Beruflich Dokumente
Kultur Dokumente
3 www.dv-power.com
Three-phase transformer
4 www.dv-power.com
Single-phase vs. true three-phase
voltage
What the international standards say?
5 www.dv-power.com
Single-phase vs. true three-phase
voltage
Three-phase test advantages
• Three single phase sinusoidal voltages, shifted for
120°, applied to three transformer phases at the
same time
• Allows testing of any transformer, including special
transformers like phase-shifting, arc furnace, etc.
• Simulates real state of the transformer during the
test
6 www.dv-power.com
Single-phase vs. true three-phase
voltage
Recommendations:
• Transformers with standard vector groups (YNyn, Dyn, YNd,...)
– Phase by phase measurement with single-phase voltage
• Transformers with special vector group (phase shifting
transformers) – Three-phase test with true three-phase voltage
7 www.dv-power.com
2.
Test voltage value
Test voltage value
9 www.dv-power.com
Turns ratio deviation
10 www.dv-power.com
Turns ratio deviation
11 www.dv-power.com
Turns ratio deviation
12 www.dv-power.com
Turns ratio deviation
• Real transformer turns ratio – Un
applied at HV side
• Increasing the voltage > Un,
realative voltage drop I * X is
increasing
• Decreasing the voltage < Un, I * X
is decreasing and increasing back
later
• At low saturation the voltage drop I
* X is significantly increased Dr. Radenko Wolf, Testing the electric machines, I part,
Faculty of Electrical Engineering University of Zagreb, 1970.
13 www.dv-power.com
Turns ratio deviation
• Up to 5-10% Un – measurement
error due to relative voltage drop
I * X is less than 0,1%
• At 1% Un – measurement error
< 0,3%
• Below 1% Un – measurement
error suddenly increased
• The percentages vary depending
on transformer construction (B-H
curve)
Dr. Radenko Wolf, Testing the electric machines, I part,
Faculty of Electrical Engineering University of Zagreb, 1970.
14 www.dv-power.com
Case study
• 45 MVA
• 275/33 kV
• 94,3/787,3 A
• YNd1
15 www.dv-power.com
Case study
• Test voltage 100 V
Namplate Ratio Tap Test Turns Turns Turns Ratio Ratio Ratio Turns
HV/LV Position Voltage Ratio Ratio Ratio Deviation Deviation Deviation ratio
Phase A Phase B Phase C Phase A Phase B Phase C pass/fail
302500 / 33000 1 100 5,3117 5,3031 5,31 0,36 0,2 0,33 Pass
299062.5 / 33000 2 100 5,2519 5,2436 5,2502 0,38 0,22 0,34 Pass
295625 / 33000 3 100 5,1923 5,184 5,1905 0,39 0,23 0,36 Pass
292187.5 / 33000 4 100 5,1326 5,1247 5,1308 0,4 0,25 0,37 Pass
288750 / 33000 5 100 5,073 5,0654 5,0713 0,42 0,27 0,39 Pass
285312.5 / 33000 6 100 5,0135 5,0062 5,0118 0,44 0,29 0,4 Pass
281875 / 33000 7 100 4,954 4,9469 4,9522 0,46 0,31 0,42 Pass
278437.5 / 33000 8 100 4,8945 4,8876 4,8927 0,47 0,33 0,44 Pass
275000 / 33000 9 100 4,835 4,8283 4,8333 0,49 0,35 0,46 Pass
271562.5 / 33000 10 100 4,7755 4,7691 4,7737 0,51 0,38 0,48 Fail
268125 / 33000 11 100 4,716 4,7097 4,7142 0,53 0,4 0,5 Fail
264687.5 / 33000 12 100 4,6564 4,6504 4,6547 0,55 0,42 0,52 Fail
261250 / 33000 13 100 4,5969 4,5911 4,5952 0,57 0,45 0,54 Fail
257812.5 / 33000 14 100 4,5374 4,5317 4,5358 0,6 0,47 0,56 Fail
254375 / 33000 15 100 4,4779 4,4724 4,4763 0,62 0,49 0,58 Fail
250937.5 / 33000 16 100 4,4184 4,4132 4,4168 0,64 0,52 0,6 Fail
247500 / 33000 17 100 4,359 4,3539 4,3574 0,67 0,55 0,63 Fail
16 www.dv-power.com
Case study
• Test voltage 100 V
17 www.dv-power.com
Case study
• Test voltage 250 V
Namplate Ratio HV_LV Test Turns Turns Turns Ratio Ratio Ratio Turns
HV/LV Tap Voltage Ratio Ratio Ratio Deviation Deviation Deviation ratio
Position Phase A Phase B Phase C Phase A Phase B Phase C pass/fail
302500 / 33000 1 250 5.3044 5.2981 5.3043 0.23 0.11 0.22 Pass
299062.5 / 33000 2 250 5.2451 5.239 5.2451 0.25 0.13 0.25 Pass
295625 / 33000 3 250 5.1857 5.1798 5.1856 0.26 0.15 0.26 Pass
292187.5 / 33000 4 250 5.1262 5.1206 5.1262 0.28 0.17 0.28 Pass
288750 / 33000 5 250 5.0668 5.0613 5.0667 0.3 0.19 0.29 Pass
285312.5 / 33000 6 250 5.0074 5.0021 5.0073 0.32 0.21 0.31 Pass
281875 / 33000 7 250 4.9479 4.9428 4.9479 0.33 0.23 0.33 Pass
278437.5 / 33000 8 250 4.8886 4.8836 4.8884 0.35 0.25 0.35 Pass
275000 / 33000 9 250 4.8291 4.8243 4.829 0.37 0.27 0.37 Pass
271562.5 / 33000 10 250 4.7697 4.765 4.7695 0.39 0.29 0.39 Pass
268125 / 33000 11 250 4.7102 4.7057 4.71 0.41 0.31 0.41 Pass
264687.5 / 33000 12 250 4.6508 4.6464 4.6506 0.43 0.34 0.43 Pass
261250 / 33000 13 250 4.5914 4.5871 4.5912 0.45 0.36 0.45 Pass
257812.5 / 33000 14 250 4.532 4.5279 4.5317 0.48 0.38 0.47 Pass
254375 / 33000 15 250 4.4726 4.4685 4.4723 0.5 0.41 0.49 Pass
250937.5 / 33000 16 250 4.4131 4.4092 4.4129 0.52 0.43 0.51 Fail
247500 / 33000 17 250 4.3537 4.3499 4.3535 0.55 0.46 0.54 Fail
18 www.dv-power.com
Case study
• Test voltage 250 V
19 www.dv-power.com
Summary
• Higher test voltage - more accurate turns ratio results
• The test voltage should be higher than the values used
commonly used today (e.g. 100 V)
• Our preliminary advice is to use a higher test voltage (> 250 V,
< 1 kV), as it seems effective and safe
• Too high test voltage (tens of kV) can cause arc and conceal
short open circuits
• We are conducting further research to establish the optimum
voltage level for specific transformer types
• The study has been trigger for the development of a new
generation of portable turns ratio tester 500 V
20 www.dv-power.com
Thanks
Questions?
You can contact me at eddie@dv-power.com