Beruflich Dokumente
Kultur Dokumente
Department- EPS
Area- MRSS-1 and 21671bxjxf
At MRSS2- 120 MVA ,Tr-2 LV neutral bus bar was not matching with neutral bushing
palm connector resulting of oil leakage from bottom of bushing. Therefore as a step of
modification we connected these two with 4 - 12x 40 sq mm Cu flexible adequate for 56 KA for
3 sec STR. 120
Before After
Copyright © 2010 Jindal Steel & Power Ltd.
Thank you