Sie sind auf Seite 1von 18

1

 LAYOUT

 COOLING WATER SYSTEM

 CHILLED WATER SYSTEM

 COMPRESSED AIR SYSTEM

 NITROGEN SYSTEM
3

WWT

Packing

SSP

Boiler
CP

Utility
4

 Basic information

Item Utility Cooling tower CP Cooling tower


Loaciton Utility 2nd floor CP 6th floor
Type Counter flow Counter flow
Number of set 4 5
Capacity 6000 CT 7500 CT
Circulation water 3360 m3/hr 4200 m3/hr
5

 Utility’s Cooling Tower


FE
15601

TE TE
50401 50402 Q = 1361 m3/h
FE
50445
PT
50411

- Chiller : 1016 m3/h


- 4k Compressor: 200 m3/h
- 4K Dryer: 200m3/h
FE - 6K Compressor: 80 m3/h
50404 - Nitrogen: 60 m3/h
Chemical
injection

Sand
filter

WWT
Sand
RT-17
filter
(blowdown)
U-P-EFF-A/B
6

 Utility’s Cooling water distribution

FT, PT, TT

24”-15617 CP
OSC WW
cooler
6”-15607

IPA slurry
mix tank
2”-25867 24”-15617
Utility
CT
7

 CP’s Cooling Tower


PI TE

TIC
Q =~2700m3/h

PT
36807
Q = 150 m3/h

Q = 600 m3/h

Sand
filter
8

Cooling tower – Piping in FEPV

 CP’s Cooling water distribution

SSP
6”-15696 F2
6”-15696 F1

12”-15615 F1

CP Boiler
12”-15658 F1
9

 Basic information

Item Centrifugal chiller Adsorption chiller


Loaciton Utility 1nd floor CP 3th floor
Quantity 3 1
Capacity 1000 RT 1200 CT
Circulation water 600 m3/hr 726 m3/hr
per machine
Refrigerent R123 LiBr
10

400 m3/hr×40M×3set
720 m3/hr×1set 1200RT

1174 m3/hr

600 m3/hr×40M×3set 600 m3/hr×3set 1000RT

45 m3/hr
11

 Chilled water distribution


WWT

SSP 18”-15925

18”-51704
14”-15939

CP
CP-ISBL 5”-35910 H
14”15939 6”-51709 5”-51710
2”-51712 18”-51701

Boost pump Centrifugal


FT, PT, TT chiller
13

2 COMPRESSED AIR SYSTEM (AP_4K)

3,500 Nm3/hr×5set 6,000 Nm3/hr×+3℃(D.P) ×2set 60 M3

Use: 6500 Nm3/hr


60M3

Use: 12000 Nm3/hr


14

2 COMPRESSED AIR SYSTEM (AP_4K)


 Utility’s AP_4K compressed air distribution

SSP

CP
60m3
tank
Utility
15
2

3,500 Nm3/hr×2set 3,500 Nm3/hr×-20℃(D.P) ×2set 20 M3 AP: 1,965 Nm3/hr


AI: 480 Nm3/hr

AP: 900 Nm3/hr


AI: 480 Nm3/hr

20M3 20M3

AI: 1500 Nm3/hr


16
2

 Utility’s AI_6K compressed air distribution

WWT

SSP

CP Boiler

Utility
17

600Nm3/h×0.4Mpa×99.9999%

6 M3

6M3
Use for emergency

20M3

20 M3 600Nm3/h×2set
18

 Nitrogen air distribution

EG
2”- 52002

51-82-S-01-AI
3”- 35402

SSP
3”-35404
Boiler 3”- 52002
CP
3”-35408
3-15401 2”- 52004

TPA
3”- 35401 Utilty Lab
3820-T01
19

Das könnte Ihnen auch gefallen