Beruflich Dokumente
Kultur Dokumente
m
Scope
u Covers
u Unit auxiliary transformers ( UT-npc term.)
u Station service transformers( SUT-npc term.)
u Substation transformers ( Auxiliary trf- npc term.)
u This standard covers, in general, the conditions in
which there are no generator breakers or load-break
switches.
u GT not included in the scope of this standard.
u Dry type trf.- used for indoor purpose as no oil for burning.
The standard temperature rises are 80 °C, 115 °C, and 150 °C
above an ambient that averages 30 °C over a 24 h period, but
does not exceed 40 °C (most applications use 150 °C
temperature rise). Forced-air cooling may also be used to
obtain a higher rating.
u It may be used for one unit or two or more units, or there may
be more than one transformer per unit.
2.2 UAT
u Located outside Generating station Bldg. as these are oil filled.
Attention should be given to the flow of hot air so that the
cooling system of one transformer does not affect another
located nearby.
3.3 SST
u Taps (normally two 2.5% above and two 2.5% below rated
voltage) are usually specified in the HV winding to allow
adjustment of the voltage range after experience is obtained
with operation of the system. Taps may be specified below
the normal tap, above the normal tap, or divided between the
two.
u Bushings are provided with the transformer, but they have different
insulation ratings.