SitePro UPS 400Vac / CE

GE Consumer & Industrial


August 2004
Applications

Computer and Data Centers


Server Farms
Process Control
Broadcasting / SAT Systems
Radar control installations
Air traffic control
Internet Service Providers
Safety Systems in Power Plants
Medical Imaging Equipment

Mission Critical Applications requiring highest levels of protection


and reliability
2
Range

- Separate bypass feed


10-40 kVA 60-120 kVA possible
- Maintenance bypass
150-300 kVA 400-500 kVA integrated
- Same control electronics
3 across the range
Main Features

• True On-Line, double conversion


with isolation transformer (VFI)
• State of the art technology
• Small footprint
• High efficiency (up to 94.5%)
• Best in class Output Power Factor
• Superior Battery Management (SBM)
• Back feed protection

• RPA configuration up to 8 units


• Extensive Interfacing Features
4
• Various options
Concept

• independence of the
input and output voltage
and frequency (VFI)

• no break transfer to
battery or bypass power

• output transformer for


galvanic isolation

• manual bypass to
facilitate maintenance
• back feed protection
(standard)

5
Back feed protection
back feed protection K6

Bypass Static Bypass

Thyristor IGBT
rectifier DC link voltage Inverter
Inverter
isolation
transformer
Battery bank
Mains
DC Cap
Load

• Back feed protection K6 : preventing feedback to the mains from the


inverter in case of mains failure and a fault in the bypass circuit
• It provides a safer environment for end users and engineers
• GE provides back feed protection as a standard. Others as option
• Back feed protection is mandatory according to EN62040-1 (UPS safety)

6
State of the Art Technology

Fully digital • Higher reliability


• Less parts count • Easy customisation
• No potentiometers

DSP inside + SMD • Higher reliability due


• Faster POS to higher integration
(Power Operating System) • Enhanced overall
reliability
• Improved immunity against
electrical disturbances

IGBT & SVM • Digital IGBT control


• High efficiency • Energy savings
7
Softstart

The thyristor rectifier can be activated gradually. In that


way the full load will not be connected to the utility or
genset preventing an instable situation. Softstart is
programmable (default: 30 seconds)
Thyristor rectifier
Soft start by
changing the firing
angle of thyristors

Mains

Please note
Current that soft start
100%
From Talud is not related
to inrush
Mains 0%
time current

8
Performance IEC 62040-3

Level 1: Output voltage dependency from utility XXX YY ZZZ

VFI – Topology ( Double conversion/on-line) ~- - Load


~
Utility

Voltage & Frequency Independent Rectifier Inverter

SitePro Battery

Impedance

VI – Topology ( UPS-Utility-Parallel operation / single Utility ~ Load


~
conversion / Line-interactive ) Converter
~
Voltage Independent -
Battery Inverter &
Charger

Utility
VFD – Topology (off-line) Load

~- -
Voltage & Frequency Dependent ~
Charger Battery Inverter Switch

9
Performance IEC 62040-3

Level 2: Output voltage quality depending on load (XXX YY ZZZ)

S S Sine wave: THD < 8% (IEC 61000-2-2/-4) for all


linear and non-linear loads (SitePro)

X X Non-sine wave: THD > 8 % with


non-linear load

Y Y Non-sine wave: out of tolerance of


IEC 61000-2-2/ -4

Battery operation
Normal operation

10
Performance IEC 62040-3

Level 3: Dynamic output voltage behaviour (XXX YY ZZZ)

Class 1 SitePro

Class 2

Class 3

Z Z Z

Dynamic load changes with non-linear load (0% – 100%– 0%)


Dynamic load changes with linear load (0% – 100% – 0%)
Change of operation mode (Utility – battery / Inverter - By-pass)
11
Performance IEC 62040-3

SitePro Classification: VFI – SSS - 111


VFI Voltage & Frequency Independent
Frequency Converter operation available

SS Output voltage THD < 8% for all loads


SitePro: THD < 3% for all loads
Class 1
111 Class 1 performance

SitePro exceeding Class 1


‘’Best in Class’’ dynamic response:
+/-2% at load step: 0-100%-0
+/-1.5% at load step: 0-50%-0 SG Series

SitePro maintains its performance, also at unbalanced loads

12
Output Power Factor

Trend: most computer power supplies have power factor correction


That means UPS systems have to supply loads with a high power factor
SitePro has an output power factor (PF) higher than industry standard
This prevents the need for over sizing the UPS

Example Load: Standard UPS: SitePro:

80 kVA / 70 kW 80 kVA / 64 kW 80 kVA / 72 kW


PF: 70/80 = 0.875 PF: 64/80 = 0.80 PF: 72/80 = 0.90

In this case a standard UPS with output power factor 0.8 is not sufficient to
supply the load, even though the rating is 80kVA.
SitePro UPS can deliver more active power (kW) in comparison to an other UPS
of the same rating

13
Efficiency

Often a UPS is oversized with respect to the load


Usually it runs at partial load (in particular in parallel configurations)
For most UPS systems this is not the optimal working point
This causes the efficiency to be lower than at nominal power
With a special inverter control strategy the SitePro has a very constant
efficiency, for every load situation
Efficiency vs. Load

95% Typical point of


90% specification: full load
Efficiency

85%

80%
Typical area of
75%

70%
practical use
25% 50% 75% 100%
Load

SitePro Other UPS

14
Efficiency – Super ECO Mode

Bypass

AC DC
DC AC

VFI Concept: Balance:

+ optimal protection for For less critical loads run UPS on


mission critical applications bypass continuously
- energy losses
In case mains is out of limits
transfer the load to inverter

Super ECO Mode: not only is the load supplied on bypass, but the
inverter is also switched off, increasing energy savings

15
Efficiency – Super ECO Mode

< 2ms
Output voltage Bypass on/off

Inverter current

Inverter control

Fast Transfer to Inverter


Super ECO mode
• Efficiency : 98%
• to Inverter in case Bypass is out of limits
• Fast error detection
Click here for more
details on Super ECO
• Extremely short transfer times (<2 ms)
Mode
• User definable scheduling
• Available for 10 – 500 kVA
16
Superior Battery Management

SLA and NiCad batt Because the thyristor rectifier can be controlled,
the DC voltage can regulated down; just below
Application flexibility the battery voltage. In that way the batteries
High recharge current available can be tested. In case the batteries would have
a failure, the rectifier is still supplying sufficient
To support large battery DC voltage to support the inverter.
capacities
Prediction of true backup time Thyristor rectifier

No surprises
Charger temp. compensated
To prevent overcharging Mains

Progammable safe battery test


Decreasing the DC
No risk to interrupt load supply voltage making a
current flow from
Battery earth fault detection the batteries
Safety for personell
17
Reliability

SitePro is one of the most RPA features


Reliable UPS systems in the market, • Up to 8 units in parallel
using proven technology • Any UPS able to be the logic leader
• Decentralized bypass
To increase system reliability more
• Redundant Communication Bus
units can be connected in parallel
with GE‘s unique RPA concept • Transparent failover and recovery
process
Utility Supply • True redundancy with no single point
of failure

Click here for


more information
about RPA

To critical load

18
Interfacing Features

1x RS232 Serial Communication Port

6 programmable potential free alarm contacts:


- D plug
- Terminals blocks

1x Emergency Power OFF contact

1x Gen-ON Input contact

1x Control Input contact

Optional: SNMP Interface Card (10/100Mbps auto-select)


MODBUS RTU Interface (RS232 or RS485)

19
Options for SitePro

Option kVA rating: 10-15 20-30 40-60 80 - 300 400-500


5th hamonic filter x x x x
DCU (5th+7th+11th+13th harm.filter) x x
12 pulse rectifier x x standard
12 pulse rectifier with galvanic separation x x x
11th & 13th harmonic filter (with 12 pulse) x x
Active Filter x x
Isolation transformers (rect. and/or bypass) x x x x x
Parallel junction output cabinets x x x x x
Matching battery cabinets x x x x x
Battery fuse box x x x x x
Top cable entry box x x x
Remote monitoring system x x x x x
Remote signalling box x x x x x
Special colours x x x x x
SNMP Interface card x x x x x
JUMP, IRIS x x x x x

20
Conclusion

Highly Reliable
VFI concept
With Isolation Transformer
RPA
Backfeed Protection Standard
Excellent Performance
Softstart
Output exceeding standards
Constant efficiency
Superior Battery Management
Super ECO Mode
Many Options

21