Beruflich Dokumente
Kultur Dokumente
An ungrounded system does not have a grounded (neutral) conductor routed between the supply transformer and the service equipment because the supply transformer is not earth grounded.
Path of current in an ungrounded distribution system resulting from grounds on two different phases.
Two lamps should have identical wattage rating and voltage rating equal to line voltage.
Push button provides a way for comparing the normal and ground indications.
Fault on line B short-circuits lamp B, causing it to burn dimly or go out, depending on the severity of the ground. Lamp A burns more brightly.
Fault on line C short-circuits lamp C, causing it to burn dimly or go out, depending on the severity of the ground. Lamps A and B burn more brightly.
Wattage rating of the lamp determines the sensitivity of the detecting system. 25W best overall performance.
Without ground fault on the system, the secondary voltages are balanced and no voltage appears across the lamp. Ground fault on phase C, for example, will short primary coil Pc and the voltage on the secondary coil Sc will be zero. Voltage unbalance will cause the lamp to light.
Insulation resistance between conductor and ground is R ohms. With 120V applied, voltage b/w conductor and ground. If one conductor is grounded, voltage b/w the other conductor and ground will rise to 120V.
The opening of switches of vital auxiliaries should be avoided until standby equipment is placed in operation. If this operation fails, either the ground is in the generator, or more than one ground is present.