Sie sind auf Seite 1von 79

Ridha Yasser, Ph.D.

C11041301 – SEMESTER GANJIL 2019/2020


Single Phase and Three Phase Systems:

Active and reactive power


Power factor correction
Basic concepts of three phase circuits

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


A multiplication of instantaneous voltage with
instantaneous current at phase difference :

v(t )  Vm cos(t )
i(t )  I m cos(t   )

p(t )  Vm I m cos(t ) cos(t   )


C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
Expression results from integrating
instantaneous power over a single cycle:
1
P  Vm I m cos(t ) cos(t   )
2

In R.M.S. terms, simplifies to:

P  VI cos( )

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


v(t) = 2.25 cos(2π · 60t) Volt
𝜋
i(t) = 3 cos(2π · 60t – ) Ampere
3

Find the average power (Watts) over a cycle.


Solution:
1 𝜋 1
P = V I cos(θ) = (2.25 V) (3 A) cos( ) = (6.75) (0.5) = 1.6875 W
2 3 2

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


Load Convention

Active power absorbed by the load is positive.


Reactive power can be positive or negative.
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
v(t) = Vm cos(ωt) = Vm cos(ωt + δ)
i(t) = Im cos(ωt + β)
𝑄
Power factor angle: θ = (δ – β) = tan -1 ( )
𝑃
Active power: P = V I cos θ
Reactive power: Q = V I sin θ
Apparent power: S = V I* = P + jQ
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
P>0 and Q>0 P>0 and Q<0 P<0 and Q>0 P<0 and Q<0

I lags V I leads V I lags V I leads V


lagging pf leading pf lagging pf leading pf
inductive load capacitive load inductive load capacitive load
P absorbed by load P absorbed by load P delivered by load P delivered by load
Q absorbed by load Q delivered by load Q absorbed by load Q delivered by load

C I V I L
(LEADS)
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
Given: Draw the power triangle:
𝜋
v(t) = 1.5 cos(2π · 60t + ) Volt
6
2𝜋
i(t) = 2 cos(2π · 60t – ) Ampere
3
𝜋 2𝜋 5𝜋
Power factor angle: θ = (δ – β) = ( + )= = 150
6 3 6

5𝜋
Active power: P = V I cos θ = 1.5 cos ( ) = - 1.29 W
6

5𝜋
Reactive power: Q = V I sin θ = 1.5 sin ( ) = 0.75 VAR
6

Apparent power: S = 𝑃2 + 𝑄2 = 1.292 + 0.752 = 1.49 VA


C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
Given: V = 2.77∠ 15° Volt I = 1.14 ∠ -27° Ampere

θ = (δ – β) = (15° - (-27°)) = 42° I* = 1.14 ∠ +27° Ampere


Calculate active and reactive power and power factor

S = V I* = (2.77 ∠ 15°) (1.14 ∠ +27°) = 3.16 ∠ 42° VA


= 2.35 + j 2.11 VA = P + j Q VA
P = 2.35 Watt
Q = 2.11 VAR
pf = cos θ = cos(42°) = 0.743 , lagging
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
Absorbed by resistive
load

Always positive when


V and I are in phase

Average is nonzero

Periodic at double
frequency
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
Absorbed or generated
by reactive load

Changes sign

Average is zero

Periodic at double
frequency

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
𝜋
Given: v(t) = 3 cos(2π · 60t) Volt i(t) = 1.14 cos(2π · 60t – ) Ampere
4

Find phasor expressions for voltage, current, and complex power.


V = 3 ∠ 0° Volt I = 1.14 ∠ 45° Ampere
θ = (δ – β) = (0° – 45°) = –45° I* = 1.14 ∠ –45 ° Ampere

S = V I* = (3 ∠ 0°) (1.14 ∠ –45°) = 3.42 ∠ –45° VA


= 2.15 – j 2.15 VA
= P + j Q VA
P = 2.15 Watt Q = – 2.15 VAR
pf = cos θ = cos(–45°) = 0.707 , leading
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
Given: V = 5 ∠ 30° Volt I = 2 ∠ –45° Ampere
Calculate active, reactive and apparent power

Solution 1: P = V I cos(δ – β) = 10 cos(75°) = 2.59 Watt


Q = V I sin(δ – β) = 10 sin(75°) = 9.66 VAr
S = V I ∠ (δ – β) = 10 ∠ 75° = 2.59 + j 9.66 VA
Solution 2:
S = V I* = (5 ∠ 30°) (2 ∠ +45°) = 10 ∠ 75° VA
= 2.59 + j 9.66 VA
= P + j 9.66 VA
P = 2.59 Watt Q = 9.66 VAr
pf = cos θ = cos(75°) = 0.259 lagging

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


Two connection schemes:

“Wye” or “Y” connection

“Delta” or “” connection

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


“Wye” connection joins neutrals of each phase at a common junction.

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


“Delta” connection has no neutral, and each vertex forms a bus.

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


Wye connected Delta connected

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


A three-phase source is balanced when each leg
produces equal magnitude voltage, with phase
difference between any two phases.

A three-phase load must have the identical


impedances on each phase to be balanced.
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
By convention, the three phases are designated a, b, and c.

If a phase is chosen as reference, then the balanced line-to-


neutral voltages in a wye-connected generator will be:
Ean = Eln ∠ 0° V
Ebn = Eln ∠ -120° V
Ebn = Eln ∠ +120° V

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


A system of three unbalanced phasors can be resolved in the following three symmetrical
components:
• Positive Sequence: A balanced three-phase system with the same phase sequence as the original
sequence.
• Negative sequence: A balanced three-phase system with the opposite phase sequence as the original
sequence.
• Zero Sequence: Three phasors that are equal in magnitude and phase.

Unbalanced Positive Negative Zero


Load Sequence Sequence Sequence
e.g., the positive, negative and zero sequence components of phase-a are denoted by Va1, Va2
and Va0 respectively
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
Ecn

Ean

Ebn

This diagram shows a.b.c. or positive sequence, in which


Ean leads Ebn by 120, and Ebn leads Ecn by 120.
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
Eb
n

Ean

Ec
n

In this alternative arrangement, called a.c.b. or negative


sequence, Ean leads Ecn by 120, and Ecn leads Ebn by 120.
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
In a wye-connected generator, line-to-line voltages can be
calculated from line-to-neutral voltages.
The line-to-line voltages are greater in magnitude by a factor
of 3, and they lead the line-to-neutral voltages by 30º:

El l  3El n 30

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


Balanced line-to-line and line-to-neutral voltages:
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
Find the positive sequence line-to-line voltages in the balanced wye-
connected generator if the line-to-neutral voltages have a magnitude
of 12 kV, and phase a is the reference.

Solution: Ell = √3 Eln ∠ +30° kV


= 20.8 ∠ +30° kV
Eab = 20.8 ∠ 30° kV
Ebc = 20.8 ∠ -90° kV
Eca = 20.8 ∠ 150° kV
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
Line currents in a three-phase system can be calculated from
phase voltages and impedances.

For a balanced system with a wye-connected load, the line


current equation is:
El n
IY 
ZY

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


The illustration shows
balanced load currents
in a wye-connected
load:

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


Balanced load currents in
a delta-connected system
are obtained from:

El l
I 
Z

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


Given a wye-connected load of impedance ZY=1030° and
balanced positive sequence source with Ean=14.40°kV, find
the load currents.
Solution: El n
IY 
ZY
Ean 14.40 kV
IA    1.4430 kA
ZY 1030 
Ebn 14.4120 kV
IB    1.44150 kA
ZY 1030 
Ecn 14.4120 kV
IC    1.4490 kA
ZY 1030 

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


The practice of improving a lagging power factor by installing
capacitors in parallel with an inductive load is called power
factor correction.
Inductive load = lagging power factor
Capacitive load = leading power factor
It is desirable to operate with power factor close to unity for
better efficiency and voltage regulation.

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


P  Ql  Qc
To improve the Power Factor:
Qc Parallel a Capacitor to the
P  Ql Inductor
<
Qc
S P – constant
Ql  Qc  Q Q – decrease
 
P

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


Given:
A single-phase source which delivers 80 kW to a load at 0.7 pf lagging.
If the source voltage is 480 V, calculate the current required by this
load.
Solution: P  VI  pf  80 kW
P 80 kW
S  VI    114 kVA
pf 0.7
Q  (S2  P 2 )  81.6 kvar
power factor angle  cos -1 (0.7)  45.6
S 114 kVA
I   238 A
V 480 V

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


Given:
Determine the capacitive reactance needed to reduce the power factor to 0.9
lagging in the previous example.

Solution (students to verify calculations as an exercise):


Before pf correction: After pf correction: Net XC needed:

X C  1.55 

R  2.88  R  2.88 
X L  2.94  X L  1.39 

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


In this typical three phase system, the generator has three voltage
sources with equal magnitude and phase difference, and it delivers
power to a balanced wye connected load.
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
Voltages applied to the load in a balanced
three-phase system are:

Van  V0
Vbn  V  120
Vcn  V  240

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


Line voltage has a magnitude of 3 times phase voltage, and it leads
the corresponding phase voltage by 30.

Line-to-line voltages are calculated as follows:

Vab  Van  Vbn  3Van30  3V30


Vbc  Vbn  Vcn  3Vbn30  3V  90
Vca  Vcn  Van  3Vcn 30  3V  210

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


A three phase power system consists of a wye connected generator
connected to a balanced wye connected load of impedance ZL=1030 °
per phase and a terminal load voltage of 3.2 kV. Neglecting feeder
impedance, determine line current supplied by the generator.

Solution: Select phase a as reference.

Van (3200 / 3 )0V


I a  I an    184.8  30A
ZL 1030

I b  184.8  150A
I c  184.890A

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
Semester Ganjil 2017 / 2018
Ridha Yasser, Ph.D.
C11041301 – TRANSFORMATOR & MESIN INDUKSI
44

2003 IEEE/PES
Transmission and Distribution Conference & Exposition

Presented by
Jack Bateman, P.E.
Oncor

September 9, 2003

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
46

Apparent Power
Volt - Ampere ( VA )

Reactive Power
Volt - Ampere Reactive
(VAR )
θ V = Voltage
Active Power
( WATTS )
θ
I = Current
Apparent Power = Voltage * Current
Apparent Power = Active Power + Reactive Power

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


Reactive Power
θ
Active Power
Apparent Power = V * I = Active Power + Reactive Power

Active Power = Apparent Power Cos θ


*
Active Power = Apparent Power Power Factor
*
Reactive Power = Apparent Power
* Sin θ
Power Factor = Cos θ = Active Power / Apparent Power
C11041301 GANJIL 2019/2020 47
TRANSFORMATOR & MESIN INDUKSI
48

V I cos θ = │I│2 R V I sin θ = │I│2 X


Where R is Resistance Where X is Reactance

Does Work Does No Work

Energy Converted to Heat, Light, Or Work No Energy Converted, No Heat Generated

Energy Periodically Stored In the Magnetic


Energy Is Consumed, No Energy Storage Field of an Inductor or the Electric Field of a
Capacitor, then Discharges Back to the
System -- No Energy Is Lost

The Total Active Power Generated Must


Equal Total Active Power Consumed The Total Reactive Power Produced Must
Equal the Total Reactive Power Required

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


49

VARs are supplied by passing current through a


capacitance

VARs are delivered by passing current through an


inductance

VARs are supplied by - generators, line charging,


capacitors, other specialized equipment

VARs are delivered to - reactors, T&D lines, induction


motors
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
A lot of engineers call the reactive
component of current and the Reactive Power Loss
reactive component of apparent
power “ imaginary “. 2
I X

Imaginary current or power couldn’t


possibly affect the real world
power system, could it ?

It sure does, “ imaginary “ is just a


bad choice of terms.

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


Reactive Current Is a Vector Component of Load Current

Reactive Current Increases the Magnitude of Load Current

Reducing Reactive Current Increases Power Factor,, Reduces Load Current

For 500 KW Load


Power Reactive Load
Factor Current Current
(%) (Amps) (Amps)
65 27 36
71 23 33
78 18 30
86 14 27
93 9 25
98 5 24
100 0 23 Active Current

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


52

An amp of reactive current uses as much line and


equipment capacity as an amp of active current
Reactive current increases active and reactive
power losses
Reactive current increases voltage drop

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


53

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


54

Transmission System Loaded To Higher Level

Generating Units Remote To Load Centers

Power Purchases and Retail Competition

Increased Load Growth

Increased Active and Reactive Power Losses

Limited Dynamic and Static Reactive Capacity


C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
55

Reactive problems have a way of sneaking up on you -


They evolve slowly as the transmission system becomes
heavily loaded

Reactive capacity may be sufficient for normal operating


conditions, however, sufficient dynamic reactive capacity
may not be in place to recover from major system
disturbances

Reactive problem may not be recognized until it’s too late


C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
56

VAR flows create excessive voltage drop on transmission


lines and transformers

Insufficient dynamic reactive resources to maintain system


voltage control and serve reactive load and reactive losses
under contingency conditions

VAR flows increase loading on transmission lines utilizing


valuable line capacity

VAR flows increase active and reactive power losses


C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
57

Voltage profile changes with load level

Low Voltage - Contingencies

Marginal transmission system voltages under normal


conditions

Generators and transformers out of regulation

Voltage Collapse

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


A progressive and uncontrolled decrease in voltage,
typically triggered by a major disturbance to a
heavily loaded transmission system with insufficient
dynamic reactive resources to serve reactive
losses and return voltage to acceptable levels,
resulting in partial or total blackout.

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


59

Heavy loading on transmission lines significantly increases reactive


losses requiring additional reactive resources to serve

Voltage drop across 345 kV transmission lines is predominantly


caused by line reactance which is 8-10 times line resistance

Delivering 1 MVAR results in 8-10 times as much voltage drop as


delivering 1 MW on the 345 kV transmission system

Excessive Voltage Drop Is the Penalty Paid for Delivering


Reactive Power On the Transmission System
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
60

R X
VS Vr Vs-Vr = I ( R + j X )

I
VS

jIX Vs–Vr =│I│(cosθ + jsinθ) (R+jX)


Vr
 Vs–Vr =│I│(cosθ R+jcosθ X+jsinθ R-sinθ X)
I IR

VS
│Vs-Vr│≈ │I│cos θ R - │I│sin θ X

Vr j |I| X cos

|I| R cos  │Vs-Vr│≈ IACTIVE * R – IREACTIVE * X


|I| X sin 
j |I| R sin 
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
61

Vs 100 Mile 345 kV T-Line


Z=.00545 + j.04752 PU @100MVA
Vr

L
O
Line Charging = 92.3 MVARS A
D

GENERATION Vs LINE LOSS Vr LOAD │ Vs – Vr│


(%)
(MW) ( MVAR ) (%) ( MW ) ( MVAR ) (%) ( MW ) ( MVAR )

514 24 103.5 14 119 100.2 500 0 3.3

24 634 103.5 24 208 72 0 500 31.5

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


Add more reactive generating capacity

Add more transmission capacity

Add more reactive sources close to the load center to


reduce reactive loading on transmission system

and
Reserve generating unit reactive capacity for
contingencies
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
63

Static Synchronous Compensator 45


Synchronous Condenser 40
Static VAR Compensator 35
Transmission Capacitors 21
Substation Capacitors 16
Distribution Feeder Capacitors 12

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


64

“I’m a distribution operating technician and we


have low voltage problems on very few
distribution feeders. If there’s a low voltage
problem on the transmission system, that’s their
problem, it doesn’t have anything to do with me.”

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


65

Generation, the transmission system, the distribution system,


and load make up an integrated power system.

The relationship between them is determined by the laws of


physics and is not a function of the business unit you’re in.
Each cannot operate independently from the others.

Reactive resources should be installed where the capacity will


do the most good and the installation is cost effective.

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


RECOMMENDATIONS
Distribution Maintain a Minimum 99 % Lagging Power
Factor Measured at Low Side of Substation
Transformer
Transmission Install Capacitors On Transmission
System To Maintain Adequate Voltage and Reactive
Reserve On Generating Units
Generation Ensure Full Reactive Generating Capability
Available On All Units
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
67

What is reactive compensation …

and what do those capacitors do ?

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


68

The Installation of a Reactive Source Close to the Load Center to


Reduce Reactive Loading On Up-line Equipment and Lines
Improves Up-line Power Factor
Reduces Transmission and Distribution Line Voltage Drop
Reduces Active and Reactive Power Losses
Reduced Reactive Loading On Lines and Equipment
Allows Delivery of More Active Power
Minimizes the Amount of Reactive Capacity Needed to Support
Voltage
Maintains Adequate Reactive Reserve On Generating Units To Control
Voltage and Serve Reactive Load Under Contingency Conditions

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


69

Power Factor on Low Voltage Side of Substation Transformer

1.0
1.00
POWER FACTOR
FACTOR

.99
.99

Load Power Factor


.98
.98
POWER

.97
.97

> 80 % Peak 99 - 100%


40 - 80 % Peak 97 - 100%
40
40% 50
50% 60
60% 70
70% 80
80% 90
90% 100
100% < 40 % Peak 97 - 99%

% of%Peak Load
OF PEAK LOAD

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


70

Use Watt / VAR Data To Determine Appropriate


Control Settings for Individual Feeders
Aggregate Feeders To Meet Power Factor
Guideline On Low Side of Substation Transformer
If There Is Not a High Voltage Problem, a Feeder
May Go Leading To Compensate for a Feeder
Which Cannot Be Corrected So That the
Aggregate Power Factor Meets Power Factor
Guideline
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
71

Power Factor Is the Percentage of Apparent Power Delivered


To Customers In the Form of Active Power
Active Power - Uses System Capacity - Metered To
Customers
Reactive Power - Uses System Capacity - Historically Not
Metered To Customers – Implementing Power Factor Penalty
Power Factor Is a Measure of How Efficiently System
Capacity Is Utilized

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


72

Optimize the value and productivity of assets


Obtain the greatest value from assets
Ensure the greatest return on investment

An excellent way to achieve these goals is to


use reactive compensation to reduce loading on heavily loaded or
overloaded distribution circuits

The Cost of a Capacitor Bank is significantly less than


the Cost to Rebuild or Re-conductoring a Circuit

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


73

Source Induction
Source Induction
Motor
Motor Feeder
Feeder M
M
I feeder I motor
I feeder I motor IC

Add Capacitor
then, I feeder = IR + j IX - j IC
I feeder= I motor = IR + j IX
Size Capacitor for 100% Power Factor
I R = Active Current
Capacitor Supplies Motor Reactive
Requirements, I C = I X
I X = Reactive Current
I motor = IR + j IX = IR + j IC
IR
I feeder is Reduced I feeder = IR
IX

I feeder= I motor = IR + j IX I feeder = IR


Feeder Loading Reduced
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
74

UNCORRECTED CORRECTED
500 kW PF = 65 % 500 kW PF = 95 %

θ = 49° θ = 18o
Cos θ = 0.65 Cos θ = 0.95

500 kW ( 23.1 AMPS ) 500 kW ( 23.1 AMPS )

A high power factor relates to a small reactive component


Power factor is the percentage of Apparent Power delivered in the form of Active Power
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
75

Ensure All Existing Capacitors In Service By June 1


Install All Proposed Capacitors By June 1
Optimize Use of Any Customer Owned Capacitors
Conduct Power Factor Awareness Training
Operate Within Power Factor Guideline

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


76

What is reactive compensation…


and what do those capacitors do ?

Reactive compensation is the installation of a


reactive source close to the load center which may
relieve reactive loading all the way back to the
generator. The reduction in reactive loading unloads
lines and equipment allowing delivery of more active
power, improves power factor, reduces T & D line
voltage drop, and reduces active and reactive power
losses. Capacitors are the most cost effective
reactive source.

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI


77
Reactive current and power shouldn’t be referred to as imaginary, it’s just
poor terminology. Reactive current and reactive power are vector
components of load current and apparent power and contribute to their
magnitude. Reactive components of current use up line and equipment
capacity, increase active and reactive power losses, and increase voltage
drop.
Reactive Power Loss
Reactive loading is a fact of life ! 
I2X

because

VARs are for REAL


C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
VARs Are Supplied By Capacitors and Generating Units
VARs Are Delivered To Inductors
Motor Load Is Inductive and the Largest Component of Reactive Load
Reactive Compensation Close to the Load Center Will Ensure Available Reactive Reserve on
Generating Units for Use During Emergency Conditions
Reactive Compensation With Capacitors
 Reduces Reactive Loading On Lines and Equipment
 Allowing Delivery of More Active Power
 Reduces Active and Reactive Power Losses
 Reduces Voltage Drop
Installation of Transmission and Distribution Capacitors Is the Most Cost Effective Solution to
the Reactive Problem
C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI
PERTANYAAN ?

C11041301 GANJIL 2019/2020 TRANSFORMATOR & MESIN INDUKSI

Das könnte Ihnen auch gefallen