Beruflich Dokumente
Kultur Dokumente
Electrical Equipment
(1) the excitation system design for which the static type is preferred with an
excitation transformer and automatic voltage regulator for each group of four
units;
(2) the generation voltage that could provide economy at 13.8 kV by eliminating
the intermediate step-up transformation;
(3) possible integration of the switchboard into the powerhouse units with
transmission to shore over only a few high-voltage cables;
(4) use of one transformer for groups of four or eight turbo generator units;
(5) group transformers to reduce the number and utilize more effectively the
transmission line breakers;
ABSORPTION OF RAW TIDAL ENERGY
where, dT is the steepness of the front or tail of the tidal pulse in MW/min,
and dL/dt is the rate of change in the system load in megawatts/minute.
Summary
• Raw tidal energy absorption capability of a system varies with
changes in system load and must-run generation change, but it is
essentially the difference between system load and must-run
generation at any given time.
• The changes are sufficiently slow to allow an hourly simulation with
sufficient accuracy for prefeasibility studies.
• However, a more detailed analysis of the dynamic problems
associated with the output gradient of tidal plants would require
system simulation in much smaller time steps than one hour.
• The conceptually simplest approach for calculating annual absorption
of raw tidal energy is to develop a chronological sequence of 8760
hourly load must-run and tidal output data, and then to compute the
amount of raw tidal energy absorbable by the simple process of
subtraction.
Conti…
• The dominant parameters affecting the absorption capability
are the ratio of the maximum tidal output to peak system load,
the must-run level, and the annual system load factor.
• The must-run level is governed by both static and dynamic
considerations.
• The dynamic constraint, arising from the limited load following
capability of a thermal plant, is only significant in the case of
tidal plants that are very large with relation to the system peak.
• The lower the must-run level and the higher the annual load
factor, the higher is the raw tidal absorption capability for the
same tidal plant/system peak ratio.
Next Class topic..
• ENHANCING RAW TIDAL ENERGY OUTPUT