An on-off controller simply drives the manipulated variable from fully closed to fully open depending on the position of the controlled variable relative to the set point. A common example of on-off control is the temperature control in a domestic heating system. When the temperature is below the thermostat set point the heating system is switched on and when the temperature is above the set point the heating switches off. There is, however, a bit of subtlety applied in practical on-off systems. If the heating switches on and off the instant the measured temperature crossed the set point then the system would chatter - repeatedly switch on and off at very high frequency. If this happened the boiler wouldn't last very long! To avoid chattering, practical on-off controllers usually have a dead band around the set point. When the measured value lies within this dead-band the controller does nothing - its only when the value moves outside that action is taken. The effect of this is to introduce continuous oscillation in the value of the controlled variable - the large the dead-band the higher the amplitude and lower the frequency. The On Off Controller or two position controller is the simplest, cheapest and the most used controllers. It is used in domestic heating systems, refrigeration, water tanks, etc. When the measured variable is below the set point, the controller is ON and the output signal has maximum value. When the measured variable is above the set point, the controller is OFF and output is zero. Due to mechanical friction or arcing of electrical contacts, the controller actually goes on slightly below the set point and goes off slightly above the set point. This differential gap in the controller output may be deliberately increased to give decreased frequency of operation and reduced wear. The favourable conditions for using On Off Controller are as follows: The reaction rate should be slow. There should be little or no dead time. There should be little or no transfer lag.
Dead time causes the value of the measured variable to
go beyond the limit set by the differential gap, since the presence of dead time means a delay in corrective action of the controller. The greater the dead time, the greater the amplitude and period as shown in Fig. 21.4. With both the dead time and the transfer lag, the measured variable exceeds the controller differential gap, as seen from Figs 21.4 and 21.5. With the transfer lag, all the changes are more gradual. Hence, the measured variable peaks due to the effect of transfer lag are rounded off on the two position controllers and are not as sharp as they are due to dead time effect. In an industrial plant, a closed-loop control system has the role of keeping a measured physical signal to a predefined value (set point). The physical signal, also called controlled variable, can be of any kind, electrical (voltage, current, power), mechanical (position, speed, force, torque), hydraulic (pressure, flow) or thermal (temperature). The difference between the controlled variable (measured) and the predefined value is called error. The input of the controller is the error and the controller output is an actuation signal which is send to an actuator. The controlled variable is further measured with a sensor and the information is feed back to the controller. The difference between the set point and the plant output (measured) occurs because of the disturbances which affect the plant (process). The role of the controller is to reject these disturbances and keep the plant output (controlled variable) to the predefined value (set point). The ways in which the controller reacts to the error are called control laws or control modes. In industrial applications there are several control laws used, most of them being on-off control, PID control or other more advanced laws (fuzzy, neuro-fuzzy, optimal, etc.). FEED BACK CONTROLS - Feedback controls are widely used in modern automated systems. A feedback control system consists of five basic components: (1) input, (2) process being controlled, (3) output, (4) sensing elements, and (5) controller and actuating devices. These five components are illustrated in Figure 1. The term closed-loop feedback control is often used to describe this kind of system. The input to the system is the reference value, or set point, for the system output. This represents the desired operating value of the output. Using the previous example of the heating system as an illustration, the input is the desired temperature setting for a room. The process being controlled is the heater (e.g., furnace). In other feedback systems, the process might be a manufacturing operation, the rocket engines on a space shuttle, the automobile engine in cruise control, or any of a variety of other processes to which power is applied. The output is the variable of the process that is being measured and compared to the input; in the above example, it is room temperature. The sensing elements are the measuring devices used in the feedback loop to monitor the value of the output variable. In the heating system example, this function is normally accomplished using a bimetallic strip. This device consists of two metal strips joined along their lengths. The two metals possess different thermal expansion coefficients; thus, when the temperature of the strip is raised, it flexes in direct proportion to the temperature change. As such, the bimetallic strip is capable of measuring temperature. There are many different kinds of sensors used in feedback control systems for automation. The purpose of the controller and actuating devices in the feedback system is to compare the measured output value with. the reference input value and to reduce the difference between them. In general, the controller and actuator of the system are the mechanisms by which changes in the process are accomplished to influence the output variable. These mechanisms are usually designed specifically for the system and consist of devices such as motors, valves, solenoid switches, piston cylinders, gears, power screws, pulley systems, chain drives, and other mechanical and electrical components. The switch connected to the bimetallic strip of the thermostat is the controller and actuating device for the heating system. When the output (room temperature) is below the set point, the switch turns on the heater. When the temperature exceeds the set point, the heat is turned off. Simplicity is the primary reason why On-Off Control is not used in commercial applications. Most homeowners would agree that a certain amount of variability in their oven’s temperature – as an example – is expected. Processes like an oven are simple. For one, they don’t interact with other processes. And second, if you’re a bad cook, then more precise control probably isn’t the answer. In contrast, industrial process manufacturing is complex. Processes are highly dynamic and interactive. Whether in terms of safety or economics, the benefits of more precise control are significant. Following are a few aspects of On-Off Control that you should keep in mind when considering it for commercial application: An Open or Shut Case
As its name implies, On-Off Control assigns the
Controller Output (CO) to one of two positions such that the final control element (FCE) is either fully open or fully closed. Unlike intermediate value or PID control, there is no in between. Most industrial processes require greater latitude when it comes to adjusting the CO’s position. Ups and Downs
On-Off Control can result in excessive variability as
the controller has so few options for maintaining Set Point. A process equipped with On-Off Control will constantly overshoot its Set Point and cycle as a result. The work demanded of the FCE regularly accelerates the time to failure and increases maintenance costs. Setting Boundaries
Deadband is a range of operation around the Set
Point and within which the controller’s action will not change. On-Off Control with Deadband establishes upper and lower boundaries that are acceptable to the control loop’s operation. While Deadband’s “cushion” reduces wear on the FCE, variability remains within the process which can present challenges for other downstream processes. Most industrial processes require tighter control than is possible with On-Off Control. While it is frequently used in industrial HVAC and simple furnaces, On-Off Control is used sparingly in industrial process manufacturing. Given its ability to achieve tighter and more stable control, intermediate value PID-based control is well suited to industrial application requirements. To learn more about these basic and advanced control strategies, consider taking a training course from a recognized authority on process control. Incontrol theory, an on/off controller, also known as a hysteresis controller, is a feedback controller that switches abruptly between two states. These controllers may be realized in terms of any element that provides hysteresis. They are often used to control a plant that accepts a binary input, for example a furnace that is either completely on or completely off. Forexample, a thermostat is a simple negative-feedback control: when the temperature (the “process variable” or PV) goes below a set point (SP), the heater is switched on. Another example could be a pressure switch on an air compressor: when the pressure (PV) drops below the threshold (SP), the pump is powered. Refrigerators and vacuum pumps contain similar mechanisms. The valve in the inflow line to the system is an electrically operated solenoid valve. (Remember an electrically operated solenoid valve has only two operating positions . fully open or fully closed.) Assume that under initial conditions with a demand on the system the level will start to fall and V1 will have to be opened to provide an inflow. This can easily be achieved by mounting a differential pressure switch, P1 at the bottom of the tank to operate when the level falls to L1. When the level is at L1 the liquid will be height h1 above switch. The pressure at the switch will be P1 = ρgh1. ρ. The mass density of the liquid
g. The acceleration due to gravity
h1. The height of the liquid
The resulting switch closure can energize the solenoid valve V1 causing an inflow to the tank. Assuming the valve is correctly sized, this will cause a rise in the level back towards the setpoint. In order to arrest the rise in level the built in differential feature of the switch can be employed to de-energize the solenoid valve when level L2 is reached. This system will achieve a mean level in the tank about the desired setpoint. This method is known as ON/OFF control. Clearly it is impossible to maintain the system at the setpoint since there must be a difference in the operating levels L1 and L2 as the valve can only be energized or de-energized. It is often counterproductive to try to reduce the differential between L1 and L2 to too small a value as this will result in excessive cycling, and hence wear, of the valve. Summary
On/off control – control signal is either
0% or 100% Control at set point not achievable, a dead band must be incorporated. Useful for large, sluggish systems particularly those incorporating electric heaters.