HD4/R
MV SF6 circuit-breakers
for secondary distribution
HD4/R
Core technology
Upper terminal
Fixed contact Blasting nozzles
Fixed arcing contact Moving arcing contact

Moving contact
Lower terminal

Insulating tie-rod

Epoxy resin cylinder


Anti-explosion valve
© ABB Group
Month DD, Year | Slide 2
HD4/R
Quenching technique – SF6 Autopuffer

(1) (2) (3) (4)

Circuit breaker Moving contact Arcing contact Circuit breaker


closed separation separation open

© ABB Group
Month DD, Year | Slide 3
HD4/R
Main components

1. Protection relay (accessory)


2. Shaft seat for charging the closing
springs
3. Closing pushbutton
4. Opening pushbutton
5. Charged/discharged closing
spring indicator (accessory)
6. CB contacts status (open/closed)
7. SF6 pressure status locking and
signalling device (accessory)
8. MV terminals
9. Current transformers/sensors
(accessory)
10. Epoxy resing poles with
assembled SF6 auto-puffer
11. Key lock in open position

© ABB Group
Month DD, Year | Slide 4
HD4/R
Integrated solution

Self-supplied relay Not self-supplied relay


HD4/R with shunt opening release

Apparatus

PR 521 REF 601 IEC


REF 601 CEI 0-16
Relay

Current transformer Current sensors


- 40/1A
Current - 80/1A
sensors - 250/1A
- 1250/1A

© ABB Group
Month DD, Year | Slide 5
HD4/R
Wide range of accessories

- Shunt opening release


- Auxiliary contacts (5 to 12)
- Key lock in open position
- Additional shunt opening release
- Opening solenoid (PR521)
- Shunt closing release
- Motor charger of closing spring
- Thermal relay for protecting motor charger
- Undervoltage shunt opening release
- Charged/discharged spring signalling contact
- Pushbutton protection
- Padlock
- Wheels
- Two-level pressure switch
- Three-level pressure lamps
- Locking device for insufficient SF6 pressure

© ABB Group
Month DD, Year | Slide 6
HD4/R
Reliability and flexibility

Reliability Flexibility
- 10.000 Close-open - Wide range of accessories
operations
- Possibility to have relays
- Maintenance-free and CTs on board

- SF6 auto-puffer technology - Interchangeable with VD4/R


ideal for critical loads
• No current chopping
• No restrike
• Reduced overvoltage

© ABB Group
Month DD, Year | Slide 7
HD4/R
SF6 circuit breaker

SF6 circuit breaker for secondary


distribution AIS
 On board relay and CTs/sensors
 Interchangeable with VD4/R

Command able to do fast operation cycle:


O-0.3s-CO-15s-CO

Rated Voltage [kV] 12 17.5 24 36

Rated Current [A] 1250

Short time current [kA] 25 (3s) 20 (3s) 16 (3s)


Mechanical class M2
Electrical class E2, C2

© ABB Group
Month DD, Year | Slide 8
HD4/RE
SF6 circuit breaker optimized

SF6 circuit breaker for secondary


distribution AIS
 On board relay and CTs/sensors
 Interchangeable with VD4/R and HD4/R
 optimized and compact

Rated Voltage [kV] 12 17.5 24

Rated Current [A] 630

Short time current [kA] 16 (1s)


Mechanical class M1
Electrical class E1

© ABB Group