Sie sind auf Seite 1von 1

Why - Why Analysis

Uneven Power
Shorted Power contacts
contacts Bypass
Magnetic Contactor Melted Power
contacts
Pump Motor
CWP-4 Shorted
Started Output Relay
when panel Malfunction of PLC
is OFF Relay
Melted relay
Circuit
Breaker
Shorted SCR Tripped
rectifier
Shorted Softstarter Soft starter
Unit Spark
Shorted
control Circuit

Root Cause: Shorted Silicon Controlled Rectifier


Recommendation for Safety: Switch Off Motor Isolator if the Valve is
closed to prevent Line overheating if same issue occur in the future