Beruflich Dokumente
Kultur Dokumente
Book:
Introduction
Primary function of an Air Conditioning System is to maintain the conditioned
space at required temperature, moisture content, air quality and noise
Cooling And Heating Load Calculations are done to ensure that the cooling and
heating equipment designed or selected serves the intended purpose of
maintaining the required conditions in the conditioned space
⇒
Mechanical Engineering Dept. CEME NUST 3
Cooling and Heating Load Calculations
Thermal Resistance R of a material is its ability to resist the flow of heat through
it
Building construction materials with a high R-value are desirable to reduce heat
losses
Mechanical
Further explanation about U-values Engineering
Tables, Dept.to
refer CEME NUST
Ch-3,Page: 52, Book: Edward G 10
Pita
Cooling and Heating Load Calculations
Following Table lists recommended U-values for below grade basement walls and
floors
Air Flow Rates in HVAC work are usually measured in ft3/min (CFM)
sensible heat equation is:
“Corner Room Infiltration” and “Door Usage”: Ch-3,Page: 57, Book: Edward G Pita
Based on the number of air changes per hour (ACH) in a room caused by the
infiltration
One Air Change is defined as being equal to the room air volume
Suggested values range from 0.5 ACH to 1.5 ACH for buildings ranging from
"tight" to "loose“ construction
Mechanical Engineering Dept. CEME NUST 20
Cooling and Heating Load Calculations
For each room, find Areas of exposed windows, walls, and so forth, through
which there will be heat transfer
Calculate Heat Transfer Losses through all exposed surfaces in the room →
Total these to find the room heat transfer loss
Find the room heating load. Room heating load = Room Heat Transfer Loss +
Room Infiltration Loss
Mechanical Engineering Dept. CEME NUST 23
Cooling and Heating Load Calculations
For Cooling → Amount of heat that must be removed (The Cooling Load) is not
always equal to the amount of heat received at a given time
o This difference is a result of the Heat Storage and Time Lag Effects
o Of the total amount of heat entering the building at any instant, only a
portion of it heats the room air immediately
o Other part (The Radiation) heats the building mass-the roof, walls, floors,
and furnishings → Heat Storage Effect
o later time the stored heat portion contribute to Heating the Room Air → Time
Lag Effect
Some of this heat is stored in the building mass and is not heating the room air
Conduction heat gains through the exterior roof, walls, and glass
Q = U A CLTDC
oCLTD is not the actual temperature difference between the outdoor and
indoor air
oCLTD values for some roof and wall constructions are given in standard
tables based on the following conditions:
⇒
Example 10 ⇒
A south-facing wall of a building in Pittsburgh, Pennsylvania. has a net opaque
area of 5600 ft2. The wall is constructed of 4 in. face brick + 2 in. insulation + 4 in.
heavy weight concrete. The inside air temperature is 77 F. Find the wall cooling
load at 4 PM Solar Time on June 21.
⇒ Wall is in Group B
⇒ CLTD = 15
Table 6.4: LM = -1 F
⇒
⇒
Mechanical Engineering Dept. CEME NUST 37
Cooling and Heating Load Calculations
Q = U A TD
Q = Heat gain (cooling load) through partition,
floor, or ceiling, BTU/hr
U = Overall heat transfer coefficient for
partition, fioor, or ceiling, BTUlhr-ft2-F
A = Area of partition, floor, or ceiling, ft2
TD = Temperature difference between
unconditioned and conditioned space, F
Q = SHGF A SC CLF
Solar Heat Gain Factor (SHGF) is the maximum solar heat gain through single
clear glass at a given month, orientation, and latitude → Values are available in
standard Tables
Shading Coefficient SC, to account for heat gains with different fenestration
arrangements → Values are available in standard Tables
Cooling Load Factor CLF accounts for the storage of part of the solar heat gain
→ Values are available in standard Tables
In these cases, only an indirect radiation reaches the glass from the sky and
ground.
The SHGF values for any shaded glass is the same as the N (north) side of the
building, which also receives only indirect radiation.
In order to find the total radiation through partly shaded glass, the shaded area
portion must first be found.
A building at 32°N latitude has a wall facing west with a 4 ft overhang, and a 5
ft wide by 6 ft high window whose top is 1 ft below the overhang. How much
of the glass receives direct solar radiation at 3 PM?
Solution
The vertical proportion of shade, from Table
6.11 is 0.97. The total vertical distance the
shade extends down is therefore
L=0.97x4=3.9ft
The height of shade on the window is
3.9 - I = 2.9 ft,
Further Discussion: Ch-3,Page: 139, Table: 6.13, Ex-6.11, Book: Edward G Pita
Mechanical Engineering Dept. CEME NUST 53
Cooling and Heating Load Calculations
What is the heat gain from 240 people at night in a movie theater at 75F DB?
Solution
Cooling Loads
Component Cooling Load
Cooling load/Heat gains from individual components like roof, glass,
floor, windows, equipment and infiltration.
Room Cooling Load
is the sum of each of the cooling load components (roof, walls, glass.
solar, people, equipment, and infiltration) in the room.
Building Cooling Load
is the rate at which heat is removed from all air-conditioned rooms in
the building at the time the building cooling load is at its peak value.
Coil Cooling Load
is the rate atwhich heat must be removed by the air conditioning
equipment cooling coil(s).
Refrigeration Load
is the load on the refrigeration equipment.
Mechanical Engineering Dept. CEME NUST 56
Cooling and Heating Load Calculations
April has highest value of 224, but in April, outside temperatures are expected
to be low in the morning, therefore, there will be large conduction heat losses
as well through both window and wall.
Next max SHGF value occurs for May, but for the same reason above, we can
chose month of June having value of 216
So Month is fixed, next we should know at what time in this month could peak
load occur.
Heat Gain through solar radiation Q = SHGF x A x SC x CLF
And Heat gain through wall conduction, Q = U x A x CLTDc
So we will check at what time we will have max CLF and CLTD value using
Table 6.10 and Table 6.2
Mechanical Engineering Dept. CEME NUST 61
Cooling and Heating Load Calculations
Using tables we see, that Peak CLF occurs at 0800 hrs and CLTD at 1000 hrs.
So we can calculate values at 0800, 0900 and 1000 hrs
SC for Window is 0.53 (Table 6.7), and CLF is 0.8 (8 AM), 0.76(9 AM), 0.62(10AM)
8 AM 9 AM 10 AM
Solar Radiation through Q = 216 x 60 x 0.53 x Q = 216 x 60 x 0.53 Q = 216 x 60 x 0.53 x
Glass, 0.8 = 5500 x 0.76 = 5220 0.62 = 4180
Q = SHGF x A x SC x CLF
Conduction through Q = 1.01 x 60 x 1 = Q = 1.01 x 60 x 3 = Q = 1.01 x 60 x 5 =
Glass, Q = UxAxCLTDc 61 182 283
Conduction through Wall, Q = 0.14 x 40 x 49 = Q = 0.14 x 40 x 56 Q = 0.14 x 40 x 57 =
Q = UxAxCLTDc 274 = 314 319
Total (BTU/hr) 5835 5716 4782
Cooling Coil Load will be greater than the building load because- there are heat
gains to the air conditioning system itself, due to:
Ventilation
Outside air is generally brought into the building for health and comfort
reasons
Sensible and latent heat of outside air is greater than the room air, so it
becomes part of the cooling load
Qs= 1.1 ⨯ CFM ⨯ TC
QL = 0.68 CFM (Wo' Wi')
Qt = Q s + Ql
o South-facing glass, maximum solar load is in the fall or winter in early afternoon
measure dimensions of all surfaces through which there will be external heat
gains, for each room
Select heat transfer coefficient U-values for each element from appropriate
tables, or calculate from individual R-values
Select heat transfer coefficient U-values for each element from appropriate
tables, or calculate from individual R-values
Determine time of day and month of peak load for each room by calculating
external heat gains at times that they are expected to be a maximum
o Often calculations at a few different times will be required
Find the cooling coil and refrigeration load by adding the ventilation load (to the
building heat gains; add blow-through fan, return air fan, and pump heat gains,
if significant