Go to FILE - Show and explain NEW PROJECTS and show SET DEFAULTS
Show PROTECTOSEAL.COM
Show EMAIL US
Choose ANNEX A
Do examples of the following;
7.00
QUASI Design Pressure for the "Normal" Relief Vents 6.30 in.wc
6.30
at 90% of the emergcency vent set point = 6.3 in.w.c. pressure,
(< 1.0 scfh leakage through the ERV at pressures below this point. Use this "calculated design pressure" when sizing
the "Normal" P/V vent to achieve the Normal requirement by no more than 90% of the ERV setting.
6.00
5.00
90% of Normal Vent Set Point
4.95
(> 1.0 scfh leakage through Normal
4.00
3.00
2.00
1.00
0.00
5,000 10,000 12,682 17,433 20,000 30,000 40,000 600,000 650,000 700,000 742,155 750,000
Flow of Air in scfh
(1.00)
VACUUM (IN.W.C.)
(1.727)
NORMALVENT'S ACCUMULATED OVERVACUUM (-1.727 in.w.c.) ,
at which point the tank's vacuum requirement of 12,862 scfh is satisfied
(3.00)