In the template also in the topology a point-to-point connection is defined for the PRE0.
The Data Flow Direction also indicates that the CP-8022 will act as slave in this connection.
The PRE0 was assigned also to the X2 serial interface of the CP-8022
Defaults
LNK_ADR
Addressing Link (only to assign addresses and to
pass information to other links.
Note: Information of this link is never compiled, so
the system works even without it.
LNK_1703_DI
Link for Digital Information from RTUS of the SICAM
1703 family.
LNK_CAExplus
Link to make information accessible to CAEx (logic
editor)
LNK_SCC_BIN
Link to prepare information for SICAM SCC. Ist use is
optional (e.g. a signal can be used in SCC as long as
it is sent via IEC104, regardless of the use of this
link)
LNK_1703_SDFR
Link for Data Flow Routing (to specify data flow of
the signal). Only required in specific cases where
Intern © Siemens AG 2019 All rights reserved. new addresses are required or when information
should be re-routed.
SICAM TBII Workshop
Process Technique – Internal signal addressing (based on IEC104)
Double
click
via TCP/IP:
PC
LAN
RJ45
X2
RJ45 LAN/WAN
(1)
AU
Individual
Acknowledge diagnostic CPU Diagnostic
(4) Diagnostics
Select all
With any web browser navigate to the web page of the A8000, as shown. Then,
type the user and password:
By clicking on
one line
additional
information is
made available in
a yellow window
to the right
Select „Diagnosis“…………………. and „Security logbook“ to see the security log (e.g. events
related to cyber-security)
COM Port
SUB-D Standard RJ-45 X2
PIN Color Pin
1 n.b.
2 red 4
3 green 5
4 n.b.
5 yellow 6
6 n.b.
7 n.b.
8 n.b.
9 n.b.
(1)
(3) User-
Password
(2)Double-click
From To From PE To PE
Reset Filter
Define Filter Communication Communication
all AU all AU all selected all selected
selection selection
Define
individually
LNK_ProcessMsg
1) Types Overview
4) Via „drag-and-drop- fill it with the „Process data message“ parameters available in
the Type overview Parameter tab. Then, save:
5) In the Type overview menu open the Signal Type you want to
expand with the new link:
7) Now that the new link is available in the images, you can edit the parameters there:
8) The signal address (CASDU1, CASDU2, IOA1, IOA2, IOA3) and Type (TI) could be taken
from the LNK_ADR. A reference can be done for that by using the reference-formula mode
(drag-and-drop):
Aim of the new type is: to receive signals via MODBUS RTU
Workflow:
Entries in the first row can be easily duplicated in the other rows by use of the Fill in menu:
(1)
(8)
(10
) (dr
a
dro g-and
p) -
(9)
(11) (12)
(dra
g
dro -and-
p)
(1 2
)(
dr
dr ag-a
op nd
) -
Now, please create an image for a binary input from the CP-8050, as shown in the figure
below
Bay1
Urs
Bdr=19200
8N1
Control
Center
.0
Q8
IP Add=172.16.0.x
P3
DN
IP Add=172.16.0.31
DNP add=100
BUS
MO D / I P A8000
MODBUS TC P
DEVICE
Q0 MODBUS
Slave Add=31 DNP add=x