Interlocks.
Interlocks in a substation is used to ensure the
safety of the equipments , operating personal and to prevent the wrong sequence of operations.
person close the earth switch without opening the isolator then it can be the cause of phase to earth fault. Which is an example of wrong sequence of operation or human error this is also hazardous for human life and equipments.
Opening of isolator without opening of circuit breaker
Bay operation/Switching.
Bay opening
Bay closing Protection trip(Bay opening due to protection)
Sequence of operation.
De-energization of a bay (Opening of a bay) I. Circuit breaker open II. Isolator open III. Earth switch close
I. II. III.
Protection trip
At the time of fault circuit breaker will open instantaneously .
Circuit breaker
Earth switch
Isolator.
Bus isolator close interlocks:
Bus earth switch open II. Associated earth switch open III. Circuit breaker open IV. Earth switch after CB open V. Isolator switch in remote position
I.
.
Bus isolator open interlocks: .
Circuit breaker open II. Associated earth switch open III. Earth switch after CB open IV. Isolator switch in remote position
I.
.
Line isolator close interlocks: .
Associated earth switch open II. Circuit breaker open III. Earth switch after CB open IV. Isolator switch in remote position
I.
.
Line isolator open interlocks: .
Circuit breaker open II. Associated earth switch open III. Earth switch after CB open IV. Isolator switch in remote position
I.
dead bus and dead line live bus and dead line dead bus and live line live bus and live line
Continued.
.
Line earth switch close interlocks:
Associated line