Presentation outline
Introduction of LP Bypass system Overview of LP Bypass System details and lay out Control scheme of LP bypass system
PMI Revision 00
LP bypass bypasses steam to IPT & LPT & maintain flow through RH. Function of LP bypass:1. To monitor the pressure in reheat system and to control it under certain operating condition. 2. The volume of steam not utilized by the IPT & LPT during start up & shut down must pass through condenser.
PMI Revision 00
LP BYPASS SYSTEM
LP Bypass system provide a very effective means of controlling reheat steam flow during
Startup Low-load / part load operation Sudden load rejection
PMI Revision 00
LP BYPASS SYSTEM
It enhances fast starting capability of turbines from all initial conditions e.g.
PMI Revision 00
LP BYPASS SYSTEM
LP steam-bypass system operates in parallel with the turbine
Protects Condenser from excessive temperature and pressure that could result from sudden injection of superheated steam
LP BYPASS SYSTEM
The controls for LP Bypass system are combination of electrical and well proven hydraulic system Electro-hydraulic converter provides the necessary link between hydraulic actuator and electrical system
PMI Revision 00
SEQUENCE OF EVENTS RESULTING FROM LOAD REJECTION Upon receiving load rejection signal from electrical system: Turbine Speed Controller assumes control of the TG set It initiates fast closure of HP & IP turbine control valves through position controller Fast closure of turbine control valves cause an immediate decrease in HP 1 st . Stage pressure
May 24, 2012 PMI Revision 00 8
SEQUENCE OF EVENTS RESULTING FROM LOAD REJECTION Pressure increases in main and reheat steam systems These pressure changes are sensed by HP and LP Bypass controllers Respective bypass valves are opened
PMI Revision 00
If LP steam- bypass system fails or the condenser cannot accept LP bypass steam , Safety Valves open and dump steam to atmosphere
PMI Revision 00
10
PMI Revision 00
11
PMI Revision 00
12
PMI Revision 00
13
PMI Revision 00
14
Control scheme
Set point formation Pressure control for LP bypass system LP bypass HYDRAULIC System Protection system
PMI Revision 00
15
Control scheme
The LPBypass Controller acts as a maximum pressure Controller It regulates the reheater pressure either to the fixed set value or suitably derived variable set value If the reheater pressure exceeds this set value, the Controller causes the electrohydraulic converter to operate and initiate bypass operation
PMI Revision 00
16
The Two set values fixed and variable are formed for the LPBypass control system set value to be used is determined by a maximum value selector For the formation of variable set point, a pressure transducer is used to measure the steam pressure in HP turbine
PMI Revision 00
17
PMI Revision 00
18
LP Bypass System
PMI Revision 00
19
20
LP BYPASS SETPOINTS
PMI Revision 00
21
The controller controls plunger coil of Electro Hydraulic Converter With increase in voltage, the jet pipe is deflected towards right Converter piston moves downwards leading to generation of LPB signal oil through Follow-up pistons provided in the hydraulic control system
May 24, 2012 PMI Revision 00 22
Two Follow-up Pistons actuate and open first stage of water injection valve Remaining two Follow-up Pistons generate signal oil for opening LPBypass stop and control valve
May 24, 2012 PMI Revision 00 23
PMI Revision 00
24
PMI Revision 00
25
Protection Devices
Low Vacuum Condensor Protection Spray Water Pressure Switch Condensor Temperature Protection
May 24, 2012 PMI Revision 00 26
PMI Revision 00
27
Second stage Water Injection Valves open when steam flow through LPBypass Valves increases more than 45 %
May 24, 2012 PMI Revision 00 28
PMI Revision 00
29
PMI Revision 00
30
PMI Revision 00
31
Actuator LPBPCV
May 24, 2012
500 MW
PMI Revision 00
33
PMI Revision 00
34
PMI Revision 00
35
PMI Revision 00
36
PMI Revision 00
37
PMI Revision 00
38
PMI Revision 00
39
THANK YOU
PMI Revision 00
40