• SYSTEM STATUS
Date & Time: 26 June 2013, 14:44
Fault duration: 90 ms
150KV: U-Phase drop to 91.4 KV. Drop 60.9 % • 30 KV: • Drop 65.4 % • 6 KV: • Drop 70.7 %
V-Phase drop to 123.6 KV. Drop 82.4 % • Drop 81.1 % • Drop 96.5 %
W-Phase drop to 133.8 KV. Drop 89.2 % • Drop 90.6 % • Drop 82.4 %
Voltage drop
time
Type C
Voltage sag effect: adjustable speed drive controls, Voltage sag solutions: • UPS
programmable logic controllers, Off line
motor contactors On-Line
Computer • Dynamic voltage restorer (DVR)
Lighting • Voltage Regulator
Motor • Static transfer switch
Confidential - All rights reserved
• Static Var Compensator (SVC)
PT KRAKATAU POSCO© 1/31/2011 3
Voltage and Current Response when Voltage Sag Occure
4
Confidential - All rights reserved
PT KRAKATAU POSCO© 1/31/2011