SHARING
SESSION
Rozi Ramadhani
Local Technical Support - IAP
INTRODUCTION
Emerson Vertiv
2
EMPOWERING
VITAL
APPLICATIONS
FOR A DIGITAL
WORLD:
AN INTRODUCTION
TO VERTIV
COMMERCIAL AND
INDUSTRIAL
Healthcare, Rail, Transportation,
Power Generation, Oil and Gas
5
DKSH AS AUTHORIZED DISTRIBUTOR
6
OUR FLAGSHIP BRANDS
We’re a brand-new company that’s also an established industry leader
VERTIV CAPABILITIES
A complete life-cycle approach to service, from project launch to ongoing
maintenance and performance optimization
• Nuclear
Application
Liebert RG
AC UPS FP-60Z NP-90Z
CP-70Z
(Z) CP-60Z
FP-50Z CP-50Z
DC UPS
Rectifiers XP-90R NP-90R
(R) CP-70R
DC/AC
Inverters
(i) XP-90i NP-90i
CP-70i
CP-50i
Customizability
UNDERSTANDING
POWER QUALITY
ISSUES
10
*Additional Notes
UPS SYSTEMS ARE A CRITICAL POINT BETWEEN THE
POWER SOURCE AND THE LOAD TO BE SECURED
Critical load
to be protected
G
Power network
DC UPS AC UPS
Rectifier
Rectifier Charger
Charger
Battery Inverter
Battery Manual
Bypass
switch
Static
bypass
PLC’s
DC Motors Motors, Safety
Instrum. Lighting
Pumps Actuator
Remote s
Telecontrol Drives DCS
MV & HV
Switchgear Unit Valves
(coils) PLC’s
Turbine Control
Lube oil Room
pump
AC UPS SYSTEMS
Mains DC Voltage
AC Voltage
AC Input
Consumers / Load
3 phase
RECTIFIER INVERTER
AC / DC Converter DC / AC Converter
BATTERY
Energy Storage
• 3 Phase Input
• Voltage: 3x380/400/415 +/-10% • 1- or 3-Phase Output
• 4 Standard IGBT-PWM controlled Inverter
• Frequency: 50 or 60 Hz
DC Voltages:
• 6-pulse thyristor-controlled • Short-circuit proof
110, 125, 220 or
Rectifier 400 VDC • Option: oversized Inverter
• Option: 12 pulse thyr.-contr. Module to interrupt bigger fuses
Rectifier
• Option: oversized for higher
charging current or DC-load
• Float- and Boost charge *Additional Notes
1
AC SINGLE UNIT CONFIGURATION
Bypass Input
Manual Bypass Switch
*Additional Notes
1
AC REDUNDANT SYSTEM
CONFIGURATION
Bypass Input
UPS Module B
50 % 50 %
Normal
Bypass
BatteryOperation
Operation
Rectifier Input Secured Load Bus
Module B
UPS Module A
50 % 50 %
Rectifier Input
Module A
*Additional Notes
1
DC UPS SYSTEMS
Mains DC Voltage
Consumers
3 Phase / Load
AC Input
RECTIFIER
AC / DC Converter BATTERY
Energy Storage
• 3 Phase Input
• Voltage: 3x380/400/415 +/-10%
• Frequency 50 or 60 Hz • 5 Standard DC
• 6-pulse thyristor-controlled Voltages:
Rectifier 24, 48, 110, 125 or
• Option: 12 pulse thyr.-contr. 220 VDC
Rectifier
• Option: oversized for higher
charging current
• Float- / Boost- and Initial charge
*Additional Notes
1
DC SINGLE UNIT CONFIGURATION
Rectifier Normal
Battery Operation
Operation
Rectifier Input
Secured Load Bus
Battery
*Additional Notes
1
DC REDUNDANT SYSTEM
CONFIGURATION
CHARGER B
Normal
Rectifier Input Operation
Battery Operation
Module B Secured Load Bus
CHARGER A
Rectifier Input
Module A
*Additional Notes
1
INVERTER SYSTEMS
DC Voltage AC Voltage
DC Bus
Consumers / Load
INVERTER
DC / AC Converter
*Additional Notes
2
AN INDUSTRIAL UPS
• Critical design factors and long term impact
21
INDUSTRIAL UPS SINGLE LINE DIAGRAM
Avoid mechanical contactors in the critical circuit of industrial applications due to high failure
rate compared to purely solid state switching:
= =
~ ~
Robust industrial design Prone to failure in an
employs no moving parts industrial atmosphere
BENEFITS OF AN INDUSTRIAL UPS (CONT.)
What is SEEN
out side What is REALLY
inside
Some dubious
practices to be
careful !!
What about ventilation ? An external cubicle, over
IP20 UPS, seriously affect ventilation and thus life
Power electronics
Control electronics
What is SEEN
out side What is EXPECTED
inside
Customers connections
Accessibility
ROBUST MECHANICAL DESIGN AND TESTING
years
Lead Calcium AGM (Porous
Lead Acid
Refer to
2 years (no affect of manufacturer’s manual
Dry charged temperature) to other storage
conditions
Commissioning
with electrolyte procedure necessary
after storage
w/out electrolyte No limit
Commissioning
< 1 year if filled and charged
Recombination No limit if filled and discharged
procedure necessary
after storage
NOTA :
Ventilation area is
necessary for
Vented batteries
Rack enclosed in cubicles Cubicle
MAINTENANCE