Sie sind auf Seite 1von 11

How to connect and

configuration alarm
We used 4 dry contact for monitor
• Dry contact 1: for AC failure
• Dry contact 2: for DC low and high
• Dry contact 3: for rectifier fault
• Dry contact 4: for battery LVD

• In the site(3rd license of Egypt) now use


normally open dry contact
How to connect the dry contact in user manual
Where is the dry contact board in system? how to connect ?
Connect BBU EXT-ALM0
Alarm cable Line order

BBU Pin on the Wire Color Wire Type Pin on the Description Alarm Alarm
Alarm RJ45 RJ45 ID Name
Port Connector Connecto
r

White and
X1.1 X2.1 Boolean value input 0+
orange
Twisted for AC
65530
pair Boolean value input 0- failure
X1.2 Orange X2.2
(GND)

White and for DC


X1.3 X2.3 Boolean value input 1+
green Twisted low
65531
pair Boolean value input 1- and
EXT- X1.6 Green X2.6 high
(GND)
ALM0
White and
X1.5 X2.5 Boolean value input 2+ for
blue Twisted
65532 rectifie
pair Boolean value input 2-
X1.4 Blue X2.4 r fault
(GND)
White and
X1.7 X2.7 Boolean value input 3+ for
brown Twisted
65533 batter
pair Boolean value input 3-
X1.8 Brown X2.8 y LVD
(GND)
Run the MML in NodeB
• SET ALMPORT: SRN=0, SN=19, PN=0, MODE=CUSTOM, PT=BOOL, ALMID=65530,
AVOL=LOW;
• SET ALMPORT: SRN=0, SN=19, PN=1, MODE=CUSTOM, PT=BOOL, ALMID=65531,
AVOL=LOW;
• SET ALMPORT: SRN=0, SN=19, PN=2, MODE=CUSTOM, PT=BOOL, ALMID=65532,
AVOL=LOW;
• SET ALMPORT: SRN=0, SN=19, PN=3, MODE=CUSTOM, PT=BOOL, ALMID=65533,
AVOL=LOW;
Define the alarm in M2000 in NOC
How to connect configuration
alarm for APM30H
How to Connect alarm cables
How to configuration alarm for
APM30
• Set power configuration mode:
SET PWRSYSCFG: SRN=7, CS=CONFIGED, PTYPE=APM30;

Set NCMU board:


SET NCMUCFG: SRN=8, CS=CONFIGED;