . 7 ° C

R e s e t a l a r m
b u f f e r N

S u p e r v i s o r a u t o .
c o m p . s e l e c t i o n
E n a b l i n g N
D e l a y 0 3 0 s

C o mm u n i c a t i o n
S u p e r v i s o r

P a s s w o r d M a n a g e r
O l d : 0 2 0 0 1
N e w : 0 0 0 0 0
S a v e c h a n g e s ? N
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 86
TOP SECRET
SECRET
M a x P u l l U p R a t e INTERNAL USE ONLY
PUBLIC
0 1 . 5 ° C
Maint  Settings S t a r t u p
S h u t d n
D T
D T
0 0 2
0 0 1
.
.
6
7
° C
° C

D e f r o s t f o r c i n g
1. 21x down C i r c . 1 : N o
C i r c . 2 : N o
f o r c e
f o r c e

S e t P a s s w o r d < L e f t S e t P a s s w o r d < L e f t
E n t e r M a n a g e r < R g h t E n t e r M a n a g e r < R g h t
P a s s w o r d : 0 0 0 0 0 < + P a s s w o r d : 0 2 0 0 1 < +
N o A c c e s s G i v e n < - M a n a g e r A c c e s s < -

D e f r o s t f o r c i n g
C i r c . 1 : F o r c e c o o l
C i r c . 2 : F o r c e f a n

2. 22x down D e f r o s t c y c l e s
c o u n t e r r e s e t : N

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 87
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Maint  Settings
I n v e r t e r F o r c e d
1. 24x down S p e e d # 1
E n a b l i n g N

I n v e r t e r F o r c e d < D
S p e e d # 1 < C
E n a b l i n g Y < +
C o m p r . # 1 0 0 0 . 0 % < -

2. 25x down I n v e r t e r
S p e e d # 2
F o r c e d

E n a b l i n g N

I n v e r t e r F o r c e d < D
S p e e d # 2 < C
E n a b l i n g Y < +
C o m p r . # 1 0 0 0 . 0 % < -

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 88
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

EEV valve control

Expansion valve

Superheat is controlled using the saturated


suction temperature ( LP) and the suction temperature.

Live time battery


18 months

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 89
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Driver EVD200 with Electronic EXV

1.The driver control the position of the electronic expansion valve.


2.The driver will maintain the SSH set point
3.In addition the driver control that the suction pressure will not
drop under a certain value (LOP ) or will be greater another
value ( MOP )

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 90
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Parameters
• Pre-opening valve
• Type of valve
• Type of refrigerant
• Superheat Set-Point e Dead Band
• Proportional, Integral time and Derivative time
• Low Superheat protection
• LOP Protection
• MOP Protection
• High suction temperature
• Low pressure sensor temperature
• Hardware configuration (battery and plan )
All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 91
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Pre-opening valve
Is a set percentage value of the valve at the compressor start
up
22

20 • An excessive pre-opening, can


Pre-opening correct
18
cause liquid return from the
16
suction to the compressor.
14
(use default value)
SuperHeat (°C)

12 Pre-opening incorrect
10 • A small pre-opening can cause
8 the compressor to trip for low
6
pressure ( use default value )
4

0
0 2 4 6 8 10 12 14 16 18 20 22
Time

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 92
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Driver EXV status led


Under normal conditions five(5) LED indicates:

 POWER: (yellow) remains On in presence of supply. Remains Off in case of battery


operation
 OPEN: (green) Flashing during the valve opening. On when valve is fully open.
 CLOSE: (green) Flashing during the valve closing. On when valve is fully close.
 Alarm: (red) On or flashing in case of hardware alarm.
 pLAN: (green) On during the normal working of pLAN.

In presence of critical alarm situations, the combination of LED On identifies the alarm
as show in the next page.

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 93
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Driver EXV led meaning alarm


Alarms that stops the system PRIORITY LED OPEN LED CLOSE LED POWER LED ALARM
Eprom reading error 7 Off Off On Flashing
Valve open in case of lack of
6 Flashing Flashing On Flashing
supply
At start up, wait for battery
5 Off On Flashing Flashing
loading (parameter……….)
Other alarms PRIORITY LED OPEN LED CLOSE LED POWER LED ERROR
Motor connection error 4 Flashing Flashing On On
Probe error 3 Off
Flashing On On
Eeprom writing error 2 - - On On
Battery error 1 - - Flashing On
pLAN LED pLAN
Connection OK On
Driver connection or address error = 0 Off
The Pco Master doesn’t answer Flashing

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 94
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

MOP protection

When comes on The Valve


If the saturated suction Close to decrease the
temperature is above the MOP saturated suction
limit temperature

WARNING
This protection will only work if the temperature is below the maximum
limit
(the closing of the valve can increase the satur. temperature )

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 95
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Electronic expansion valve

Tapered slide valve


Inlet Outlet

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 96
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Economizer

1. Principal

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 97
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Economizer

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 98
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Economizer

1
4

2 3

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 99
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Economizer

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 100
TOP SECRET
SECRET
INTERNAL USE ONLY

pCOe expansion #1 – Additional hardware &


PUBLIC

Economizer

Analog Input Digital Input


Ch. Description Type Ch. Description
B1 Comp. Capacity Sensor #1 4-20mA DI1 SPARE
B2 Comp. Capacity Sensor #2 4-20mA DI2 SPARE
B3 Suction Temp #1 (**) NTC DI3 Low Pressure Switch #1 (*)
B4 Suction Temp #2 (**) NTC DI4 Low Pressure Switch #2 (*)

Analog Output Digital Output


Ch. Description Type Ch. Description
AO1 SPARE DO1 a) Compressor #1 alarm (*)
DO2 Compressor #2 alarm (*)
DO3 Economizer #1 (*)
DO4 Economizer #2 (*)
b) (*) Optional
(**) In case EEXV driver is not installed. If EEXV driver is installed, suction temperature is
detected through EEXV driver.

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 101
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Wiring economizer kit

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 102
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Economizer

1. Conditions:
1. Installation of expansion board
2. Address of expansion board: 1
3. Economizer activated if compressor capacity = 90 %
4. Economizer switch OFF if compressor capacity = 75%
5. Precaution
1. Economizer switch OFF if HP saturated > 65°C
2. Economizer switch ON if HP saturated < 60°C
6. Above setting can be programmed in the controller

All Seasons °
CLIMATE COMFORT Daikin EWAD-BZ & EWYD-BZ Service Training: 06 April 2018 103
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Economizer Economizer connection on