FIRE FIGHTING SYSTEM

• Fire is a reaction giving off heat, light, and


smoke;
• The three essential elements for a fire to occur
are: heat, fuel, and oxygen.
• These three elements form what is called the
fire triangle. Removing any one of these
components and a fire cannot occur, or
continue.

4/12/2019 BUILT ENVIRONMENT 1


FIRE TRIANGLE

4/12/2019 BUILT ENVIRONMENT 2


Sources of Ignition
•Friction
•Hot surfaces
•Electrical shorts and electrical equipment
•Static electricity
•Tools
•Open flames
•Heating systems

4/12/2019 BUILT ENVIRONMENT 3


Classes of Fire
Classification according to type of material under fire:

Class A fires; involving solid materials - paper, wood, fabrics and so


on. Cooling by water or spray foam is the most effective way of
extinguishing this type of fire.
Class B fires; involving flammable liquids such as petrol, oils, fats;
foam and dry powder extinguishers should be used.
Class C fires; which are fuelled by flammable gases such as natural
gas, butane and so on. Priority must be given to shutting off the
source of fuel and the fire should be tackled with dry powder.
Class D metal fires; involving metals such as aluminum and
magnesium; special powders are required in such situations.
Class E fires; in which live electrical equipment is involved (sometimes
known as ‘electrical fires’). Non-conducting agents such as powder
and carbon dioxide must be used
4/12/2019 BUILT ENVIRONMENT 4
Classification according to the hazard of occupancy

•Extra light hazard; Non-industrial occupancies like hospitals, hotels,


libraries, office buildings, schools, museums,
nursing homes, and prisons.
•Ordinary hazard; Commercial and industrial occupancies involving
handling combustible materials. Under this class
there are four groups of occupational fire hazards:
Light group; butcheries, breweries, restaurants, coffee shops, and cement works
Medium group; bakeries, laundries, garages, potteries, engineering shops
High group; aircraft factories, leather factories, carpet factories, plastic
factories, warehouses, departmental stores, printing
rooms, saw mills chemical labs, and tanneries
Special group; cotton mills, distillers, film and television studios, and match
factories.
•Extra high hazard; Commercial and industrial occupancies involving
handling highly inflammable materials such as;
celluloid works, foam plastics, rubber factories,
paint and varnish factories, wood and wool
works, oil and other flammable liquids.
4/12/2019 BUILT ENVIRONMENT 5
Fire Detectors
Heat and flame detectors; have three basic operating
principles:
•Fusion; melting of a metal rather like a normal electrical
fuse which operates a switch thus closing an electrical alarm
circuit.
•Expansion; a bimetallic strip is used which expands when
heated and makes contact with an open electrical circuit,
thus closing it and sounding an alarm.
Flame (heat) and smoke detectors; an infra-red beam is
transmitted across the protected area. The smoke and heat
interfere with the transmission of the beam; this is detected
by the receiving unit and the alarm is initiated.
4/12/2019 BUILT ENVIRONMENT 6
Fire Protection of Buildings

There are four categories of fire protection


systems for buildings
• Portable extinguishers
• Fixed foam, carbon dioxide, and dry
powder extinguishers
• Sprinkler systems

4/12/2019 BUILT ENVIRONMENT 7


Portable Fire Extinguishers
• Water or spray foam fire extinguisher; suitable for class A
fires involving solid materials - paper, wood, fabrics and so
on.
• Foam and dry powder extinguishers; suitable for class B
fires involving flammable liquids such as petrol, oils, fats;
should be used.
• Dry powder extinguisher; suitable for class C fires which
are fuelled by flammable gases such as natural gas, butane
and so on.
• Special powder extinguisher; suitable for class D metal
fires involving metals such as aluminum and magnesium.
They work by simply smothering the fire with powdered
copper Non-conducting agents such as powder and carbon
dioxide extinguishers; suitable for class E fires in which live
electrical equipment is involved

4/12/2019 BUILT ENVIRONMENT 8


Portable Fire Extinguishers
• Halotron 1 extinguishers; like carbon dioxide units, are for use on
class B and C fires. Halotron 1 is an ozone-friendly replacement for
Halon 1211. It discharges as a liquid, has high visibility during
discharge, does not cause thermal or static shock, leaves no residue,
and is non-conducting. These properties make it ideal for computer
rooms, clean rooms, telecommunications equipment, and
electronics.
• FE-36 (Hydrofluorocarbon-236fa) extinguishers; The FE-36 agent is
less toxic than both Halon 1211 and Halotron 9. In addition, it has
zero ozone-depleting potential.
• Water mist extinguishers; are ideal for Class A fires where a potential
Class C hazard exists. Unlike an ordinary water extinguisher, the
misting nozzle provides safety from electric shock and reduces
scattering of burning materials. This is one of the best choices for
protection of hospital environments, books, documents, and clean
room facilities. In non-magnetic versions, water mist extinguishers
are the preferred choice for MRI or NMR facilities or for deployment
on mine sweepers.

4/12/2019 BUILT ENVIRONMENT 9


Portable Fire Extinguishers

4/12/2019 BUILT ENVIRONMENT 10


Automatic Sprinkler Systems

4/12/2019 BUILT ENVIRONMENT 11


Types of
Automatic Sprinkler Systems
• In general, sprinkler systems may be classified into two
main types: wet-pipe and dry-pipe systems
• Wet-pipe System; In the wet-pipe system the pipe
work is fully charged with water at all times and thus, it is
the fastest system in delivering water. This system is
recommended except when freezing conditions may exist or
accidental mechanical damage to sprinkler head may result
in property loss or damage. Therefore, this system should
not be used in spaces designated for electrical equipment
such as computers, switch boards and alike.

4/12/2019 BUILT ENVIRONMENT 12


Wet-pipe System

Schematic of wet-pipe sprinkler system


4/12/2019 BUILT ENVIRONMENT 13
Types of
Automatic Sprinkler Systems
• Dry-pipe system: In this system no water is introduced
into the piping network until a fire occurs. The dry-pipe
systems are used where conditions are such that freezing
may occur due to weather or other conditions such as cold
stores where the temperature is artificially maintained close
to, or below freezing. In dry type systems the pipes are kept
charged, at all times, with air or nitrogen under pressure.
Activation of a sprinkler head by heat released from a nearby
fire results in a pressure loss which in turn activates a dry
pipe valve which opens allowing water to enter the piping
network and sprayed through opened sprinkler heads. The
disadvantage of this system is that accidental damage to a
sprinkler head or gas leakage may falsely indicate the
existence of fire and activate the system causing property
damage. To avoid these unfavorable characteristics of dry-
pipe system a preaction valve is used resulting in what is
termed the "preaction system".
4/12/2019 BUILT ENVIRONMENT 14
Dry-Pipe System

Schematic of dry-pipe sprinkler system


4/12/2019 BUILT ENVIRONMENT 15
Types of
Automatic Sprinkler Systems
• Preaction System: This system is a dry-pipe
system with a preaction valve activated by a
separate fire detection system that is more
sensitive to fire than sprinkler heads. The fire
detection system may consist of smoke- or
flame-sensitive detection sensors that signal the
actuators to open the preaction valve allowing
water to flow through the sprinkler heads that
are already opened by heat from fire. Thus, this
system is much safer than the dry-pipe system
as the water is allowed to enter the piping
system only if fire occurs.
4/12/2019 BUILT ENVIRONMENT 16
Preaction System

Schematic of preaction sprinkler system

4/12/2019 BUILT ENVIRONMENT 17


Types of
Automatic Sprinkler Systems

• Deluge System: This system is also a dry-


pipe system with sprinkler heads (or
nozzles) open all the time. The system is
equipped with "deluge" valve operated by
heat, smoke, or flame sensitive sensors.
Upon valve opening water discharges out of
all sprinkler heads simultaneously.

4/12/2019 BUILT ENVIRONMENT 18


Deluge System

Schematic of deluge sprinkler system

4/12/2019 BUILT ENVIRONMENT 19


SPRINKLER

4/12/2019 BUILT ENVIRONMENT 20


SPRINKLER

4/12/2019 BUILT ENVIRONMENT 21


SPRINKLER

Upright sprinkler Pendent sprinkler

4/12/2019 BUILT ENVIRONMENT 22


Discharge Diagram For Standard Sprinklers

4/12/2019 BUILT ENVIRONMENT 23


SPRINKLER

4/12/2019 BUILT ENVIRONMENT 24


Temperatures and Identification Colors of Sprinklers

Operating Temperature Identification Color


oC

57 Orange
68 Red
79 Yellow
93 Green
141 Blue
182 Mauve
227/288 Black

4/12/2019 BUILT ENVIRONMENT 25


PARTS IDENTIFICATION

4/12/2019 BUILT ENVIRONMENT 26


SPRINKLER DISTRIBUTION ARRANGEMENTS

4/12/2019 BUILT ENVIRONMENT 27


Design of Hose Reel System
General guidelines for the design of hose-reel systems
have been developed by different codes of practice. These
are:
• Nozzle:
(a) Minimum pressure at the nozzle, P = 200 kPa
(b) Flow rate at each nozzle: q = 0.4 l/s (Hall, p. 39)
q = 0.5l /s (Code, p. 55)
(c) Hose-reel type and size:
Type: Rubber hose/flexible (BS3169)
Size: Lengths for two different diameters are given in
the following table
(d) Coverage: 418 m2/hose

4/12/2019 BUILT ENVIRONMENT 28


Design of Hose Reel System
General guidelines for the design of hose-
reel systems (Jordanian Code)
• Nozzle Size:
Operating pressure (bar) Hose diameter (mm)
3.5 65
3.0 40
3.0 19 0r 25*
1.25 19 or 25**
* Nozzle diam 4.5mm
** nozzle diam. 6.4 mm

4/12/2019 BUILT ENVIRONMENT 29


Design of Hose Reel System
Pressure at the Hose diameter Min. Hose
hose base*** (mm) length (m)
4.5 bar 65 23
5.5 bar 65 46
4.0 bar 40 23
4.0 bar 19 or 25* 30 or 25
1.5 bar 19 or 25** 30 or 25
* Nozzle diam 4.5 mm, ** nozzle diam 6.4 mm, *** it is allowed to lower the
pressure according to hydraulic calculation but not less than operating pressure.

4/12/2019 BUILT ENVIRONMENT 30


Design of Hose Reel System
Hose diameter Flow rate Nozzle diam
(mm) (lt/min) (mm)
65 473 (7.88 lt/s) 19

40 189 (1.48 lt/s) 12

25 30* (0.5 lt/s) 4.8

19 30** (0.5 lt/s) 6.4

* Operating pressure 3 bar, ** operating pressure 1.25 bar

4/12/2019 BUILT ENVIRONMENT 31


Design of Hose Reel System
Hazard Max Area Hose diameter
classification covered by a (mm)
hose m2
Light 800 19, 25

Ordinary 600 19,25

High 400 40

* Operating pressure 3 bar, ** operating pressure 1.25 bar


4/12/2019 BUILT ENVIRONMENT 32
SYSTEM FLOW RATE

• For systems using 65mm diameter hose:


– 31.5 – 78.8 lt/s for high and special hazards
– 15.8 – 78.3 lt/s for light and ordinary hazards
• For systems using 40 mm diameter hose .
– 6.3 lt/s for light and ordinary hazards.
• For systems using 19 or 25 mm diameter hose
– 1 lt/s

4/12/2019 BUILT ENVIRONMENT 33


Design of Hose Reel System

Table 1 hose diameter vs. length

D = 19 mm D = 25 mm
18 18
23 23
30 24
37 30
40 37
4/12/2019 BUILT ENVIRONMENT 34
Design of Hose Reel System
• Supply Pipe/Riser:
– Minimum number of hoses operated simultaneously:
– 3 at 0.4 l /s giving 1.2 l/s (Hall, p. 39)
– 2 at 0.5 l /s giving 1.0 l/s (Code, p. 55)
• Pressure at the connection to the hose reel (Code, p.
55):
– P=1.25 bar for a nozzle of 9.4 mm diameter (Code)
– P= 3.0 bar for a nozzle of 4.8 mm diameter (Code)

4/12/2019 BUILT ENVIRONMENT 35


Design of Hose Reel System

Riser size:

Table 2: Riser diameter vs. building height

Diameter, D Building height


(mm) (m)

50 15
64 > 15

4/12/2019 BUILT ENVIRONMENT 36


Design of Hose Reel System
• Tank: water supply/storage tank size
= 1.6 m3 (Hall)
= 1.125 m3 (Code, p. 55)
• Hose-Reel assembly type:
– Fixed: the least expensive
– Swinging: more flexible for drawing off the hose
– Recessed-swinging: good for corridors
• Pumping specifications (if needed):
– 2.3 l / s discharge capacity
– duplicate pumps for maintenance

4/12/2019 BUILT ENVIRONMENT 37


Design of Hose Reel System
Example:

A five storey building with floor area of 800m2


(28x15 m) is to be equipped with hose-reel fire
fighting system. Size the system for down-feed
and up-feed water supply for a light fire hazard
classification. The height of each floor is 3.2m.

4/12/2019 BUILT ENVIRONMENT 38


Design of Hose Reel System
Solution:
• According to the coverage of 412 m2 per hose
reel, two hose-reels on each floor is sufficient to
cover the whole floor area.

• Assume 2 hoses operating simultaneously, the


riser flow rate is then 1.0 l/s (0.5 l/s, each.)

• The hose length is chosen from Table 1 as 30m


with diameter of 19mm.

4/12/2019 BUILT ENVIRONMENT 39


Design of Hose Reel System
A storage tank of 1.6 m3 is capable of providing two
hose reels at 1.0 l/s total flow rate for 1600 seconds
(or 27 minutes) duration.

We also choose a nozzle with 4.8 mm diameter


(Pressure connection to reel=3.0 bar.)

We further choose the riser to be 50 mm in diameter since


the building height is just slightly greater than 15 m (i.e.,
16 m) as the pump will take care of the difference.
4/12/2019 BUILT ENVIRONMENT 40
Hf d 5H f
q
25  L  10 5
Design of Hose Reel System
The only item left is the pump size. So, we size
the pump as follows:

Pressure required at point A is 3 bar (3.0e+5 Pa or 30.6 m


head).
Static pressure head at point A is 15 m (up-feed) or 3.0
m down-feed.
Friction head loss Hf calculated using Thomas Box
formula
q = {(d5 *Hf)/(25*L*105)}1/2
Hf = q2*25*L*105/d5
4/12/2019 BUILT ENVIRONMENT 41
Design of Hose Reel System
Taking L= 1.5 L physical= 1.5*15 = 22.5 m
(up-feed)
= 1.5*3 = 4.5 m (down-feed)

Hf = 2 5
q *25*L*10 /d 5 = 0.18 m
(up-feed)
= 0.04 m (down-feed)
4/12/2019 BUILT ENVIRONMENT 42
Design of Hose Reel System
Total head is then:
Htotal =HA + H f + Hstatic
=30.6+0.18+15=45.78 m
(up-feed)

=30.6+0.04-3.0 = 27.64 m
(downfeed)
• Thus the system specifications are:

4/12/2019 BUILT ENVIRONMENT 43


Design of Hose Reel System

4/12/2019 BUILT ENVIRONMENT 44


Standpipe/Riser and Hose-reel System

HOSE REEL

BREAK TANK
PUMP SYSTEM

4/12/2019 BUILT ENVIRONMENT 45


Design of Sprinkler Installations

Sprinklers heads may be


arranged in two different
arrangements;
Standard and Staggered
arrangements as shown.

Sprinkler Heads
Arrangements
4/12/2019 BUILT ENVIRONMENT 46
Design of Sprinkler Installations

• The requirements and


design parameters for a
sprinkler system are given in
the table next:

4/12/2019 BUILT ENVIRONMENT 47


Parameter Light and Extra Light Ordinary High
1 Maximum area covered per system (m2) 4800 3600 2300
2 Maximum area covered per head (m2) 15, 21* 12, 9 for HPS 8, 9*
3 Maximum distance between heads (m) 4.6 4.5, 4.0*, 3.75 for HPS 3.7
4 Maximum distance between branches (m) 4.6 4.5, 4.0*, 3.75 for HPS 3.7
5 Maximum number of heads per branch line 8 8 6
6 Maximum number of heads per system
a. Wet pipe system 500 1000 1000
b. Dry pipe system
i.With accelerator 250 500 500
ii.Without accelerator 125 250 250
7 Head orifice diameter (mm) 10 15 20
1 1 a
Minimum pressure at outlet (bar)
8 Piping network diameters Table 12, p. 59 Tables 13&14, p. 64 Table 15, p.66
9 Flow rate in the riser (l/min) 1890-2830 2650-3780 b

Corresponding time duration (min) 30-60 60-90 60-120


10 Discharge density required by the total area covered See Fig. 7, p.59 See Fig. 7, p.59 See Fig. 7,
by sprinklers p.59
11 Discharge capacity of sprinkler head (l/min)
12 Values of k coefficient. 45-50 78-85 110-120
*Hall, p. 46
(a) or from catalog
(b) determined by official authority
(c) can be reduced to 0.5 bar according to the building type (see item 2, p. 58)
(d) use lower limit when early warning system is installed or when the building is close to fire fighting squad center
(e) C = 1.5 wooden installations
= 1.0 ordinary installations
= 0.8 installations made of noncombustible materials
Table 3
= 0.6 installations made of fire resistant materials

4/12/2019 BUILT ENVIRONMENT 48


Design of Sprinkler Installations
In designing sprinklers system two approaches are
available:
1. The occupancy hazard fire control approach
2. The special design approach
1- The occupancy hazard fire control approach includes:
• The Pipe Schedule, and
• The Hydraulic Calculation approach
which can follow any of the following methods:
Area/density method
Room design method
Special design method; building service chute corridors

4/12/2019 BUILT ENVIRONMENT 49


Design of Sprinkler Installations

2- The special design approach includes


• Residential sprinklers
• Quick- response early suppression sprinklers
• Large drop sprinklers
• Exposure protection
• Water curtains

4/12/2019 BUILT ENVIRONMENT 50


Design of Sprinkler Installations

Will consider only the

PIPE SCHEDULE METHOD

4/12/2019 BUILT ENVIRONMENT 51


Design of Sprinkler Installations
Pipe Schedule Method
Basic information:
The discharge capacity of sprinkler
head (l/min) is given by:
Q = k √p
where p is the pressure at the head's
outlet (bar) and k is a constant given
in Table 3, item 12.
4/12/2019 BUILT ENVIRONMENT 52
Design of Sprinkler Installations

Basic information:
Max number of sprinklers per branch is 8.

4/12/2019 BUILT ENVIRONMENT 53


Design of Sprinkler Installations
Pipe Schedule Method
This method is used for the pipe materials; copper and
steel. It consists of the following steps:
1- Determine the hazard type applicable to the
given space/building . See note next slide.
2- Select the type of sprinklers arrangement, i.e.,
Standard or Staggered.
3- Distribute the sprinklers according to the rules
given in Table 3
4- Size the piping system according to item 7 of
Table 3
4/12/2019 BUILT ENVIRONMENT 54
• Sprinkler systems having
sprinklers with orifices other
than 1/2 in. (13 mm) nominal,
extra hazard, Groups 1 and 2
systems, and exposure
protection systems shall be
hydraulically calculated.

4/12/2019 BUILT ENVIRONMENT 55


The number of automatic
sprinklers on a given pipe size
on one floor shall not exceed
the number given in Tables 4a&
b. for a given occupancy.

4/12/2019 BUILT ENVIRONMENT 56


• Table 4a. Light Hazard Pipe Schedules

• Steel Copper
• 1 in. 2 sprinklers 1 in. 2 sprinklers
• 11/4 in. 3 sprinklers 11/4 in. 3 sprinklers
• 11/2 in. 5 sprinklers 11/2 in. 5 sprinklers
• 2 in. 10 sprinklers 2 in. 12 sprinklers
• 21/2 in. 30 sprinklers 21/2 in. 40 sprinklers
• 3 in. 60 sprinklers 3 in. 65 sprinklers
• 31/2 in. 100 sprinklers 31/2 in. 115 sprinklers
• 4 in. See NFC 4 in. See Section 5-2
• For SI units, 1 in. = 25.4 mm.

4/12/2019 BUILT ENVIRONMENT 57


Table 4b Ordinary Hazard Pipe Schedule (source; NFC)

Steel Copper
1 in. 2 sprinklers 1 in. 2 sprinklers
11/4 in. 3 sprinklers 11/4 in. 3 sprinklers
11/2 in. 5 sprinklers 11/2 in. 5 sprinklers
2 in. 10 sprinklers 2 in. 12 sprinklers
21/2 in. 20 sprinklers 21/2 in. 25 sprinklers
3 in. 40 sprinklers 3 in. 45 sprinklers
31/2 in. 65 sprinklers 31/2 in. 75 sprinklers
4 in. 100 sprinklers 4 in. 115 sprinklers
5 in. 160 sprinklers 5 in. 180 sprinklers
6 in. 275 sprinklers 6 in. 300 sprinklers
8 in. See Section 5-2 8 in. See Section 5-2
For SI units, 1 in. = 25.4 mm.

4/12/2019 BUILT ENVIRONMENT 58


• Table: Number of Sprinklers; Greater than 12-ft
(3.7-m) Separations (source NFC)

• Steel Copper
• 21/2 in. 15 sprinklers 21/2 in. 20 sprinklers
• 3 in. 30 sprinklers 3 in. 35 sprinklers
• 31/2 in. 60 sprinklers 31/2 in. 65 sprinklers
• For SI units, 1 in. = 25.4 mm.
• Note: For other pipe and tube sizes, see Table 8-
5.3.2(a).

4/12/2019 BUILT ENVIRONMENT 59


Design of Sprinkler Installations
Pipe Schedule Method
EXAMPLE:

• A 5-story building with floor plan view shown


below. Design a sprinkler system using Pipe
Schedule method. The hazard classification is light
hazard.

4/12/2019 BUILT ENVIRONMENT 60


Design of Sprinkler Installations
Pipe Schedule Method

Solution:
• Floor area is calculated to be A =471 m2
• Number of sprinklers on the floor= 471/15 = 31 sprinklers.
• According to Table 3 the following sizes are selected for a steel
piping:
• Line A-B: there are 16 sprinklers. The diameter DA-B = 65 mm
• Line B-C: there are 12 sprinklers. DB-C = 65 mm
• Line C-D: there are 8 sprinklers. DC-D = 50 mm
• Line D-E: there are 4 sprinklers. DD-E = 40 mm
• Branches: each branch has 4 sprinklers, 2 on each side. Thus,
• DB-F =DC-G =…=DE-I =25 mm
• The riser size supplying the floor; 100 mm

4/12/2019 BUILT ENVIRONMENT 61


Parameter Light and Extra Light Ordinary High
1 Maximum area covered per system (m2) 4800 3600 2300
2 Maximum area covered per head (m2) 15, 21* 12, 9 for HPS 8, 9*
3 Maximum distance between heads (m) 4.6 4.5, 4.0*, 3.75 for HPS 3.7
4 Maximum distance between branches (m) 4.6 4.5, 4.0*, 3.75 for HPS 3.7
5 Maximum number of heads per branch line 8 8 6
6 Maximum number of heads per system
a. Wet pipe system 500 1000 1000
b. Dry pipe system
i.With accelerator 250 500 500
ii.Without accelerator 125 250 250
7 Head orifice diameter (mm) 10 15 20
1 1 a
Minimum pressure at outlet (bar)
8 Piping network diameters Table 12, p. 59 Tables 13&14, p. 64 Table 15, p.66
9 Flow rate in the riser (l/min) 1890-2830 2650-3780 b

Corresponding time duration (min) 30-60 60-90 60-120


10 Discharge density required by the total area covered See Fig. 7, p.59 See Fig. 7, p.59 See Fig. 7,
by sprinklers p.59
11 Discharge capacity of sprinkler head (l/min)
12 Values of k coefficient. 45-50 78-85 110-120
*Hall, p. 46
(a) or from catalog
(b) determined by official authority
(c) can be reduced to 0.5 bar according to the building type (see item 2, p. 58)
(d) use lower limit when early warning system is installed or when the building is close to fire fighting squad center
(e) C = 1.5 wooden installations
= 1.0 ordinary installations
= 0.8 installations made of noncombustible materials
Table 3
= 0.6 installations made of fire resistant materials

4/12/2019 BUILT ENVIRONMENT 62


Design of Sprinkler Installations
Pipe Schedule Method

4/12/2019 BUILT ENVIRONMENT 63


Water Supply
Water Supply
to

Water Based Systems


Water Systems

Riser-Hose-Real
Riser-Hose-Real
and

Sprinkler Systems
Sprinkler Systems
4/12/2019 BUILT ENVIRONMENT 64
Water Supply to Water Based Systems
(riser-hose-real and sprinkler systems)
• Community Water Supply System

• There are three principle components to the water based fire


protection system; storage, distribution and the hydrants
themselves. While functional hydrants and a good water
delivery system are important, everything starts with proper
storage.

• Water for fire protection should be provided by gravity storage


wherever possible. This is because using elevation as the means
for developing proper water pressure in water mains and
hydrants is reliable, not dependent on pumps that could fail or
be shut down as a result of an electrical outage. Storage can be
provided through one or more large reservoirs or by multiple
smaller reservoirs throughout the community that are linked
together.

4/12/2019 BUILT ENVIRONMENT 65


Water Supply to Water Based Systems
(riser-hose-real and sprinkler systems
Elevation of Storage Reservoir
Every meter of head will produce 10.1 kPa of
pressure. therefore to generate 410 kPa in
the water distribution system, storage
reservoirs must be located at an elevation of
approximately 50 meters above the service
area. Adequate system pressures are generally
accepted to be between 410 to 575 kPa.
Accordingly, reservoirs should be placed at
elevations between 45 and 57.5 meters above
service areas.

4/12/2019 BUILT ENVIRONMENT 66


Water Supply to Water Based Systems
(riser-hose-real and sprinkler systems
Since most communities are not perfectly flat, there
will be some variation in service pressure. While it
may be possible to establish a reservoir level to most
of a hilly community, it is often possible to design a
system where the predominance of the community
falls within the 450-575 kPa range with pressures in
some portions experiencing less desirable but
acceptable ranges as low as 340 kPa and as high as
810 kPa.
In locations where pressure gradients may fall outside
these less desirable pressure ranges, additional
reservoirs should be set at appropriate elevations to
serve these areas or main-line pressure regulators
should be installed to protect low-lying areas from
excessive pressurization.
4/12/2019 BUILT ENVIRONMENT 67
Water Supply to Water Based Systems
(riser-hose-real and sprinkler systems
• Reservoir size; most municipal water systems for
fire protection provide combination service for
fire hydrants and domestic (private and
commercial) use. Thus the determination for
volume of water stored is based on a number of
factors.
• Reservoirs should have adequate capacity to
provide continuous domestic flow in the event of
a disruption of the reservoir refilling system. They
must also have adequate storage to provide
anticipated fire flows for a reasonable duration.
4/12/2019 BUILT ENVIRONMENT 68
Water Supply to Water Based Systems
(riser-hose-real and sprinkler systems
• A reasonable rule of thumb is that storage should be
sufficient to provide at least two days of peak domestic
consumption plus required fire flows as determined by the
Fire fighting authorities in the city.
• For example, in a typical residential neighborhood with no
unusual hazards, storage based on a fire flow of 3785
L/min for two hours may be appropriate.

• In commercial or industrial zones, flows on the order of


19,000 L/min for 3 hours may be required. Reserve
capacity may have to be balanced by water quality issues.
There must be sufficient water changeover in reservoirs to
keep water fresh and healthful.

4/12/2019 BUILT ENVIRONMENT 69


Water Supply to Water Based Systems
(riser-hose-real and sprinkler systems

Typical reservoir tank on hillside

4/12/2019 BUILT ENVIRONMENT 70


Water Supply to Water Based Systems
(riser-hose-real and sprinkler systems

Multiple tank reservoir

4/12/2019 BUILT ENVIRONMENT 71


Water Supply to Water Based Systems
(riser-hose-real and sprinkler systems
Private water supply system
The supply of water to the water based fire protection
system in private buildings should be done from a special
reservoir devoted for this purpose. If the building is
provided by a continuous water supply at a rate of not less
than 1.6 m3 /min, a break tank of only 11.5 m3 would be
sufficient.
In the absence of adequate or dependable water main a
reservoir of not less than 45.5 m3 in volume should be
available on site of the building. The reservoir should be
provided with a pipe outlet of 150 mm diameter at the
street level and branched into four 64 mm instantaneous
couplings for connection to fire trucks.

4/12/2019 BUILT ENVIRONMENT 72