PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Philippe Duquesnoy
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Principle of the numerical-index method
A0 0
C3 A1 1
11
A
C2 A2 2
10
C1 3
A3 9
B0
C0 4
8
C B
B1
120 ° B3 B2 7 5
6
Application of three-phase
Normal order of Relative positions of
voltage to a series of
phase sequence vectors defined in space,
transformers with delta-star
("conventional direction") using a numerical index
connection
2
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Application to transformers
Equivalency numerical coupling indexes / phase shift in degrees
Numerical index = quotient by 30 of the phase shift in degrees :
Phase-shift
0 30 60 90 120 150 180 210 240 270 300 330 360
(in degrees)
Numerical 12
0 1 2 3 4 5 6 7 8 9 10 11
indexes or 0
3
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Application to transformers (cont’d)
0 Direction of "voltage" vector :
Vector "0" : direction 6 0
10 2
Vector "4" : direction 10 4
Vector "8" : direction 2 8
4
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Transformers with star-star coupling
Demonstration w/ forward voltage system 0-4-8 applied to the primary winding
0 (6) (6) 0
0 0
(10) (10)
4 4
(2) (2)
4 8 8 4
8 8
00
5
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Transformers with star-delta coupling
Supply via forward-voltage system
Demonstration w/ forward voltage system 0-4-8 applied to the primary winding
0 11
(6) (6) (0)
0 11
(10)
(10) (10) (4)
4 3
(2) 3
(2) (2) (8)
8 7
(6)
4
8
7
11 0
6
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Transformers with delta-star coupling
Supply via forward-voltage system
Demonstration w/ forward voltage system 0-4-8 applied to the primary winding
0
(1)
11
0 11
(11) ( 5) (5)
(5)
3
4
(3) (9) (9) 3
(9)
8 4 8 7
(7) (1) (1)
11
0
7
7
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Transformers with star-delta coupling
Supply via reverse-voltage system
Demonstration w/ forward voltage system 0-8-4 applied to the primary winding
0 1
(6) (6) (0)
0 1
(2)
(2) (2) (8)
8 9
(10) 9
(10) (10) (4)
4 5
(6)
4
8
5
0 1
8
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Transformers with star-zigzag coupling
Supply via forward-voltage system
Demonstration w/ forward voltage system 0-4-8 applied to the primary winding
(6) (0)
(6) 11
0
(6) (0)
0 11
(10) (4)
(10)
4 (10) (4) 3
3
8 4 (2) (8)
(2)
8 7
(2) (8)
7
11 0
(3) (9)
4 (9)
(3) (9) 3 3
4 (7) (1)
8 (1)
8 7 7
(7) (1)
0
11
Voltages on the primary : 0-4-8
Voltages on the secondary : 11-3-7
3
Secondary voltages lagging 330° / primary voltages
4
numerical index of the transformer is 11 8
7 10
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Application to looped three-phase network
Application rules
Starting from a "break" point, give a phase index to each conductor
Follow the path of the three conductors through the network elements
Each conductor retains its phase index
Transformer introduction of a phase shift that will depend on :
Index "N" of coupling group
Order taken by the voltage phases applied to terminals
"Break" point : comparison of phase indexes each side of this point
phase-coincidence (or not) ?
If no phase coincidence :
Analyse of three-wire drawing necessary changes of connection
Possibility of new transformer to be determined
11
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
8
Phase diagram of 4
a looped network 0
0 4 8 0 4 8
Substation P N 11
1 5 9
1
5
8 0 4 9
8 9 5 1
0
4
4 0 8 Substation T
N 11 Substation R
3 11 7 5 1 9
7 5
11 1
3 9
3 11 7
5 1 9
Substation S N6
11 7 3
11 7 3
11
7
3 12
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Application to differential protections
P2 P1 P1 P2
0 0 0 Generator
S2 S1 S1 S2
6 0 4 4 6 0
opposition of "input" indexes !
10 4
G 10 4
4
8 8
8 difference of 6 between indexes
2 8 2 8
Matching transformers :
only for ratio adjustment (if needed)
0 4 8 2 10 6
Differential protection
measurement devices
13
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Application to differential protections
Transformer
Diagram to be drawn up and numbered
Opposition of "receiver" / "generator" indexes !
difference of 6 between indexes
Phase shift "input" / "output" of transformer to be corrected by matching transformers
"Connection" of matching transformers :
Transformer "star" winding side matching transformers in star/delta configuration
Transformer "delta" winding side matching transformers in star/star configuration
Hardware wiring or software parameter
Matching transformers used for ratio adjustment
Hardware wiring or software parameter
14
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Yd11y0 6 0 11 11
5
10 4 3 3
0 6 9
0 2 8 7 7
0 4 10 1
4 6 0
0
4 8 2 6
8 10 4
4 5 9 1
8 11 3 7
8 10
2 8
2 11 3 7
0 4 8
5 9 1
6 10 2
6 10 2
5 0 4 8
87
6 10 2 bias 5
0 4 8 11 0 4 8
6 10 2
11 3 7
5 9 1
9
87 bias 9
3
1
87 bias 1
7
15
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Transformers coupling : symbols and conventions
Coupling system defined by :
Letters written in the order of the voltages
• Upper Case : High Voltage
• lower case : Low Voltage
D or d : delta configuration
Y or y : Star configuration
Z or z : Zigzag configuration
Number indicating the numerical index :
• Phase shift HV / LV (HV = reference !)
If star side neutral point earthed letter N or n added
16
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Methods for verification of the coupling index of a transformer
Transformer YNd11 Direct method
A-N B-N C-N
a-b b-c c-a
a b c
A-a = 0 B-a C-a
A B C N 11 0
A-b B-b C-b
A-c B-c C-c
a A A-b
A-c
b
c
C-c C-b B-b
B-c
C B
17
PHASE-SHIFT REPRESENTATION :
THE NUMERICAL INDEX METHOD
Methods for determining the coupling index of a transformer (cont’d)
"Polarity" method
18