Beruflich Dokumente
Kultur Dokumente
• Objectives:-
• To know about
• Transmission Systems
• Distribution system:
• Substations:
• Faults:
• Power Factor:
• Various types of Tariffs
1
Transmission Systems
• You will learn:
• layout of transmission system
• comparison between different type of transmission system
• Construction features of transmission lines:
• Mechanical features of transmission lines:
• Electrical features of line
• HVDC transmission lines
Concept of Energy Transmission
3
A transmission system includes all land, conversion structures and
equipment at a primary source of supply; lines, switching and
conversion stations between a generating or receiving point and
the entrance to a distribution centre or wholesale point, all lines
and equipment whose primary purpose is to augment, integrate or
tie together sources of power supply.
Main Parts of Power System
Four Main Parts:
Generation System
Transmission System
Distribution System
Consumer (LOAD)
5
Simplified Diagram of Power System
6
Generating Station
The commonly used power plants are:
7
Generation
9
Transmission
Basic Features
11
Distribution
15
Load
24
Purpose of Transmission
• To transmit power from a power
site to a market.
• For bulk supply of power to
load centres from outlying
steam stations.
• For interconnection purposes,
that is, for transfer of energy
from one system to another in
case of emergency or in
response to diversity in system
peaks.
Choice of Frequency
• As a general-purpose distribution
frequency 60 cycles has an But frequency less than 60 cycles
economic advantage over 50 might be interesting because as
cycles in that it permits a the frequency is decreased the
maximum speed of 3600 rpm inductive reactance of the line,
as against 3000 rpm. 2πfL, decreases and the
• Where a large number of capacitive reactance, 1/ 2πfC
distribution transformers are increases, resulting in higher load
used a considerable economic limits, transmission efficiency,
gain is obtained in that the and better regulation.
saving in materials of 60-cycle
transformers over 50-cycle
transformers may amount to 10
to 15 percent.
Effect of Voltage on Transmission Efficiency
Choice of Voltage
The power capability of a • The cost of transformers,
transmission line is switches, and circuit breakers
proportional to the square of increases rapidly with increasing
the voltage on the line. voltage in the upper ranges of
Therefore, very high voltage transmission voltages.
levels are used to transmit • As the voltage increases leakage
power over long distances. current over insulators and the
escape of energy through the
air between the conductors
(corona discharge) increases.
Choice of Voltage
In addition to these two losses, the charging current, which
increases as the transmission voltage goes higher, may either
increase or decrease the current in the circuit depending upon
the power-factor of the load current and the relative amount of
the leading and lagging components of the current in the
circuit.
Choice of working voltage for transmission
• Quantum of power to be
Selection evacuated
Criterion • Length of line
of • Voltage regulation
Economi
• Power loss in Transmission
c Voltage
• Initial and operating cost
32
Economic Voltage of Transmission of Power
* 33
Typical Transmission Voltage Levels
The no. of circuits and the land requirement for transmission decreases
with the use of higher transmission voltages.
ADVANTAGES OF EHV TRANSMISSION
The no. of circuits & the land requirement reduces as transmission voltage
increases.
The total line cost per MW per km decreases considerably with the increase in
line voltage.
DISADVANTAGES OF EHV TRANSMISSION
Line supports
Erection difficulties
Insulation needs
The EHV lines generates electrostatic effects which are harmful to human
beings & animals.
DC transmission system
• Only active power
• Current flows in one direction
• Conductor cross-sections fully used
• Low transmission losses
• Requires DC-AC converters to control the voltage level
• Expensive
• Switching of higher voltage DC more difficult
COMPARISION OF HVAC & HVDC SYSTEMS
STABILITY PROBLEMS,
• CONTROLLED POWER
• ASYNCHRONOUS OPERATION POSSIBLE BETWEEN REGIONS
HAVING DIFFERENT ELECTRICAL PARAMETERS
• NO RESTRICTION ON LINE LENGTH AS NO REACTANCE IN
DC LINES
Frequency control
• Direct-Current (HVDC) Transmission Lines
COST: AC vs DC Transmission
Line Cost AC
Line Cost DC
Terminal Cost DC
Terminal Cost AC
Earth wire
Insulator
Wave trap and other
hardware(cross arm and
Clamp, Spacer,
Vibration dampers,
connectors etc.
72
The line supports are poles and the chief requirements for
such supports are :
a. Wooden poles .
b. Steel tubular poles
c. Reinforced concrete poles .
d. Steel towers .
Steel Towers
• Lines of 66 KV are supported on towers.
• They fabricated from painted or galvanized angle section which are transported separately
and erection done on site.
• Long life and high degree of reliability
• They can withstand severe weather conditions.
• The height of the towers depend on operating voltage and span length.
• The leg of the tower are set on concrete foundation
Transmission line (Steel tower)
Types of steel towers
1. Tangent towers
• They are used for straight runs.
• Stress is due to weight of line, wind and ice load.
• Extra forces due to break in the line on one side.
• Base is either square or rectangle.
• Suspension type insulators used.
2. Deviation tower
• They are used where transmission line changes
direction.
• They have broader base , stronger members and are
costlier
• Strain insulators are used.
They are classified
i. Small angle towers(2o-15ochange in direction)
ii. Medium angle towers(15o-30ochange in direction)
iii. Large angle towers(30o-60ochange in direction)
Transmission line (Steel tower)
Types of Towers
Type A Tower (Tangent Tower • Used on straight runs and up to 2° line diversion
with suspension string)
Type B Tower (Small Angle • Used for line deviation from 2° to 15°
Tower with tension string)
Type C Tower (Medium Angle • Used for line deviation from 15° to 30°.
Tower with tension string ).
Type D Tower (Large angle • Used for line deviation from 30° to 60°
tower with tension string)
Type E Tower (Dead End • Used for line termination & starting
Tower with tension string)
85
Suspension Tower Transposition Tower Tension Tower
Different Types of Towers
87
Selection of Tower Structure
88
EHV- Tower
• Each conductor is
Conductor: stranded, steel reinforced
aluminum cable.
• Steel-reinforced concrete
Foundation and foundation and grounding
grounding: electrodes placed in the
ground
Tower height
Base width
90
Height of Tower Structure
H h1 h 2 h3 h 4
h1=Minimum permissible ground
clearance
h2=Maximum sag
91
Determination of Base Width
The base width(at the concrete level) is the distance between the centre of
gravity at one corner leg and the centre of gravity of the adjacent corner leg.
A particular base width which gives the minimum total cost of the tower and
foundations
Ryle
Formula
The ratio of base width to total tower height for most towers is generally
about one-fifth to one-tenth.
92
92
Transmission Line
Span Supporting
Tower Tension Tower
Tension Tower
Insulator
Sag
Sag in Overhead Lines
The difference in level between points of
supports and the lowest point on the
conductor is called sag.
Fig. 8.23. (i) shows a conductor suspended between two equilevel supports A and B. The
conductor is not fully stretched but is allowed to have a dip. The lowest point on the conductor is
O and the sag is S. The following points may be noted :
(i) When the conductor is suspended between two supports at the same level, it takes the shape of
catenary. However, if the sag is very small compared with the span, then sag-span curve is like a
parabola.
(ii) The tension at any point on the conductor acts tangentially. Thus tension To
at the lowest point O acts horizontally as shown in Fig. 8.23. (ii).
(iii) The horizontal component of tension is constant throughout the length of the wire.
(iv) The tension at supports is approximately equal to the horizontal tension acting at any point on the
wire. Thus if T is the tension at the support B, then T= To
Conductor sag and tension.
This is an important consideration in the mechanical design of overhead lines. The
conductor sag should be kept to a minimum in order to reduce the conductor material
required and to avoid extra pole height for sufficient clearance above ground level. It is
also desirable that tension in the conductor should be low to avoid the mechanical failure
of conductor and to permit the use of less strong supports. However, low conductor
tension and minimum sag are not possible. It is because low sag means a tight wire and
high tension, whereas a low tension means a loose wire and increased sag. Therefore, in
actual practice, a compromise is made between the two.
Calculation of Sag
(i) When supports are at equal levels.
Consider a conductor between two equilevel supports
A and B with O as the lowest point as shown in Fig.
8.24. It can be proved that lowest point will be at
the mid-span.
Calculation of Sag
Calculation of Sag
(ii) When supports are at unequal levels.
Ground Clearances
CL 5.182 0.305 * K
Where- V 33
K
33
1. ≤33 KV 5.20
2. 66 KV 5.49
3. 132KV 6.10
4. 220 KV 7.01
5. 400 KV 8.84
104
Clearance for Power Line Crossings
105
Power line Crossing another Power line
106
Spacing between the conductors
• The most suitable spacing between the
conductors can be arrived at by
mathematical calculations.
V
Spacing= S
150
Where,
S=sag in meters
V=voltage in KV
Clearances b/w Conductors
SYSTEM TYPE OF Vertical spacing b/w Horizontal spacing b/w
VOLTAGE TOWER conductors(mm) conductors(mm)
SINGLE
CIRCUIT 1080 4500
66 kV
DOUBLE
CIRCUIT 2060 5550
SINGLE
CIRCUIT 4200 7140
132 KV DOUBLE
CIRCUIT 3965 7320
109
Types of Conductors
110
Choice of conductors
An overhead transmission line usually consists of three conductors or
bundles of conductors containing the three phases of the power system.
The conductors are usually aluminum conductor steel reinforced
(ACSR), which are steel core (for strength) and aluminum wires (having
low resistance) wrapped around the core.
In overhead transmission lines, the
conductors are suspended from a pole
or a tower via insulators.
Table: Technical Data of ASCR Conductors Commonly used in EHV Transmission By Wapda.
Code Stranding Weight Per Km Weight Diameter Cross Area of Rated D.C
Words Aluminum Steel Aluminum Steel Complete Complete Steel Area of Complete Ultimate Resistance at 200
Conductor Core Conductor Conductor Core Aluminum Conductor Strength
ohm/km
No/mm No/mm kg/km kg/km kg/km mm mm mm2 mm2 kg
Gopher 6/2.36 1/2.36 72 34.1 106 7.08 2.36 26.25 30.62 980 1.093
Rabbit 6/3.35 1/3.35 145.1 68.8 214 10.05 3.35 52.88 61.69 1875 0.543
Dog 6/4.72 7/1.57 288.1 106.2 394 14.15 4.71 104.98 118.53 3225 0.273
Hare 6/4.72 1/4.72 288.1 136.5 425 14.16 4.72 105 122.5 3225 0.273
Osprey 16/4.465 ¼.465 777 121.8 898.8 22.23 4.465 281.9 297.56 6220 0.123
Cuckoo 24/4.62 7/3.08 1116 407.6 15424 27.72 9.24 402.33 454.48 12385 0.072
Zebra 54/3.18 7/3.18 1182 439 1621 28.62 3.18 428.9 484.59 13000 0.0686
Moose 54/3.53 7/3.53 1463 535 1998 31.77 3.53 528.5 597.0 16224 0.0559
Panther 30/3 7/3 588 387 976 21 3 212.1 261.5 9150 0.07311
• Mechanical Requirement
• Electrical Requirement
• Tensile Strength(For
Mechanical Tension)
Requiremen
• Strain Strength(For
t
Vibration)
114
• Continuous current rating.
• Short time current carrying rating.
Electrical • Voltage drop
Requiremen • Power loss
t • Minimum dia to avoid corona
• Length of line
• Charging current
115
Continuous Current Rating.
116
INSULATOR
Insulator material-
• High grade Electrical Porcelain
• Toughened Glass
• Fiber Glass
Iron Cap
Locking Key
Ball Socket
Insulator's Head
Compression
Expansion Layer Loading
Insulating Glass
or Porcelain
Skirt
69 kV 4–6
115 kV 7–9
138 kV 8–10
230 kV 12
345 kV 18
500 kV 24
765 kV 30–35
ADVANTAGES
DISADVANTAGES
• Spacing between conductor is increased
• Height of tower increases
• Cost is high.
Fig.) Suspension Insulator
STRAIN INSULATOR
When there is a dead end of the line or there is corner or sharp curve,
the line is subjected to greater tension.
In order to relieve the line of excessive tension, strain insulators are used.
For low voltage lines (< 11 kV), shackle insulators are used as strain
insulators.
However, for high voltage transmission lines, strain insulator consists of
an assembly of suspension insulators as shown in Figure.
The discs of strain insulators are used in the vertical plane.
When the tension in lines is exceedingly high, at long river spans, two or
more strings are used in parallel.
Fig.) Strain Insulator
SHACKLE INSULATOR
Shackle type insulators, similar to strain type insulators, are used on sharp curves,
end poles and in section poles.
However, unlike strain insulators, shackle insulators are designed to support lower
voltages.
These insulators are single, round porcelain parts that are mounted horizontally or
vertically.
They can be directly fixed to the pole with a bolt or to the cross arm.
Fig.) Shackle Insulator
V-Strings
A single string of insulator follows the
conductor and sways like a pendulum in a
strong side wind.
V-strings are used to prevent conductor
movement at towers. They are used for high
voltage transmission system.
In large transmission
lines, these wires are
located above the phase
conductors, shielding
them from lightning.
Earth Wire
Design criterion:
• Shield angle
• 25°-30° up to 220 KV
• 20° for 400 KV and above
138
Tower Grounding
139
Method of Tower Grounding
140
141
• Internal inductance is independent of size or radius of
the conductor.
• Since the flux density is gradually increasing from centre
of conductor towards surface of conductor, so Lint exists
in case of ACSR or solid conductor.
For single phase line
Inductance of a transmission line
A two-conductor A four-conductor
bundle bundle
• Without transposition, the middle conductor will suffer maximum flux
linkage, so current flowing through this conductor is reduced to
outside conductor, hence the system becomes unbalance.
• For making the system to be balanced, the position of R, Y & B
conductors are changed at regular intervals of distance. This is called
transposition.
Advantage-
System becomes balance and symmetric
The interference to the surrounding communication line is reduced.
The corona effect is reduced.
The effect of capacitance and inductance in all the conductors
becomes uniform which causes uniform power flow and voltage level
in all the conductors.
The effect of ground or earth capacitance on conductors is reduced.
Capacitance of a single phase two-wire
transmission line
Thus:
cab (9.29.1)
D
ln
r
Which is the capacitance per unit length of a single-phase two-wire
transmission line.
The potential difference between each conductor and the ground (or neutral)
is one half of the potential difference between the two conductors.
Therefore, the capacitance to ground of this single-phase transmission line
will be
2
cn can cbn (9.29.2)
D
ln
r
Capacitance of a single phase two-wire
transmission line
Similarly, the expressions for capacitance of three-phase lines (and for lines with
more than 3 phases) can be derived. Similarly to the inductance, the capacitance
of the transmission line can be found from tables supplied by line developers.
Analysis shows that:
1. The greater the spacing between the phases of a transmission line, the lower
the capacitance of the line. Since the phases of a high-voltage overhead
transmission line must be spaced further apart to ensure proper insulation, a
high-voltage line will have a lower capacitance than a low-voltage line. Since
the spacing between lines in buried cables is very small, shunt capacitance of
cables is much larger than the capacitance of overhead lines. Cable lines are
normally used for short transmission lines (to min capacitance) in urban areas.
2. The greater the radius of the conductors in a transmission line, the higher the
capacitance of the line. Therefore, bundling increases the capacitance. Good
transmission line is a compromise among the requirements for low series
inductance, low shunt capacitance, and a large enough separation to provide
insulation between the phases.
Shunt capacitive admittance
The shunt capacitive admittance of a transmission line depends on both the
capacitance of the line and the frequency of the power system. Denoting the
capacitance per unit length as c, the shunt admittance per unit length will be
yC j c j 2 fc (9.31.1)
YC yC d j 2 fcd (9.31.2)
where d is the length of the line. The corresponding capacitive reactance is the
reciprocal to the admittance:
1 1
ZC j (9.31.3)
YC 2 fcd
Example
Example : An 8000 V, 60 Hz, single-phase, transmission line consists of two hard-
drawn aluminum conductors with a radius of 2 cm spaced 1.2 m apart. If the
transmission line is 30 km long and the temperature of the conductors is 200C,
a. What is the series resistance per kilometer of this line?
b. What is the series inductance per kilometer of this line?
c. What is the shunt capacitance per kilometer of this line?
d. What is the total series reactance of this line?
e. What is the total shunt admittance of this line?
1 1
Z sh 5
j13.0k
Ysh j 7.684 10
Transmission line models
Unlike the electric machines studied so far, transmission lines are characterized by
their distributed parameters: distributed resistance, inductance, and capacitance.
The distributed series and shunt elements of the transmission line make it harder
to model. Such parameters may be approximated by many small discrete
resistors, capacitors, and inductors.
However, this approach is not very practical, since it would require to solve for
voltages and currents at all nodes along the line. We could also solve the exact
differential equations for a line but this is also not very practical for large power
systems with many lines.
Transmission line models
Fortunately, certain simplifications can be used…
Overhead transmission lines shorter than 80 km (50 miles) can be modeled as a
series resistance and inductance, since the shunt capacitance can be neglected
over short distances.
The inductive reactance at 60 Hz for – overhead
lines – is typically much larger than the resistance
of the line.
Lines longer than 240 km (150 miles) are long transmission lines and are to be
discussed later.
Transmission line models
The total series resistance, series reactance, and shunt admittance of a
transmission line can be calculated as
R rd (9.37.1)
X xd (9.37.2)
Y yd (9.37.3)
where r, x, and y are resistance, reactance, and shunt admittance per unit length
and d is the length of the transmission line. The values of r, x, and y can be
computed from the line geometry or found in the reference tables for the specific
transmission line.
Short transmission line: phasor diagram
AC voltages are usually expressed as phasors.
Assuming that the generator is ideal, an increase of load will increase a real and
(or) reactive power drawn from the generator and, therefore, the line current, while
the voltage and the current will be unchanged.
1) If more load is added with the same lagging power factor, the magnitude of the
line current increases but the current remains at the same angle with respect to
VR as before.
Transmission line characteristics
The voltage drop across the reactance increases but stays at the same angle.
Assuming zero line resistance and remembering that
the source voltage has a constant magnitude:
VS VR jX L I (9.41.1)
Therefore, when a lagging load increases, the received voltage decreases sharply.
In a summary:
1. If lagging (inductive) loads are added at the end of a line, the voltage at the end
of the transmission line decreases significantly – large positive VR.
2. If unity-PF (resistive) loads are added at the end of a line, the voltage at the end
of the transmission line decreases slightly – small positive VR.
3. If leading (capacitive) loads are added at the end of a line, the voltage at the end
of the transmission line increases – negative VR.
The voltage regulation of a transmission line is
Vnl V fl
VR 100% (9.42.1)
V fl
where Vnl and Vfl are the no-load and full-load voltages at the line output.
Transmission line characteristics
2. Power flow in a transmission line
The real power input to a 3-phase transmission line can be computed as
where VS is the magnitude of the source (input) line-to-neutral voltage and VLL,S is
the magnitude of the source (input) line-to-line voltage. Note that Y-connection is
assumed! Similarly, the real output power from the transmission line is
3VSVR
Pmax (9.46.1)
XL
This maximum power is called the steady-state stability limit of the transmission line.
The real transmission lines have non-zero resistance and, therefore, overheat long
before this point. Full-load angles of 250 are more typical for real transmission lines.
Few interesting observations can be made from the power expressions:
1. The maximum power handling capability of a transmission line is a function of the
square of its voltage. For instance, if all other parameters are equal, a 220 kV
line will have 4 times the power handling capability of a 110 kV transmission line.
Therefore, it is beneficial to increase the voltage… However, very high voltages
produce very strong EM fields (interferences) and may produce a corona – glowing of
ionized air that substantially increases losses.
Transmission line characteristics
2. The maximum power handling capability of a transmission line is inversely
proportional to its series reactance, which may be a serious problem for long
transmission lines. Some very long lines include series capacitors to reduce the total
series reactance and thus increase the total power handling capability of the line.
3. In a normal operation of a power system, the magnitudes of voltages VS and VR do
not change much, therefore, the angle basically controls the power flowing through
the line. It is possible to control power flow by placing a phase-shifting transformer at
one end of the line and varying voltage phase.
Pout
100% (9.47.1)
Pin
Transmission line characteristics
4. Transmission line ratings
One of the main limiting factors in transmission line operation is its resistive heating.
Since this heating is a function of the square of the current flowing through the line
and does not depend on its phase angle, transmission lines are typically rated at a
nominal voltage and apparent power.
Ploss 3I L2 R (9.48.1)
The greater the current flow, the greater the resistive heating losses.
Transmission line characteristics
2. The voltage drop in a practical line should be limited to approximately 5%. In other
words, the ratio of the magnitude of the receiving end voltage to the magnitude of the
sending end voltage should be
VR
0.95 (9.49.1)
VS
This limit prevents excessive voltage variations in a power system.
3. The angle in a transmission line should typically be 300 ensuring that the power
flow in the transmission line is well below the static stability limit and, therefore, the
power system can handle transients.
Any of these limits can be more or less important in different circumstances. In short
lines, where series reactance X is relatively small, the resistive heating usually limits
the power that the line can supply. In longer lines operating at lagging power factors,
the voltage drop across the line is usually the limiting factor. In longer lines operating
at leading power factors, the maximum angle can be the limiting f actor.
Corona discharge
Corona discharge
• Corona Discharge Effect in the transmission lines is a phenomenon in
which ionization of the surrounding air of power conductors takes
place at voltages, greater than critical break down voltage.
• hissing noise, followed by the violet glow and the production of ozone
gas and finally electrical breakdown and flash over is observed, all
these constitutes the Corona Discharge Effect Phenomenon.
Corona Discharge Effect is affected by many
things such as
• Conductor Diameter
• number of conductors per phase
• phase spacing
• conductor surface condition
• Weather
• altitude
• temperature and line voltage
Important Terms
• Critical disruptive voltage.-It is the minimum phase-neutral voltage at
which corona occurs.
• Visual critical voltage. - It is the minimum phase-neutral voltage at
which corona glow appears all along the line conductors.
• Power loss due to corona- Formation of corona is always
accompanied by energy loss which is dissipated in the form of light,
heat, sound and chemical action. When disruptive voltage is
exceeded, the power loss due to corona is given by :
Effects of Corona Discharge
• Effect constitute power loss in the transmission lines popularly called
as corona loss
• production of ozone gas
• interference with the neighbouring Radio and Television
communication lines.
How Corona Discharge Effect Occur: