UTILITIES AVAILABLE
Chilled Water
Warm water
Cooling water
Compressed air
Steam
Potable Water
3
o
4
RECOMMENDED WATER QUALITY
TABLE- 1
TEST ITEMS CHILLED
WATER
1) pH QUALITY
7.2 - 8.5 STD.
2) TOTAL (CACOэ) PPM MAXIMUM 80
HARDNESS
3) TOTAL ALKALINITY LESS THAN 100
(CACOз) PPM
4) CHLORIDE ION (PPM) LESS THAN 50
5) TOTAL ION (Fe) PPM LESS THAN 0.3
6) SILICA (SiO2) PPM LESS THAN 30
7) AMMONIUM ION PPM LESS THAN 0.2
8) TDS LESS THAN 1200
5
1. Chilled water supplied from utility is
circulated through chilled water coil of
Air Handling Units.
8
CHILLER
Chiller:
Chiller detail:
9
CHILLER PARTS:
Compressor: Type: Centrifugal
Capacity: 500 TR
Motor : 324 KW
3 phase,
Shaft driven
10
11
WORKING PRINCIPLE
Evaporator in the chiller acts as cooler as
here water gets cooled due to heat absorption action
of boiling refrigerant.
The chilled liquid at 5º c is then supplied
to application area and return water at 10 ºc again
comes to the evaporator via balancing tank to
complete the circuit.
DAY MODE:
STL Tanks can be discharged through Plate Heat
Exchangers (PHE) to cool the return Chilled water at 10 ºC to 5 ºC .
BACK UP MODE:
It provides power failure back up of 800 TR for 1 hour at
5.1 º chilled water temperature at Balancing tank.
16
BENIFIT OF THERMAL STORAGE SYSTEM.
• It meet the additional HVAC load 311 TR to maintain
chilled water temperature to 5.1º C in the balancing
tank.
2. System to operate with existing 3× 500 TR and new
2×200 TR Chillers and system keeping 1×500 TR
Stand by.
3. It avoid part loading of 500 TR chillers to possible
extent.
4. It provides power failure back up of 800 TR for 1 hour
at 5.1 º C chilled water temperature at
Balancing tank.
17
``
18
DEFINITION:
Parameters:
19
20
DEFINITION:
Parameters:
21
RECOMMENDED WATER QUALITY
TABLE- 2
TEST ITEMS COOLING
WATER
1) pH QUALITY
7.2 - 8.5 STD.
2) TOTAL (CACOэ) PPM MAXIMUM 300
HARDNESS
3) TOTAL ALKALINITY LESS THAN 100
(CACOз) PPM
4) CHLORIDE ION (PPM) LESS THAN 200
5) TOTAL ION (Fe) PPM LESS THAN 1.0
6) SILICA (SiO2) PPM LESS THAN 50
7) TDS PPM LESS THAN 1500
22
APPLICATION
• CHILLER CONDENSER.
• COMPRESSOR INTER COOLER AND
AFTER COOLER.
• DIESEL GENERATOR.
• COOLING OF PROCESS VESSELES.
• COOLING OF PUMP MECHANICAL
SEAL.
23
Cooling Tower:
24
Components Details:
Casing
Motor
Fan
Water distribution system
Nozzle
Drift eliminator
Packing (fills)
25
COOLING TOWER
(INDUCED DRAFT)
MOTOR
WATER
INLET
26
Working Principle:
Cooling Tower helps to change the phase of
water by creating a condition in which hot water
evaporates in the presence of moving air. Thus heat is
extracted from the water and transferred to the air. This
process is called evaporative cooling.
27
CO MPR ES SED
AI R
1.DEFINITION
Compressed Air is the air at pressure
higher than the atmospheric pressure.
28
WORKI NG
PARA MET ERS
WORKING PRESSURE OF COMPRESSOR : 8.5 To 10.0 Kg/Cm²
29
PARAMETERS
Sr.No Tests Acceptance
Criteria
1 Carbon dioxide(ppm) NMT 1000 ppm
31
32
Details of Air Compressor:-
33
Detail s o f Air Comp ressor:-
34
Working of Air Compressor:-
35
Air dryer:-
The air from compressor passes through the
air dryer before going to the Air Receiver. In Air
dryer, air is cooled to dew point of 2 to 4 º c
thereby removing the moisture content in the
compressed air by condensation.
Dryer Details:-
Make : Ultratroc.
37
STEAM
Steam Boiler: -
Steam Boiler is equipment which generates
steam by heating of water.
IBR Boilers :-
As per the Indian Boilers Act, 1923, and Indian
Boilers Regulations, 1950 issued by Government
of India, Ministry of works, Mines and power –
central Boilers Board, “BOILER” means any closed
vessel exceeding 22.75 liters (5 Gallons) in
capacity which is used expressively for generating
steam under pressure and includes any mounting
or other fitting attached to such vessel which is
wholly or partly under pressure when steam is
shut OFF.
38
Non ‘IBR’ Boilers
40
• Pure steam generator.
• Multi column distilled water plant.
• Sanitation of DM water and WFI water storage tank.
• Manufacturing vessels.
• Bottle washing.
• Coating machines.
• Fluid bed equipments.
41
Boiler Details:
42
STEAM BOILER ARRANGEMENT
UNIT 1
STEAM OUT
BURNER
F.O ASSEMBLY
PUMP UNIT III
UNIT IV
FURNACE
SOFT WATER
OIL
TANK
BOILER FLAMES
COIL
FLUE GASES
EXHAUST TO
BOILER SHELL
CHIMNEY
INNER
SHELL
Water Softener :
Softener is an equipment which is used to
convert the potable water into soft water.
Definition:
Potable water is treated raw water .
Parameters:
Pathogens - Nil
Colony forming units - NMT 500 CFU/ML
48
Application:
Generation:
There are two sources of potable water i.e.,
i) Bore well
ii) IDC water (Industrial Development
Corporation)
Both water sources are being collected in epoxy lined
RCC underground tanks (100000 liters) by means of two
separate pipe lines.
49
Water treatment:
To control the microbial growth in
potable water sodium hypochlorite is
being dosed.
51
52