OF SUBSTATIONS
BY-ROHIT SHARMA
INTRODUCTION
It consolidates maximum possible technical information/data
and salient parameters pertaining to substations as per
general prevailing practices for the use and guidance during
construction of Substation.
The site requirements need to be looked into by the owner of
the systems .
It shall be ensured that all statutory requirements stipulated
under Forest Conservation Act, Wild Life Protection Act,
Archeological Survey Act and other Acts/Rules/Laws, as may be
applicable, are fulfilled properly.
Adequate clearances shall be provided as per relevant
standards and CEA-safety (Measures relating to Safety and
Electricity Supply) .
GENERAL
Bus bars shall be of the rigid type with tubular aluminum bus
conductor or flexible stranded conductor with ACSR or AAAC or
other suitable conductors.
AIS substation shall be shielded against direct lightning stoke
by shield wire or earth wire or spikes or a combination thereof.
GIS
GIS installations shall generally be preferred for the locations
where space is a major constraint and also seismic prone
areas and costal areas.
Single bus with or without sectionalization and double main
bus switching schemes shall be used depending upon the
voltage level.
In our project we are taking Double main Bus scheme .
GIS shall be isolated phase or three phase non magnetic
enclosure type for voltage less than 400kV.
For 400kV and higher voltage levels ,it shall be isolated
phase enclosure type.
Future extension on either end without any drilling , cutting
or welding is possible.
All parts subjected to wear and tear are easily accessible for
maintenance purposes.
The equipment shall be protected against all types of
voltage surges.
TECHNICAL PARTICULARS
S.NO Parameters 33kV 132kV 220kV 400kV 765k
V
Insulators
The minimum creepage distances shall be decided for the
maximum pollution condition in the area of installation.
SUB- STATION AND SWITCHYARD SUPPORT FACILITIES
AC&DC Systems
AC & DC supplies shall be provided as per requirements given
in Central Electricity Authority (Technical Standards for
Connectivity to the Grid) Regulations, 2007.
The minimum duration for which the batteries operate are as
follows-
FIRE DETECTION, ALARM AND PROTECTION SYSTEM FOR
SUB- STATION AND SWITCHYARD
Control Room
Sub- station or switchyard control room shall be provided to
house the control and relay panels, PLCC equipments,
telemetry equipments and recording equipments, AC & DC
distribution boards, DC batteries etc.
Oil Evacuating, Filtering, Testing & Filling Apparatus
To monitor the quality of the oil of transformers and shunt
reactors necessary oil evacuating, filtering, testing and
filling apparatus shall be provided at a sub- station.
Oil tanks of adequate capacities for storage of pure and
impure transformer oil shall be provided.
Control concept
All the breakers in sub- stations and switching stations shall be
controlled and synchronized from the switchyard control room
or control room of the generating station.
Disconnectors of 220kV and higher rating shall have control
from remote as well as local whereas the earth switches shall
have local control only.
Disconnectors and associated earth switches shall be provided
with electrical as well as constructional mechanical interlocks.
CABLES AND CABLING
Cables shall be flame retardant, low smoke(FRLS) type as
per relevant IS/IEC.
In outdoor switchyards, a cable trench system shall be
provided. The main considerations and practices shall be:
1) Proper spacing shall be maintained - control and power
cables shall be laid in separate trays .
2) Proper attention shall be given to ventilation and heat
dissipation aspects particularly in case of HV cables.
3) Vaults and tunnels if employed shall be provided with
dewatering facilities.
ELECTRICAL AND MECHANICAL AUXILIARIES