Sr. Name of Element Outage Status as on 04.04.

19 Remarks
No. GSS
1. 132/33KV 50 MVA, ECE 24.06.18 Transformer Test report not Expected to
Sheohar Make T-2 found OK. be charged by
Tr.(Supplied by Oil sample sent to Durgapur 08.04.19.
M/s GEPDEC) on 28.03.19 and report is
expected to reach by
05.04.19.
2. 132/33 KV 20 MVA, AVAL 05.08.18  Transformer is at AVAL
Teghra Make T-1 workshop. Under
Tr.(under Project-1.
guarantee- M/s
KPM)

3. 132/33 KV 50 MVA , TELK 16.09.18 L.O.I. issued from Bhagalpur Will be


Banka(new) make circle on 17.01.19 for attended
inspection of defective during 1st of
transformer by M/s TELK. week of April .
Sr. Name of GSS Element Outage Status as on 04.04.19 Remarks
No.

4. 132/33 KV 50 MVA , ABB 05.01.18 CRITL team tested on -


Purnea make 28.02.19 and following result
found:
• IR value- HV to earth low
• Core balance of Y ph not
found satisfactory.
•Tan delta 2.5KV & 5KV
sustain and 10KV not sustain.
5. 220/132/33 100 MVA, CGL 05.07.16  M/s Kanohar & M/s Mahati Processed
KV Dehri- Make T-1 has submitted proposal for to declare
on-Sone (repaired) rectification of the scrap.
transformer.
The rate seems too high.
Sr. Name of GSS Element Outage Status as on 28.03.19 Remarks
No.

6. 220/132/33 150 MVA, -  150 MVA Transformer is Faulty 150 MVA


KV Pusauli BHEL make to be replaced by 100 MVA Transformer to be
CGL(PGCIL) make. transported to BHEL
workshop.

100 MVA , -  Transformer has reached M/s CGL arrived at


CGL make and erection has been site on 04.04.19 for
diverted completed. testing of
from transformer.
PGCIL Problem observed in R ph
lead.