Beruflich Dokumente
Kultur Dokumente
IEEE std.1159-1995:
momentary intrup: ber 0.5 cycles and 3 sec
Sustained intrup: longer than 3 sec
Temporary intrup: bet 3 sec and 1 min
IEEE std.1250-1995
Instantaneous : bet 0.5 and 30 cycles
Temporary intrup: bet 2 sec to 2 min
momentary intrup: bet 30 cycles and 2 sec
Sustained intrup: longer than 2 min
•These are slow fuses which will not trigger when a transient fault is
cleared by main circuit breaker .
•A permanent fault can also be cleared by the main breaker, but that would
lead to a long interruption for all customers.
• Permanent fault is cleared by expulsion fuse.
Induction motor – able to maintain some voltage in the system for a short time, that too
only for a few cycles.
Synchronous motor – maintain their field even when the supply voltage disappears.
- able to maintain some system voltage until their load has come to a
standstill.
This could be a problem when large amounts of generation are connected to the feeder.
This is so called embedded generation.
To avoid this problem, this embedded generation is equipped with a loss of grid
protection that disconnects the generator when an unusual voltage or frequency is
detected.
A number of surveys have been performed to
obtain statistical information about voltage
magnitude variations and events.