Alarm Code

Alarm Code
●Alarm grouping
F---:Alarm that unit stop
E---:Alarm that unit restart or backup operation
T---:Alarm during PTI
F5---:Alarm that unit stop related to inverter
E5---:Alarm that unit restart related to inverter
Communication Interrupted: Communication error between CPU board (EC1) and
operation board (EC3)
Alarm Controller action at the generating of alarm
F --- Critical shut down. (Requires inspection/repair)
The unit stops, but restarts 3 minutes after the condition returns to normal.
If the same error occurs multiple times, the unit will switch to standby for 4 hours or
E --- stop.
Unit continues operation by back-up operation.
Alarm display only. Unit continues operation.

Alarm LED and Alarm Code Display


Alarm Alarm LED (Red) Alarm code display
F Alarm
Blinking
E807 E304 Press or key to display alarm code.
E Alarm OFF
Alarm Code : F Alarm
Alarm Controller
Diagnosis Alarm content
Code Action
HPS activates within 30 seconds after compressor starts.
001 F101
(2400 kPa or more)
LPT drops below -72kPa within 2 seconds after compressor
002 F109
starts
003 F301 Temperature setting request
004 F401 SS, DSS, RS and DRS all failed in chilled mode
004 F405 HPT, DCHS1 and DCHS2 all failed
004 F407 HPT and LPT both failed
UNIT stops
004 F409 LPT, DCHS1 and DCHS2 all failed
Abnormal power supply voltage detected within 2 seconds
005 F701 after unit turns on.
One of R, S or T phase is open after unit turns on
006 F703 Unbalance power supply
007 F705 Open power phase during operation
008 F707 Fuse F2U is open (I/O board)
009 F809 E809 (shortage of refrigerant) is generated twice
Alarm Code : E Alarm
Alarm
Diagnosis Alarm content Controller action
Code
001 E101 HPS activates during operation
101 E105 Compressor operating current is too high (over DC 51A)
DCHS1 or DCHS2 becomes 130 ℃ or more for 10 minutes
002 E107 Restart after 3 min.
or 145 ℃ or more.
002 E109 LPT drops below -70kPa during operation
010 E115 Condenser fan motor internal thermostat activated
011 E201 Pumpdown control is not completed within rated time
Alarm display only
012 E202 Automatic pumpdown failure
013 E203 Overcooling prevention Restart after 3 min.
014 E207 Defrost is not completed in 90 min.
Humidity setting request (during dehumidification
003 E303
operation)
015 E304 Incorrect configuration set (Reheat coil) Alarm display only
003 E305 Defrost interval setting request
003 E307 Calendar setting request
003 E311 Trip start setting request
Alarm Code : E Alarm
Alarm
Diagnosis Alarm content Controller action
Code
016 E401 Supply air temperature sensor (SS) failure
016 E402 Data recorder supply air temperature sensor (DSS) failure
016 E403 Return air temperature sensor (RS) failure
016 E404 Data recorder return air temperature sensor (DRS) failure
Backup operation
017 E405 Discharge gas temperature sensor (DCHS1) failure
018 E406 Suction gas temperature sensor (SGS) failure
018 E407 Evaporator inlet temperature sensor (EIS) failure
018 E409 Evaporator outlet temperature sensor (EOS) failure
018 E411 Ambient temperature sensor (AMBS) failure Alarm display only
019 E413 Low pressure transducer (LPT) failure
Backup operation
019 E415 High pressure transducer (HPT) failure
020 E417 Power voltage sensor (PT) failure
021 E419 Current sensor (CT) failure
022 E425 USDA #1 sensor failure Alarm display only
022 E427 USDA #2 sensor failure
022 E429 USDA #3 sensor failure
Alarm Code : E Alarm
Alarm
Diagnosis Alarm content Controller action
Code
018 E435 Economizer inlet temperature sensor (ECO IN) failure
018 E437 Economizer outlet temperature sensor (ECO OUT) failure Backup operation
017 E439 Discharge gas temperature sensor (DCHS2) failure
024 E607 Sheet key failure Alarm display only
Abnormal power voltage is detected during operation. One
005 E701 Restart after 3 min.
of R, S or T phase is open during operation
025 E707 Temporary power supply shut down during operation Restart after 3 min.
026 E801 CPU onboard battery failure
027 E805 FA sensor failure
Alarm display only
Ventilator open warning: Ventilator is open during frozen
028 E807
operation
009 E809 Refrigerant shortage Restart after 3 min.
A communication error between CPU board (EC1) and
029 E903 Alarm display only
operation board (EC3)
Alarm Code : Inverter F Alarm
Alarm
Diagnosis Alarm content Controller action
Code
101 F528 E528 (Compressor does not startup) is generated 5 times.
E52E (Temporary compressor overcurrent ) is generated 4
102 F52E
times.
E52F (Compressor current sensor failure) is generated 4
102 F52F
times.
103 F536 E536 (Current sensor offset error) is generated 4 times.
Inverter board failure (Microcomputer I/O port logic UNIT stops
103 F538
judgmentfailure when unit is on)
104 F53A Incorrect setting (Controller model)
102 F53B Inverter board failure (EEPROM fault when unit is on)
E53C (Main circuit condenser recharging error) is
103 F53C
generated 4 times.
101 F53D E53D (Compressor lock) is generated 4 times.
Alarm Code : Inverter E Alarm
Alarm
Diagnosis Alarm content Controller action
Code
Compressor over current (>16.1A) is detected during
101 E523
operation.
Compressor over current (>19A) is detected during
101 E524
operation.
Actual frequency much lower than command frequency due
101 E525
to compressor over load
Actual frequency much higher than command frequency
105 E526
due to external factors
101 E528 Compressor does not operate after startup.
106 E52C Inverter board temperature higher than 99 ℃
Inverter board temperature abnormal (> 150 ℃ or < -45 ℃ Restart after 3 min.
102 E52D
is detected.)
102 E52E Current is too high temporary during startup (over 51A)
102 E52F Compressor current sensor failure at startup
107 E531 Power supply voltage is unbalance
Power supply voltage error (too high, too low at
108 E532
abnormally)
109 E533 Power supply voltage error (open phase)
103 E536 Current sensor offset fault when compressor starts
103 E53C Main circuit charge failure when compressor starts
101 E53D Compressor lock when compressor starts
110 E542 Cooling fan lock during operation (LX10F15A only) Alarm display only
A communication error between CPU board (EC1) and
111 E5FF Restart after 3 min.
Inverter board (EC8)