Why do we care?
Survey Accuracy?
LiDar / Conventional Survey Accuracy
Absolute Accuracy of +/- 6 inches Relative Accuracy of +/- 3 inches
What is the Accuracy of Thermal Studies? What is the Precision of Thermal studies? Is the study Reliable & Repeatable?
Conductor Calibration
Conductor Sag to a Calibration Temperature
Conductor Calibration
Example of how a 20 degree F Error in Calibration temperature could equate to 35-50 degree Error in thermal rating. Calibrating Temperature Thermal Rating Deg (F)
Difference +85
+90 +110 +130 +160
60
80 100 120 140
145
170 210 250 300
Error in Calibration temperature is not one to one with accuracy of thermal rating.
Predictive Methods
IEEE 738-2006 Calculations Infrared Thermography
Ambient Temperature
Wind Pressure
Wind Pressure
Wind Pressure
5.5 mph
Solar Absorption
Conclusion
Importance and Impact of Conductor Temperature Calibration
Direct Measurements increase Accuracy of transmission line rating studies; therefore, the results are:
more Reliable more Repeatable
Better Accuracy and Precision Will Result in Reducing Project Costs and Clearance Deficiency Risks
Conclusion
Recommendations Use as many methods as possible IEEE 738-2006 should not be only method used in conductor calibration Precision & Accuracy is Critical to Reliable and Repeatable Results Direct Measurement Methods Can Increase Precision & Accuracy, While Reducing Overall Project Costs and Reducing Risk of Clearance Violations
Line Rating: Its all about the Temperature! Ryan Bliss, P.E., S.E., M.ASCE
Questions?