Sie sind auf Seite 1von 26

Load Frequency Control of

Two Area System


By
Dr. Aurobinda Bag
Sr. Asst. Prof., Dept. of EEE
Load Frequency Control (Two Area System)
• A large power system can be divided into a number of load frequency
control (LFC) areas, which are interconnected by tie lines.
• Such an operation is called a pool operation.
• A power pool is an interconnection of the power systems of individual
utilities.
• Each power system operates independently within its own jurisdiction,
but there are contractual agreements regarding internal system exchanges
of power through the tie lines with keeping system frequency constant.
• There are also agreements relating to operational procedures to be
followed in the event of major faults or emergencies.
05/02/2020 2
Load Frequency Control (Two Area System)
• For analyzing the dynamics of the LFC of an n-area power system, primarily
considering two-area systems.
• Two control areas 1 and 2 are connected by a single tie line as shown in Figure
below.

Fig.1
• Here, the control objective is to regulate the frequency of each area and to
simultaneously regulate the power flow through the tie line.
05/02/2020 3
Load Frequency Control (Two Area System)
• For the sake of convenience, each control area can be represented by an equivalent turbine,
generator, and governor system.
• In the case of a single control area, the incremental power (ΔPG−ΔPD) was considered by the
rate of increase of stored KE and increase in area load caused by the increase in frequency.
• In a two-area case, the tie-line power must be accounted for the incremental power balance
equation of each area, since there is power flow in or out of the area through the tie line.

• Power flow out of Control area-1 can be expressed as (1)

• where
 ∣E1∣ and ∣E2∣ are voltage magnitudes of Area-1 and Area-2, respectively,
 δ1 and δ2 are the power angles of equivalent machines of their respective areas,
 and XTL is the tie-line reactance.
05/02/2020 4
Load Frequency Control (Two Area System)
• If there is change in load demands in two areas, there will be
incremental changes in power angles (Δδ1 and Δδ2).
• Then, the change in the tie-line power is

05/02/2020 5
Load Frequency Control (Two Area System)
• Therefore, change in incremental tie-line power can be expressed as
(2)
(3)

Where, (4)
T12 is known as the synchronizing coefficient or the stiffness coefficient of the
tie-line.
• Equation (4) can be written as (5)
• where Static transmission capacity of the tie line.
05/02/2020 6
Load Frequency Control (Two Area System)
• Considering the change in frequency as

• Also,

05/02/2020
(6) 7
Load Frequency Control (Two Area System)
• Hence, the changes in power angles for Areas-1 and 2 are

(7)
(8)

• Since the incremental power angles are related in terms of integrals of incremental
frequencies, Equation (3) can be modified as
(9)

• Δf1 and Δf2 are the incremental frequency changes of Areas-1 and 2, respectively.

05/02/2020 8
Load Frequency Control (Two Area System)
• Similarly, the incremental tie-line power out of Area-2 is
(10)

• Where (11)

• Dividing Equation (11) by Equation (4), we get

• Therefore, T21 = a12T12 and hence ΔPTL2 = -a12ΔPTL1 (12)

05/02/2020 9
Load Frequency Control (Two Area System)
• For single control area, surplus power in p.u. is

• For a two-area case, the surplus power can be expressed in p.u. as

(13)
• Taking Laplace transform on both sides of Equation (13), we get

(14)
05/02/2020 10
Load Frequency Control (Two Area System)
• Rearranging the equation (14) as follows, we get

(15)

• where
05/02/2020 11
Load Frequency Control (Two Area System)
• By comparing Equation (15) with single-area equation, the only
additional term is the appearance of signal ΔPTL1 (S).
• Equation (15), can be represented in a block diagram model as shown
in Fig. below.

Fig.2, Block diagram representation of Equation (15) (for Control area-1)

05/02/2020 12
Load Frequency Control (Two Area System)
• Taking Laplace transformation on both sides of Equation (9), we get

(16)

• For Control area-2, we have

(17)
05/02/2020 13
Load Frequency Control (Two Area System)

The block diagram representation of Equations (16) and (17) is shown


in Fig. below.

Fig.3, Block diagram representation of Equations (16) and (17)

05/02/2020 14
COMPOSITE BLOCK DIAGRAM OF A TWO-AREA CASE

By the combination of
basic block diagrams
of Control area-1 and
Control area-2 and
with the use of Figs.2
and 3, the composite
block diagram of a
two-area system can
be modeled as shown
in Fig.4.

05/02/2020 15
FIG. 4 Block diagram representation of a two-area system with an LFC
STEADY-STATE RESPONSE OF TWO-AREA SYSTEM
(UNCONTROLLED CASE)
• For an uncontrolled case, ΔPc1 = ΔPc2 = 0, i.e., the speed-changer
positions are fixed.
Steady state Analysis:
• Here, the changes in the frequency and tie-line power under steady-
state conditions followed by sudden step changes in the loads in the
two areas, are determined.
• Let ΔPD1, ΔPD2 be sudden (incremental) step changes in the loads of
Control area-1 and Control area-2, simultaneously.
• ΔPG1, ΔPG2 are the incremental changes in the generation in Area-1
and Area-2 as a result of the load changes.
05/02/2020 16
STEADY-STATE RESPONSE OF TWO-AREA SYSTEM
(UNCONTROLLED CASE)
• Δf is the steady state change in frequency, and will be the same for both the
areas.
• ΔPTL1 is the steady state change in the tie-line power transmitted from
Area-1 to Area-2.
• In order to determine the steady state change,
• the incremental changes in generation can be determined as follows
(1)

(2)
05/02/2020 17
STEADY-STATE RESPONSE OF TWO-AREA SYSTEM
(UNCONTROLLED CASE)
• For the two areas, the dynamics are described by:
(3)

(4)
• Under steady-state conditions, we have (5)

• Putting the value of Equations (1), (2) and (5) in Equations (3) and (4),
we get
(6)
05/02/2020 18
STEADY-STATE RESPONSE OF TWO-AREA SYSTEM
(UNCONTROLLED CASE)
• And (7)

• As ΔPTL2 = −a12ΔPTL1 and Δf1 = Δf2 = Δf

• From Equation (6), we have


(8)

05/02/2020 19
STEADY-STATE RESPONSE OF TWO-AREA SYSTEM
(UNCONTROLLED CASE)
• Substituting ΔPTL1 from Equation (8) in Equation (7), we get

PD 2  a12 PD1


f  
1 1
( B2  )  a12 ( B1  ) (9)
05/02/2020 R2 R1 20
STEADY-STATE RESPONSE OF TWO-AREA SYSTEM
(UNCONTROLLED CASE)

• Substituting Δf from Equation (9) in Equation (8), we get


 
 
1 
PTL1     B1  
 PD 2  a12 PD1  
  PD1
 R1   B  1   a  B  1 
  2 R2  12  1 R1  

 1  1   1   1 
 B1   PD 2   B2   PD1  a12   B1  PD1  a12   B1  PD1
R1  R2   R1   R1
  
 1   1
 B2    a12  B1  
 R2   R1 

(10)

05/02/2020 21
STEADY-STATE RESPONSE OF TWO-AREA SYSTEM
(UNCONTROLLED CASE)
• Equations (9) and (10) are modified as

PD1  a12 PD 2


• Tie-line frequency, f  (11)
 2  a12 1

• Tie-line power, (12)

 1 
• where  2   B2  
 R2 

05/02/2020 22
STEADY-STATE RESPONSE OF TWO-AREA SYSTEM
(UNCONTROLLED CASE)
• Equations (11) and (12) give the values of the steady state changes in
frequency and tie-line power, respectively, as a result of sudden step-
load changes in the two areas.
Analysis:
• It can be observed that the frequency and tie-line power deviations do
not reduce to zero in an uncontrolled case.
• Consider two identical areas, B1 = B2 = B, β1 = β2 = β, R1 = R2 = R and
a12 = +1 P  PD 2
f   D1
• Hence, from Equations (11) and (12), we have 2 (13)

•05/02/2020
and (14)23
STEADY-STATE RESPONSE OF TWO-AREA SYSTEM
(UNCONTROLLED CASE)
• If a sudden load change occurs only in Area-2 (i.e.,ΔPD1 = 0), then we
have

• And (15)

(16)

05/02/2020 24
STEADY-STATE RESPONSE OF TWO-AREA SYSTEM
(UNCONTROLLED CASE)
• Equations (15) and (16) illustrate the advantages of pool operation as
follows:
• Equations (11) represents the change in frequency according to the change in
load in either of a two-area system interconnected by a tie line.
• When considering that those two areas are identical, Equation (11) becomes
Equation (13).
Hence, it is concluded that if a load disturbance occurs in only one of the areas
(i.e., ΔPD1 = 0 or ΔPD2 = 0), the change in frequency (Δ f) is only half of the
steady-state error, which would have occurred with no interconnection (i.e., an
isolated case).

05/02/2020 25
STEADY-STATE RESPONSE OF TWO-AREA SYSTEM
(UNCONTROLLED CASE)

Thus, with several systems interconnected, the steady-state frequency error


would be reduced.
Half of the (∆PD2)added load (in Area-2) is supplied by Area-1 through the tie
line.

05/02/2020 26

Das könnte Ihnen auch gefallen