SUBSTATION EQUIPMENT

WT, LA, ISOLATOR, CT,


PT, CVT

INCLUDING
MAINTENANCE ASPECT
SUBSTATION EQUIPMENT
 SURGE ARRESTOR
 CVT / PT
 LINE TRAP / WAVE TRAP
 ISOLATORS
 CURRENT TRANSFORMERS
 CIRCUIT BREAKERS
 TRANSFORMERS / REACTORS
SURGE ARRESTORS
 PROTECTS SUBSTATION EQUIPMENTS FROM
TRANSIENT OVERVOLTAGES

 CONNECTED BETWEEN PHASE AND EARTH

 PROVIDES LOW RESISTANCE PATH TO


EXCESSIVE

 RATING IN PHASE TO EARTH VOLTAGE


SURGE ARRESTORS
TYPES

 GAPPED SILICON CARBIDE SURGE


ARRESTORS

 GAPLESS ZINC OXIDE ARRESTORS


(PREFERRED THESE DAYS DUE TO
HIGHER ENERGY ABSORPTION
CAPABILITIES)
SURGE ARRESTORS
TYPES

 MADE OF SMALL DISCS OF NON-LINEAR


RESISTANCE MATERIAL ZnO WHICH
PROVIDES LEAST RESISTANCE PATH
DURING SWITCHING SURGES OR
LIGHTENING STROKE
SURGE ARRESTORS
PRE-COMMISSIONING TESTS

 INSULATION RESISTANCE
MEASUREMENT

 LEAKAGE CURRENT MEASUREMENT

 SURGE COUNTER CHECK


SURGE ARRESTORS
MAINTENANCE YEARLY

 CLEANING

 LEAKAGE CURRENT MEASUREMENT

 SURGE COUNTER CHECKS


LINE TRAP
 PROVIDES HIGH IMPEDANCE TO HIGH
FREQUENCY PLCC SIGNAL

 COMBINATION OF INDUCTANCE AND


CAPACITANCE FOR BLOCKING 50 Khz-
500kHz
LINE TRAPS
RATINGS

 INDUCTANCE IN Mh

 RATED CURRENT

 BLOCKING BANDWIDTH
LINE TRAPS
PRE-COMMISSIONING TESTS

 INSULATION RESISTANCE
MEASUREMENT

 CONTACT RESISTANCE MEASUREMENT


LINE TRAPS MAINTENANCE
YEARLY CHECKS

 TIGHTNESS & CLEANLINESS OF LINE


TRAP INCLUDING TUNING UNIT

 TIGHTNESS OF TERMINAL CONNECTOR


CVT / PT
 BASICALLY A CAPACITANCE POTENTIAL
DIVIDER

 PROVIDED ON LINE / BUS FOR


MEASUREMENT / PROTECTION SYSTEM

 WHEN USED FOR PLCC PURPOSES CVTs


ARE USED
CVT / PT
RATING

 RATED PRIMARY VOLTAGE

 RATED SECONDARY VOLTAGE

 RATED BURDEN OF CORES

 CAPACITANCE IN pF (FOR CVT ONLY)

 CLASS OF ACCURACY
CVT
POWERGRID NORMS

 3 SECONDARIES (2 FOR PROTECTION


AND ONE FOR METERING)
 OUTPUT BURDEN 50 VA MINIMUM FOR
EACH SECONDARY
 3P ACCURACY CLASS FOR PROTECTION
CORES
 0.5 ACCURACY CLASS FOR METERING
CORE
CVT / PT
PRECOMMISSIONING TESTS

 INSULATION RESISTANCE MEASUREMENT

 CONTINUITY OF WINDING

 SECONDARY WINDING RESISTANCE

 VOLTAGE RATIO TEST

 TAN DELTA AND CAPACITANCE MEASUREMENT


CVT
MAINTENANCE MONTHLY

 LEAKAGE OF OIL
CVT
MAINTENANCE QUARTERLY

 MEASUREMENT OF VOLTAGES AT
SWITCHYARD MB
CVT
MAINTENANCE YEARLY

 CHECKING OF EARTHING OF HF POINT

 DAMAGE TO BUSHING OF HF POINT

 CLEANING OF PORCELAIN INSULATOR STACKS


AND TIGHTNESS OF TERMINAL CONNECTOR

 THERMOVISION SCANNING

 CHECKING OF NEUTRAL EARTHING


CVT
MAINTENANCE 3 YEARLY

 MEASUREMENT OF TAN DELTA AND


CAPACITANCE BETWEEN HV AND HF
POINT (TAN DELTA IS RATIO OF
RESISTIVE COMPONENT OF CURRENT
TO CAPACITIVE COMPONENT)
CVT
MAINTENANCE 3 YEARLY

TAN DELTA LIMITS

 +0.002 W.R. T. PRECOMM VALUE (IN


THREE YEARS)
 +0.002----+0.003 (IN EACH YEAR)
 MORE THAN +0.003 (ALARMING)
CVT
MAINTENANCE 3 YEARLY

 CAPACITANCE VARIATION LIMITS

 +/- 2% WITH RESPECT TO PRECOMM


VALUE ( 3YEARS)
 +/- 2% TO +/- 3% (1 YAER)
 +/-3% TO +/- 6 % (ALARMING)
 MORE THAN 6% (REPLACE)
CURRENT TRANSFORMERS
 PROVIDED FOR MEASUREMENT OF
SECONDARY CURRENTS FOR METERING
/ PROTECTION PURPOSES

 LIVE TANK OR DEAD TANK TYPE


CURRENT TRANSFORMERS
RATINGS

 RATED CURRENT WITH EXTENDED


CURRENT LIMITS

 VA BURDEN OF SECONDARIES

 NO. OF SECONDARIES

 ACCURACY CLASS
CURRENT TRANSFORMERS
RATINGS

POWERGRID NORMS

 120% EXTENDED CURRENT RATING FOR 2000/1


TAP RATIO OTHERWISE 200%
 420 KV CT HAS 15 MIN. 200% THERMAL RATING
AT 2000/1 AND 120% CONTINUOUS
 5 NOS. SECONDARIES IN WHICH 3RD IS FOR
METERING
 ACCURACY CLASS 0.2 FOR METERING CORE
AND PS FOR PROTECTION CORES
CURRENT TRANSFORMERS
PRECOMMISSIONING TESTS

 INSULATION RESISTANCE MEASUREMENT

 CONTINUITY TEST

 SECONDARY WINDING RESISTANCE

 POLARITY TEST

 TAN DELTA AND CAPACITANCE MEASUREMENT

 CURRENT RATIO TESTS

 MAGENTISING CURVES PERFORMANCE

 CONTACT RESISTANCE MEASUREMENT


CURRENT TRANSFORMERS
MAINTENANCE MONTHLY

 CHECK OIL LEAKAGE FROM CT

 CHECKING BELLOW FOR EXPANSION

 CHECK OIL LEAKAGE FROM SECONDARY


TERMINALS

 CHECKING HEALTHINESS OF GASKETS


CURRENT TRANSFORMERS
MAINTENANCE YEARLY

 CLEANING

 TIGHTENING OF TERMINAL
CONNECTORS AND SECONDARY
TERMINALS

 THERMOVISION SCANNING
CURRENT TRANSFORMERS
MAINTENANCE 2 YEARLY

1. TAN DELTA & CAPACITANCE MEASUREMENT

 ACCEPTABLE LIMIT FOR TAN DELTA 0.007

 INCREASE IN PRE-COMM VALUE AT 0.001 PER YEAR UPTO


0.007

 IF VALUE IS BETWEEN 0.007 TO 0.01 THEN HALF YEARLY


MONITORING

 ABOVE 0.01 REPLACE THE CT

2. NITROGEN PRESSURE CHECKING


ISOLATORS AND
EARTH SWITCH
USED TO DISCONNECT THE
CIRCUIT OFFLINE

VERY IMPORTANT EQUIPMENT


WHICH ENSURES SAFETY DURING
MAINTENANCE
ISOLATORS AND E/S
RATING AND TYPES

 RATED IN CURRENT CAPACITY ALONG


WITH VOLTAGE CLASS

 TYPES
HORIZONTAL CENTRE BREAK
DOUBLE BREAK
PENTOGRAPH
ISOLATORS AND E/S
PRECOMMISSIONING TESTS

 INSULATION RESISTANCE MEASUREMENT

 INTERLOCKS CHECKING

 OPERATING TIME

 AUXILIARY CONTACT CHECKING

 CONTACT RESISTANCE MEASUREMENT


ISOLATORS AND E/S
MAINTENANCE

 CLEANING & LUBRICATION

 TIGHTENING

 ALIGNMENT

 CONTACT RESISTANCE MESUREMENT


(ONCE IN A 4 YEARS)