Beruflich Dokumente
Kultur Dokumente
10
► PARALLELING OF DC GENERATORS
► The Armature Reaction
OBJECTIVES:
► To show practical applications of connecting
dc generators in parallel
► To solve sample problems dealing with paralleling
of dc generators
► To explain the concept of Armature Reaction
PARALLELING OF DC GENERATORS
http://www.iecsys.com/scr/images/prop_sys.jpg
PARALLELING OF DC GENERATORS
http://images.google.com.ph/imgres?imgurl=http
GENERATOR PERFORMANCE
DC GENERATORS
DC GENERATOR
CONNECTED
VS IN PARALLEL
1 Megawatt + + + +
_ _ _ _
Power Box
1. Continuous Operation
2. Same polarity
External Characteristics
The curve showing the relationship between output voltage
and output current is known as the external characteristic.
DC Generator Curves
http://images.google.com.ph/imgres?imgurl=http
External Characteristics
You know that for proper commutation, the coil short-circuited by the brushes must be
in the neutral plane. Consider the operation of a simple two-pole dc generator, shown
in figure 1.
View A of the figure shows the field poles and the main magnetic field. The armature is
shown in a simplified view in views B and C with the cross section of its coil
represented as little circles. The symbols within the circles represent arrows. The dot
represents the point of the arrow coming toward you, and the cross represents the tail,
or feathered end, going away from you.
When the armature rotates clockwise, the sides of the coil to the left will have current
flowing toward you, as indicated by the dot. The side of the coil to the right will have
current flowing away from you, as indicated by the cross. The field generated around
each side of the coil is shown in view B of figure 1. This field increases in strength for
each wire in the armature coil, and sets up a magnetic field almost perpendicular to
the main field.
ARMATURE REACTION
http://images.google.com.ph/imgres?imgurl=http
ARMATURE REACTION
In a DC machine, two kinds of magnetic fluxes are present;
'armature flux' and 'main field flux'. The effect of armature flux
on the main field flux is called as armature reaction.
MNA And GNA
EMF is induced in the armature conductors when they cut the
magnetic field lines. But, there is an axis (or, you may say, a
plane) along which armature conductors move parallel to the
flux lines and, hence, they do not cut the flux lines at the
moment. MNA (Magnetic Neutral Axis) may be defined as the
axis along which no emf is generated in the armature
conductors as they move parallel to the flux lines. Brushes are
always placed along MNA because reversal of current in the
armature conductors takes place along this axis.
GNA (Geometrical Neutral Axis) may be defined as the axis
which is perpendicular to the stator field axis.
ARMATURE REACTION
ARMATURE REACTION
Consider, no current is flowing in the armature conductors and
only the field winding is energized (as shown in the first figure
of the above image). In this case, magnetic flux lines due to
the field poles are uniform and symmetrical to the polar axis.
The 'Magnetic Neutral Axis' (M.N.A.) coincides with the
'Geometric Neutral Axis' (G.N.A.).
COMPENSATING WINDINGS or INTERPOLES are used for this purpose (fig. 2). The
compensating windings consist of a series of coils embedded in slots in the pole faces.
These coils are connected in series with the armature. The series-connected
compensating windings produce a magnetic field, which varies directly with armature
current. Because the compensating windings are wound to produce a field that
opposes the magnetic field of the armature, they tend to cancel the effects of the
armature magnetic field. The neutral plane will remain stationary and in its original
position for all values of armature current. Because of this, once the brushes have
been set correctly, they do not have to be moved again.
http://images.google.com.ph/imgres?imgurl=http
ARMATURE REACTION
I. DEMAGNETIZING AT PER POLE
ATd m
ZI a 0
Pole 360
where:
Z = # of conductors
Ia = current in each armature conductor
= IA / a
θm = forward lead in angular degrees
= θ2 / (P/2)
FOR SHUNT:
# EXTRA TURNS ATd
POLE IF
FOR SERIES: IA = IS
ATc 1 m
ZI a 0
Pole 2 P 360
where:
pole arc ZI a
# comp windings x
pole pitch 2 P
= 0.7 (AT/Pole)
Sample Problems
1. A 4 pole generator has a wave-wound armature with 722 conductors,
and it delivers 100A on FL. If the brush lead is 8o, calculate the
armature demagnetizing and cross-magnetizing AT per pole.
2. An 8-pole generator has an output of 200A at 500V, the lap-
connected armature has 1280 conductors, 160 commutator
segments. If the brush are advanced 4 segments from the no-load
neutral axis, estimate the armature demagnetizing and cross-
magnetizing AT per pole.