Beruflich Dokumente
Kultur Dokumente
Figure shows that during external faults too, the current leaving the
protected zone is the same as that entering it.
Assuming that the CTs transform the two currents with the same
fidelity, there will be no current in the spill path and the scheme remains
stable (i.e. without any CB tripping).
System used:
• IEEE 4 Bus System with all modifications
previously done for placement of Overcurrent
Relays
• Remove Relay 2 and 3 along with respective
CTs from section 1 – 2 and section 2 – 3
• Place CTs on either side of Bus 2, taking great
care that when current enters the dot on
primary side of the CT, it must leave the
similarly marked dot on the secondary side.
• Connect one more CT on load 3.
• Now set turns ratio for all CTs,
considering the full load current
in that line section or load.
Placement of differential Relay 87
• Connect all three CTs with Differential Relay.
• From Input Tab of Relay, Increase CT Terminal
to 3.
• Select 3 CT IDs for three current inputs and
their ratios will be updated.
• In output Tab of Relay Editor , Add two HV
CB on either side of bus 2 to which the relay
should send its output.
• Select a Differential relay from a library of
different models and manufacturers from DIF tab.
• For example, we select Siemens 7UT51 and Select
an operation time.
• From Star Protective Device Coordination Place
fault on bus 2 and check operation of differential
relay. Also place fault on other buses to check
restrain.