• Feroze Gandhi Unchahar Thermal Power Plant is located at Unchahar
in Raebareli district in Indian
state of Uttar Pradesh. The power plant is one of the coal based
power plants of NTPC Limited.
• Capacity:
• STATOR PROTECTION - The neutral of star connected winding is connected to primary of neutral
grounding transformer, so that earth fault current is limited by over voltage relay.
• DIFFERENTIAL PROTECTION - In case of phase-to-phase fault generator is protected by
longitudinal differential relay.
• ROTOR PROTECTION - Rotor winding may be damaged by earth faults or open circuits. The field is
biased by a dc voltage, which causes current to flow through the relay for an earth fault anywhere
on the field system.
• OVER SPEED PROTECTION – Mechanically over speed device that is usually in the form of
centrifugally operated rings mounted on the rotor shaft, which fly out and close the stop valves if
the speed of the set increase more than 10%.
• OVER VOLTAGE PROTECTION – It is provided with an over voltage relay. The relay is usually
induction pattern. The relay open the main circuit break and the field switch if the over voltage
persists.
• SEAL OIL SYSTEM – Hydrogen in the generator is under very high pressure. There is a possibility of
this hydrogen to come out of gaps, which is very hazardous. So, seal oil is used to seal the gaps so
that hydrogen doesn’t come out.
• LUBRICATION OIL SYSTEM –Turbine lubrication-oil system seeks to provide proper lubrication of
turbo generator bearings and operation of barring gear. Pumps are used to circulate lubrication-
oil inside the generator. The oil of the lubrication and the governing system is cooled in the oil
coolers. The cooling medium for these coolers is circulating water.
TRANSFORMERS
• TYPE PF TRANSFORMERS—
• UNIT AUXILIARY TRANSFORMER : --This is a step down transformer. The
primary receives from generator and secondary supplies a 6.6 KV bus. This
is oil cooled. These are 8 in number.
• NEUTRAL GROUNDED TRANSFORMER : --This transformer is connected
with supply coming out of UAT in stage-2. This is used to ground the excess
voltage if occurs in the secondary of UAT in spite of rated voltage.
• GENRATOR TRANSFORMER : -- This is a step up transformer. This supply
gets its primary Supply from generator and its secondary supplies the
switchyard from where it is transmitted to grid. This transformer is oil
cooled. The primary of this transformer is connected in star. The secondary
is connected in delta. These are four in number.
• STATION TRANSFORMER : --This transformer has almost the same rating as
the generator transformer. Its primary is connected in delta and secondary
in star. It is a step down transformer. These are 4 in number.
DC SYSTEM
1. BUS BAR
4. BREAKER
6. CORONA RING
7. EARTHING ROD
8. CURRENT TRANSFORMER
9. POTENTIAL TRANSFORMER
TYPE MADRAS
VOLTAGE 245 KV
CURRENT 10 KA
A capacitor voltage transformer (CVT) is a transformer used in power systems to step-down extra
high voltage signals and provide low voltage signals either for measurement or to operate a
protective relay. In its most basic form the device consists of three parts: two capacitors across
which the voltage signal is split, an inductive element used to tune the device to the supply
frequency and a transformer used to isolate and further step-down the voltage for the
instrumentation or protective relay as shown in figure below.