RMU MV TRANSFORMER
RMU PANEL (3 SETS)
INCOMING MV CABLE INCOMING MV CABLE
DP DP
BASEMENT BASEMENT
TECHNICAL FLOOR
TECHNICAL FLOOR
2
VPLAZA - Transformer Relocation
RMU
BASEMENT FLOOR
ORIGINAL DESIGN
BASEMENT FLOOR
ALTERNATIVE DESIGN
3
Transformer Relocation
1 DESCRIPTION
3.1 Technical Advantage - Optimize the power system due to - Easy for maintenance and
reduce voltage loss by using medium replacement.
voltage. - Reduce structural load on top of the
- No commercial space (car park) lost, building.
no impact on NLA.
Disadvantage - Need the replacement method due to - Power transmission through low
put transformer on the roof top. voltage, the power cable so long so it
shall be lost energy.
- Lost the commercial area (77m2) in
basement (carpark). Impact to LNA.
3.2 Costing Investment - Low cost - Hight cost Please see the
- Equipment cost: VND7,237,275,243 - Equipment cost: VND25,572,171,603 attach files of
the BOQ
Operation - Easy for operation, save travel time - difficulties in the management since
from MV, TX, MSB for technician. the long distance from MV to LV side.
Maintenance and replacement method - Crane to lift and replace incase - Easy in the replacement device.
transformer failure.
- Mobile lift truck for equipment.