ITS EFFICIENCY
Cooling Tower
A cooling tower is a heat rejection device that rejects waste heat to
the atmosphere through the cooling of a water stream to a lower temperature.
Cooling towers may either use the evaporation of water to remove process heat
and cool the working fluid to near the wet-bulb air temperature or, in the case
of closed circuit dry cooling towers, rely solely on air to cool the working fluid to
near the dry-bulb air temperature.
Common applications include cooling the circulating water used in oil
refineries, petrochemical and other chemical plants, thermal power
stations and HVAC systems for cooling buildings. The classification is based on the
type of air induction into the tower: the main types of cooling towers are natural
draft and induced draft cooling towers.
Cooling towers vary in size from small roof-top units to very large hyperboloid
structures (as in the adjacent image) that can be up to 200 metres (660 ft) tall and
100 metres (330 ft) in diameter, or rectangular structures that can be over 40
metres (130 ft) tall and 80 metres (260 ft) long. The hyperboloid cooling towers are
often associated with nuclear power plants, although they are also used in some
coal-fired plants and to some extent in some large chemical and other industrial
plants. Although these large towers are very prominent, the vast majority of
cooling towers are much smaller, including many units installed on or near buildings
to discharge heat from air conditioning.
Classification by use
COOLING TOWERS CAN GENERALLY BE CLASSIFIED BY USE
INTO EITHER HVAC (AIR-CONDITIONING)
OR INDUSTRIAL DUTY AS SUGGESTED
BY RANTAEL , ROGELLITO AND STRONGHOLD, APRIL IN THE
BOOK THE MYSTERY OF COOLING TOWERS UNFOLDED
HVAC
An HVAC cooling tower is a subcategory rejecting heat from a chiller. Water-cooled
chillers are normally more energy efficient than air-cooled chillers due to heat
rejection to tower water at or near wet-bulb temperatures. Air-cooled chillers
must reject heat at the dry-bulb temperature, and thus have a lower average
reverse-Carnot cycle effectiveness. Large office buildings, hospitals, and schools
typically use one or more cooling towers as part of their air conditioning systems.
Generally, industrial cooling towers are much larger than HVAC towers.
HVAC use of a cooling tower pairs the cooling tower with a water-cooled chiller or
water-cooled condenser. A ton of air-conditioning is the removal of
12,000 Btu/hour (3517 W).
The equivalent ton on the cooling tower side actually rejects about 15,000 Btu/hour
(4396 W) due to the heat-equivalent of the energy needed to drive the chiller's
compressor. (1,500 pound/hour) of water 10 °F (5.56 °C), which amounts to 15,000
Btu/hour, or a chiller coefficient-of-performance (COP) of 4.0. This COP is equivalent
to an energy efficiency ratio (EER) of 13.65.
According to the location of the fan, they are further classified as:
Forced draft cooling towers, and
Induced draft cooling towers.
Forced Draft Cooling Tower
A mechanical draft tower with a blower type fan at the intake. The fan forces air
into the tower, creating high entering and low exiting air velocities. The low
exiting velocity is much more susceptible to recirculation. With the fan on the
air intake, the fan is more susceptible to complications due to freezing
conditions. The forced draft benefit is its ability to work with high static
pressure. They can be installed in more confined spaces and even in some
indoor situations. This fan/fill geometry is also known as blow-through.
Induced Draft Cooling Tower
A mechanical draft tower with a fan at the discharge which pulls air through
tower. The fan induces hot moist air out the discharge. This produces low
entering and high exiting air velocities, reducing the possibility of
recirculation in which discharged air flows back into the air intake. This
fan/fill arrangement is also known as draw-through.
Fan Assisted Natural Draft Cooling Tower
A hybrid type that appears like a natural draft setup, though airflow is assisted
by a fan.
Hyperboloid (sometimes incorrectly known as hyperbolic) cooling towers have
become the design standard for all natural-draft cooling towers because of
their structural strength and minimum usage of material. The hyperboloid
shape also aids in accelerating the upward convective air flow, improving
cooling efficiency. These designs are popularly associated with nuclear power
plants. However, this association is misleading, as the same kind of cooling
towers are often used at large coal-fired power plants as well. Conversely, not
all nuclear power plants have cooling towers, and some instead cool their heat
exchangers with lake, river or ocean water.
Thermal efficiencies up to 92% have been observed in hybrid cooling towers
Cooling Tower Efficiency Calculation
The calculation of cooling tower efficiency involves the Range and approach of the
cooling Tower. Cooling tower efficiency is limited by the ambient wet bulb
temperature. In the ideal case, the cold water temperature will be equal to the wet-
bulb temperature. This is practically not possible to achieve. This requires very large
tower and results in huge evaporation and windage or drift loss resulting in a
practically not viable solution. In practice, the cooling tower efficiency will be in
between 70 to 75%.