Beruflich Dokumente
Kultur Dokumente
CTI
Relay closest to fault operates first
Relays closer to source operate slower
t Time between operating for same
current is called CTI (Clearing Time
Interval
CTI
50 50
+2 +2
(TOC) Coordination
Relay closest to fault operates first
Relays closer to source operate slower
Time between operating for same
t current is called CTI
CTI
Time Overcurrent Protection
(TOC)
• Selection of the curves uses
L L
B b
2 4
d D
L c L I
3
C
Types of Protection
Voltage
Uses voltage to infer fault or abnormal
condition
May employ definite time or inverse time curves
May also be used for undervoltage load shedding
◦ Simple
◦ May be slow
◦ Selectivity at the cost of speed (coordination stacks)
◦ Inexpensive
Current Transformers
100 V = 20 * 5 * (1ohm)
200 V = 20 * 5 * (2 ohms)
400 V = 20 * 5 * (4 ohms)
800 V = 20 * 5 * (8 ohms)
Voltage Transformers
• Voltage (potential) transformers are used to isolate
and step down and accurately reproduce the scaled
voltage for the protective device or relay
• VT ratios are typically expressed as primary to
secondary; 14400:120, 7200:120
• A 4160:120 VT has a “VTR” of 34.66
Switchgear Defined
Assemblies containing electrical switching,
protection, metering and management devices
Used in three-phase, high-power industrial,
commercial and utility applications
Covers a variety of actual uses, including motor
control, distribution panels and outdoor
switchyards
The term "switchgear" is plural, even when
referring to a single switchgear assembly (never
say, "switchgears“)
Switchgear Examples
Switchgear:
MetalClad vs. Metal-Enclosed
Metal-clad switchgear (C37.20.2)
◦ Breakers or switches must be draw-out design
◦ Breakers must be electrically operated, with anti-
pump feature
◦ All bus must be insulated
◦ Completely enclosed on all side and top with
grounded metal
◦ Breaker, bus and cable compartments isolated by
metal barriers, with no intentional openings
◦ Automatic shutters over primary breaker stabs.
Metal-enclosed switchgear
◦ Bus not insulated
◦ Breakers or switches not required to be draw-out
◦ No compartment barriering required
Switchgear Basics
All Switchgear has a metal
enclosure
Metalclad construction
requires 11 gauge steel
between sections and main
compartments
Prevents contact with live
circuits and propagation of
ionized gases in the unlikely
event of an internal fault.
Enclosures are also rated as
weather-tight for outdoor
use
Metalclad gear will include
shutters to ensure that
powered buses are covered
at all times, even when a
circuit breaker is removed.
Switchgear Basics
Devices such as circuit breakers or fused
switches provide protection against short
circuits and ground faults
Interrupting devices (other than fuses) are
non-automatic. They require control signals
instructing them to open or close.
Monitoring and control circuitry work
together with the switching and interrupting
devices to turn circuits on and off, and guard
circuits from degradation or fluctuations in
power supply that could affect or damage
equipment
Routine metering functions include
operating amperes and voltage, watts,
kilowatt hours, frequency, power factor.
Switchgear Basics
Power to switchgear is
connected via Cables or Bus
Duct
The main internal bus carries
power between elements
within the switchgear
Power within the switchgear
moves from compartment to
compartment on horizontal
bus, and within
compartments on vertical
bus
Instrument Transformers
(CTs & PTs) are used to step
down current and voltage
from the primary circuits or
use in lower-energy
monitoring and control
circuitry.
SF6 and Vacuum Breakers
A Good Day in System
Protection……
◦ CTs and VTs bring electrical info to relays
◦ Relays sense current and voltage and declare
fault
◦ Relays send signals through control circuits to
circuit breakers
◦ Circuit breaker(s) correctly trip