Sie sind auf Seite 1von 44

HEAT LOAD CALCULATION 2

HEAT LOAD 2 1
home back next

TOPICS COVERED
LOAD CALCULATIONS
FORMS FORMULAS TABLES FACTORS AIR SIDE PSYCHROMETRY
2
home back next

HEAT LOAD 2

HEAT LOAD 2

HEAT LOAD FORM


SEE TRANSPARENCY

HEAT LOAD 2 4
home back next

HEAT LOAD ESTIMATE PROBLEM


   


HEAT LOAD 2

 

General office Ceiling 10 Wall 4 brick, plastered both side Window- ordinary single glass internal shade Door- plywood sandwich air space Occupants - 35 person Lighting - Fluorescent 5
home back next

DESIGN CONDITIONS


Outdoor design conditions 92F db / 80F wb or 95db/83wb Overestimating effect Night time temp. & rh different 76F db/ 75F wb / 95% rh

HEAT LOAD 2 6
home back next

DESIGN CONDITIONS


Indoor design conditions


Base on requirement and standards

75F db / 55% rh 72F db / 55% rh 71F db / 50% rh Peak time at 4.00 pm

HEAT LOAD 2 7
home back next

CURRENT AIR-CONDITIONING DESIGN DATA COMPARISON


JKR INDOOR TEMP.(o C) LIGHTING LOAD (w/ft2) OFFICE EQUIP. (w/ft2) OUTLET VELOCITY (ft/min.) FRESH AIR (cfm/person) 24 4-6 (2) 25-50* 20 ASHRAE 95 23-26 1.85-4.65 0.8-2 40-150 20 CIBSE 22+/-2 1.4 1.4 20

*-Carrier Handbook
HEAT LOAD 2 8

QUESTION
Fill in the table other information for the following conditions
Outdoor air 92db/80wb Indoor 75db/55%rh

HEAT LOAD 2 9
home back next

SOLAR GAIN THROUGH GLASS




Cooling Load = Window Area x Peak solar heat gain (Table 4) x Storage Factor (Table 5) x Shade Factor (Table 6) Refer to Table 4, Table 5 and Table 6
10
home back next

HEAT LOAD 2

SOLAR AND TRANSMISSION GAIN




Heat Gain Through Walls & Roofs = Area x Equivalent Temp. Difference (Table 7 for wall & Table 8 for roof) x Transmission Coefficient (U) (Table 9)

HEAT LOAD 2 11
home back next

TRANSMISSION GAIN (EXCEPT WALLS AND ROOFS)




Heat gain through all glass = Area x Temp. Difference (OA - RA) x Transmission coefficient (U) (Table 9) Heat gain through shade wall, partition = Area x Temp. Difference (OA - RA - 5F) x Transmission coefficient (U) (Table 9)

HEAT LOAD 2 12
home back next

TRANSMISSION GAIN (EXCEPT WALLS AND ROOFS) (2)




Heat gain through wall, partition (adjacent to Kitchen,Boiler Room) = Area x Temp. Difference (OA - RA + 15F to 25F) x Transmission coefficient (U) (Table 9)

HEAT LOAD 2 13
home back next

INFILTRATION
When ventilation exceeds infiltration (+ve pressure), then infiltration = 0 When rooms are design at -ve pressure, have to consider

 

HEAT LOAD 2 14
home back next

INTERNAL LOADS
People
No. of people from no. of chairs or base on per floor area Table 10 - Heat gain from people
 

No. of people x Table 10 Activity, Sensible & Latent

HEAT LOAD 2 15
home back next

INTERNAL LOADS
Power
Table 53 - Heat gain from electric motors Electric motors contribute only sensible heat to space

HEAT LOAD 2 16
home back next

INTERNAL LOADS
Lights - Estimate (w/ft2) Lights - Type
Incandescent
rated lamp watt x 3.413

 

Fluorescent lamp
rated lamp watt x 1.25 x 3.413

HEAT LOAD 2 17
home back next

INTERNAL LOADS
Appliances
most appliances contributes both sensible and latent heat load. They contribute latent heat by virtue of their function ex. drying, cooking Hood to remove this is most effective Table 50 & 51- Heat Gain from Restaurant
HEAT LOAD 2 18
home back next

SAFETY FACTOR
Safety factor added for possible error in the survey Over estimating safety factor will cause oversized air conditioning equipment - difficult to maintain space conditions < 5%
19
home back next


HEAT LOAD 2

ROOM SENSIBLE HEAT (RSH)


Now all the load components contributing to sensible load can be added

HEAT LOAD 2 20
home back next

SUPPLY AIR DUCT LOSSES


In transferring air from system cooling coil to space, four losses must be considered;

HEAT LOAD 2 21
home back next

Supply duct heat gain supply duct leakage loss fan heat bypassed outdoor air

SUPPLY DUCT HEAT GAIN


Supply air in the duct at 50F to 60F passes through surrounding environment above 90F - potential heat gain to supply air Insulation reduces this gain Typical figure < 2% of RSH

 

HEAT LOAD 2 22
home back next

SUPPLY DUCT LEAKGE LOSS


Lost capacity in the supply air duct depends on duct shape, duct pressure and workmanship. Low pressure (0 - 2s.p) : <5% Medium pressure (2 - 6s.p) : 2% 3% High pressure (6 & above) : <1%
23
home back next

 


HEAT LOAD 2

FAN HEAT
Draw through (draw through the cooling coil) fan add heat to air supply. Electrical losses for motor which lies in the air stream also add heat < 5%

HEAT LOAD 2 24
home back next

BYPASS OUTDOOR AIR


Some of the air passing through the coil remain untreated. Load equivalent to infiltration load Depends on bypass factors use Load = cfm x (toa-trm) x bf x 1.09

  

HEAT LOAD 2 25
home back next

EFFECTIVE ROOM SENSIBLE HEAT (ERSH)




This load determine the cfm required across the cooling coil ERSH = RSH + (SUPPLY DUCT GAIN + SUPPLY DUCT LEAK LOSS + FAN) + BYPASS OUTDOOR AIR

HEAT LOAD 2 26
home back next

LATENT LOAD
The latent counterpart of infiltration, internal loads, and supply duct load are also calculated to determine the Room Latent Heat and Effective Room Latent Heat Vapor Transmission - only for low or high dew point application.
27
home back next

HEAT LOAD 2

ROOM LATENT HEAT (RLH)


SUM OF ALL ROOM LATENT LOAD
INFILTRATION PEOPLE STEAM APPLIANCES ADDITIONAL HEAT GAINS VAPOUR TRANSMISSION
28
home back next

HEAT LOAD 2

EFFECTIVE ROOM LATENT LOAD (ERLH)




ROOM LATENT HEAT (RLH) + SUPPLY DUCT LEAKAGE LOSS + BYPASS OUTDOOR AIR

HEAT LOAD 2 29
home back next

OUTDOOR AIR / VENTILATION RATES





HEAT LOAD 2

Outdoor air/ventilation rates from Table 11-Ventilation Std. Outdoor air quantity can be determined either by cfm/person or cfm/ft2 or airchange rate (ach) Air change is defined as the quantity of changed air every hour cfm = vol x ach 60
30
home back next

OUTDOOR AIR HEAT


Outdoor air heat comprised of both sensible and latent load Except for bypassed air, the load appears on the upstream of the coil Requirements of outdoor/fresh air base on air change rate or cfm/sq.ft or per person
31
home back next

HEAT LOAD 2

QUESTION
Calculate the outdoor/fresh air requirement of the office space, if the recommended fresh air change is 2 ach. ach.
(ach/60) x Vol. = (2/60) x 32000 = 1067 cfm
HEAT LOAD 2 32
home back next

Answer :

RETURN DUCT LOSSES


Return duct are normally shorter than supply duct Temperature of air at about 75F 80F Return duct slightly negative 1% for Return duct heat gain & 1% for return duct leakage loss
33
home back next

  
HEAT LOAD 2

RETURN AIR or BLOW THRU FAN




Fan and motor heat appear on the upstream side of the coil. ..hp x 2545

HEAT LOAD 2 34
home back next

GRAND TOTAL HEAT


Total heat load the coil must remove from the air passing over it. Also known as dehumidifier load

HEAT LOAD 2 35
home back next

REFRIGERATION LOAD
Introducing two additional loads not experience by the coil
Piping sensible heat gain Pumping heat gain

HEAT LOAD 2 36
home back next

APPARATUS DEW POINT (ADP)




Effective Room Sensible Heat (ERSH) Effective Room Total Heat (ERTH)

 

ADP obtained from plot ESHF line or Table 65 Indicated ADP & Selected ADP ADP must be > 48F

HEAT LOAD 2 37
home back next

QUESTION
ERSH = 115 000 ERLH = 15 000 Calculate the ESHF Find ADP if room is 75F/55%rh 75 from table

   

HEAT LOAD 2 38
home back next

DEHUMIDIFIED AIR QUANTITY


Dehumidified rise = (trm-tadp)x(1-BF) Cfmda = ERSH 1.09 x (trm-tadp)x(1-BF)

HEAT LOAD 2 39
home back next

SUPPLY AIR QUANTITY (cfmsa)




Outlet temp. diff = RSH =Fdes.dif (trm - tgrille) 1.09 x cfmda Supply cfm = RSH = cfmsa 1.09 x Fdes. dif


HEAT LOAD 2

Bypass cfm = cfmsa - cfmda


40
home back next

RESULTING ENTERING AND LEAVING CONDITIONS AT APPARATUS  tedb= trm + cfmoa x (toa - trm) cfmsa


tldb = tadp + bf x (tedb - tadp) tewb & tlwb read from psych. chart


HEAT LOAD 2

41
home back next

SOME EX. OF COMPUTERISED HEAT LOAD CALCULATIONS




See Lotus files

HEAT LOAD 2 42
home back next

HEAT LOAD 2

43

GO TO PSYCHRO 2

HEAT LOAD 2 44
home back next

Das könnte Ihnen auch gefallen