<Hardware Quality Standard V6.0 for Outdoor Wireless Macro Base Station product>
<Hardware Quality Standard V6.0 for Indoor Wireless Macro Base Station product>
The feeder cable should be earthed at three point at least, and has perfect w
aterproof treatments .
The feeder windows should have correct sealed measures and waterproof bend.
The RF connector needs to be installed perfectly.
The lighting–proof arrester must be earthed, all ground cables are connected
to the outdoor protection ground bar of equipment room after collecting.
Retain the additional engineering material for future use. There couldn’t wa
ste or throw away the engineering material optionally.
Remark:
Class A clauses: Critical problems, meaning that the violation of this clause will severely influence the safe running of the
equipment.
Class B clauses: Major problems, meaning that the violation of this clause will influence the normal running of the
equipment or bring hidden troubles to the normal running of the equipment.
Class C clauses: Minor problems, meaning that the violation of this clause will not influence the normal running of the
equipment but will have an impact on the future capacity expansion, the convenience of maintenance operations and so on.
2. The RF cable connector needs to be installed perfectly to avoid the situation that the virtual
connection would cause an abnormal VSWR and thus the normal system operation would be
affected. (indoor, outdoor)
3. The external lightning-proof arrester of cabinet should be installed according to its design
requirements. Its connection should be firm. (outdoor)
Huawei Confidential
Page 14
Main Equipment A
6. For all kinds of cable connectors, they must be clean before installation. If necessary,
they should be cleaned according to specification. (indoor, outdoor)
7. The rack must be firmly fixed on its cement base after it is installed. (outdoor)
8. The connection of alarm cable should be correct and reliable (check when an external alarm
box exits). (indoor, outdoor)
9. The parts of the rack should not be distorted. Which may be affect the equipment
appearance. (outdoor)
Expansion
Insulation
washers
Insulation
washers
Pressure plate bolt nut
9. The rigid cables should not be cross inside the cabinet. They cannot be pulled too
tightly. Some redundancy must be reserved at their bend place. They also need to be
bent in a tidy and consistent way. (indoor, outdoor)
10. When installing cables inside the rack, the cables of the horizontal direction should
be tied to inside of corresponding crossbars, the cables of the vertical direction should
be tied to two sides of cabinet. (indoor)
NO. NAME
S1 SFP cable
S2 ~ S7 RF jumper cable
S8 ~ S13 On-panel RF cable between STDM and
SPAM
S14 ~ S19 Attaching cabinets RF cable
P1 Extended subrack
Huawei Confidential
Page 26
HUAWEI TECHNOLOGIES CO., LTD.
Main Equipment B,C
Huawei Confidential
14. The cable labels are filled in
and pasted correctly and
reliably. Their positions are
orderly and in the same
Page 27
16. While you connect the RFFM, combiners, splitters and CDDUs, for example
. Unused ports of the combiners, splitters and CDDUs should be covered with
protection cover to protect these ports from dusts and other sundries. (ind
oor, outdoor)
18. When adjusting the level of the base by adjusting bolts, the pads should be added to its
bottom to increase its stress area and avoid its distortion. (indoor)
19. The interconnecting piece on the top of the cabinet must be installed and tightened.
(indoor)
20. PVC troughs should be installed on the wall for power and signal cables of alarm box.
Redundant power and signal cables should be put under the floor or on the cabling ladder
of alarm box side. (indoor)
Huawei Confidential
Page 31
Main Equipment B,C
22. Jumpers are laid according to layers and sectors. (indoor, outdoor)
23. The matter that is paint break off and scratch and smear can not appear on cabinet. Which may
be affect the equipment appearance. Otherwise the equipment must be repaint and cleaned.
(indoor, outdoor)
24. The connection position of cable connector should reserve some redundancies. (indoor,
outdoor)
25. The rack-mounting ear should be perfect. If some breakages occur on it, repair activities should
be done with spray paint. (indoor, outdoor)
26. The upper plane of antistatic floor in the equipment room cannot be higher than the lower plane
of the base to avoid to affect the ventilation. (indoor)
27. The installation position of rack and the cable route must accord to the engineering document,
for easy to maintenance and future expansion. (indoor, outdoor)
Huawei Confidential
28. All of false boards and pan
Page 34
29. The alarm box should be correctly installed according to design requirements. Its panel should
be clean without any obvious scratches. (indoor)
1. Waterproof and sealed measures for all outdoor jumpers and feeder cables should be correctly
adopted according to specifications. (indoor, outdoor)
2. The feeder cables should not have obvious bending and twisting and bare copper appearance. (indoor,
outdoor)
3. Antennas should be in the 45-degree protected area of lightning rod. (indoor, outdoor)
Huawei Confidential
Antenna and Feeder Cable B, C
Page 41
HUAWEI TECHNOLOGIES CO., LTD.
n the top of a building and then extended downward along the
uld be used for the parts of contact with the wall corner. When
along the roof, the feeder clamps should be used to fix the
Huawei Confidential
Antenna and Feeder Cable B, C
Page 42
HUAWEI TECHNOLOGIES CO., LTD.
lled on the top of building to lead the feeder cable into the
he antenna jumper and the feeder cable before the feeder
ends. (indoor, outdoor)
Huawei Confidential
Antenna and Feeder Cable B, C
Page 43
Antenna and Feeder Cable B, C
8. The antenna jumper and the feeder cable before entering the cabinet must
have waterproof bends. (outdoor)
9. The top of an omni antenna jacket should be level of or higher than the an
tenna support. (indoor, outdoor)
10. When installing the tower amplification module, the side of connecting th
e antenna should be upward, and the other side of connecting the feeder ca
ble should be downward. The installation position of tower amplification m
odule should be close to the antenna. (indoor, outdoor)
11. The labels of communication cables, feeder cables and jumper should be stuck and tied
according to specifications. The labels should be arranged in an orderly way with same
direction. (indoor, outdoor)
12. The installation position of antenna should be accorded with the design document. (indoor, o
utdoor)
13. The distance between an omni antenna and the tower body should not less than 1.5m, and that
between a directional antenna and the tower body should not be less than 1m. (indoor, outdoor)
18. The minimum bending radius of a feeder cable should not be less than 20
times of its diameter. (indoor, outdoor)
Indoor
jumper
BTS cabinet
21. For a tower-mounted base station, the color rings are attached at the following positions:
On the jumper that connects to the antenna, attach a color ring 200 mm [0.66 ft] away
from the feeder connector.
On the feeder that is outside the equipment room, attach a color ring 200 mm [0.66 ft]
away from the feeder connector.
On the feeder that is led down from the tower platform, attach a color ring 1 m [3.28
ft] away from the feeder connector.
On the feeder that is outside the feeder window, attach a color ring 1 m [3.28 ft] away
from the feeder window.
On the feeder that is inside the equipment room, attach a color ring 200 mm [0.66 ft]
away from the feeder connector.
On the jumper that connects to the cabinet, attach a color ring 200 mm [0.66 ft] away
from the feeder connector.
22. When installing the omni antenna on a roof, the blind zones should be avoide
d as much as possible. (indoor, outdoor)
23. When the front of cabinet is parallel to the feeder cable inside the room or
the back of cabinet faces it, a sector is in line and the order of each line
should be same. When the front of cabinet is vertical to the feeder cable ins
ide the room, a sector is in row and the order of each row should be same. (i
ndoor)
1. Each power cable or ground cable should be a whole section of copper core cable without any
connector in between. It also should be connected firmly according to specifications. (indoor,
outdoor)
2. When making copper lugs at the two ends of a power cable or ground cable, they should be
soldered or crimped firmly. (indoor, outdoor)
(1) Cable
(2) Nut
(3) Spring washer
(4) Flat washers
(5) bolt
5. The grounding cable and power cable of equipment is connected correctly. Their flat
washers, spring washers and nuts are installed in a right order. The nuts are tightened
properly. (indoor, outdoor)
6. The redundant part of a grounding cable or power cable should be cut and cannot be
coiled. (indoor, outdoor)
7. The grounding of antenna and feeder cable on the top of a building without a tower
should be connected to the nearby lightning-proof protection grounding net of the roof.
(indoor, outdoor)
Huawei Confidential
Page 66
Power Cable and Grounding Rule B,C
Power Cable and Grounding Rule B,C
2. The feeder cable of GPS/GLONASS
should have a reliable grounding point. The
indoor lightning-proof arrester of
GPS/GLONASS is directly connected to the
GPS/GLONASS signal input port of the
cabinet and does not need to earthed. The
grounding of lightning-proof protection can
be adopted close the GPS/GLONASS
antenna of outdoor. (check when the
GPS/GLONASS antenna exists). (indoor,
outdoor)
Huawei Confidential
Page 68
Power Cable and Grounding Rule B,C
Power Cable and Grounding Rule B,C
4. The feeder grounding clip is directly fixed on the steel sheet of the towe
r perfectly. The installation of this clip must accord with the standard requ
irement. The antirust, anticorrosive and waterproof measures are adopted for
the grounding clip and reliable connection. (indoor, outdoor)
5. The grounding bar must be wiped off rust and cleaned dirt before they are
connected, in order to ensure their reliable connection. The outside groundin
g bar must be anticorrosion and antirust processed by using self-spray paint
or other protection materials after they are connected in order to ensure the
ir long-term good contact. Each connecting terminal should be installed corre
ctly and firmly together with flat washers and spring washers. (indoor, outdo
or)
HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential Page 70
Power Cable and Grounding Rule B,C
3cm
Huawei Confidential
Page 73
Power Cable and Grounding Rule B,C
Power Cable and Grounding Rule B,C
13. The labels of power cable and ground cable are filled in and stuck correctly and reliably. They
should be tidy position and same direction. They should be stuck on a position 2 cm away from
their connectors. They can be made in a uniform way according to customer requirements,
including the label for power distribution switch. (indoor, outdoor)
18. When connecting two or more cables to a wire pole, the cross or back-to-back installation
method is generally adopted. When lugs are overlapped, they should be bent at an angle of 45 or
90 degrees, the bigger lugs should be put on the bottom and smaller one should be put on the top.
(indoor, outdoor)
The signal cables for future capacity expansion should be tied to or inserted into the
reserved position inside an expansion cabinet. For easy to maintenance and
expansion and avoid to lose. C
The unused connector should be protected through adding a protective cap i.e.. C
The floor gaps around the rack should be blocked up. Discarded cable ties, screws
and other sundries should not be found under the floor. C
The equipment room should be neatness and tidy. Discarded packing materials
should be cleaned. Spare parts should be arranged in a tidy way after installation. C