Sie sind auf Seite 1von 13

Advant Controller 500 Insert image here

ABB Stotz-Kontakt Training page - 1 V1.0

The PLC Browser

AC500 PLC Browser

Overview

The task of the PLC Browser How to open the PLC Browser The PLC Browser commands

ABB Stotz-Kontakt Training page - 2 PLC Broeser AC500

AC500 PLC Browser

Coming up

The task of the PLC Browser How to open the PLC Browser The PLC Browser commands

ABB Stotz-Kontakt Training page - 3 PLC Broeser AC500

AC500 PLC Browser

Task Of The PLC Browser

Operates only in ONLINE - Mode:


The PLC Browser - is a terminal (Monitor) - provides standard commands for direct access of the CPU like: diagshow all
ABB Stotz-Kontakt Training page - 4 PLC Broeser AC500

(overview over errors) (system date) (system time) (execution time)

date time filename tsk

AC500 PLC Browser

Coming up

The task of the PLC Browser How to open the PLC Browser The PLC Browser commands

ABB Stotz-Kontakt Training page - 5 PLC Broeser AC500

ABB Stotz-Kontakt Training page - 6 PLC Broeser AC500

AC500 PLC Browser

How To Open The PLC Browser

AC500 PLC Browser

Coming up

The task of the PLC Browser How to open the PLC Browser The PLC Browser commands

ABB Stotz-Kontakt Training page - 7 PLC Broeser AC500

AC500 PLC Browser

Der PLC Browser Commands 1


Command ? mem memc memd reflect dpt ppt pid pinf Meaning Display of all implemented commands Memory dump from up to Memory dump relative to code area Memory dump relative to data area Reflect actual command line (for test purposes) Output of the data pointer table Output of the block pointer table Output of the project ID Output project information in the format: pinf Address of Structure: 16#0013CF74 Date: 4213949F Project Name: MODBUS_Test_BB.pro Project Title: Test MODBUS Project Version: V1.0 Project Author: Brigitte Blei Project Description: Test of serial interfaces End of Project-info. Implementation Standard Standard Standard Standard Standard Standard Standard Standard Standard

ABB Stotz-Kontakt Training page - 8 PLC Broeser AC500

AC500 PLC Browser


tsk

Der PLC Browser Commands 2


Meaning Output IEC task list with task information in the format: tsk Number of Tasks: 1 Task 0: Main program, ID: 1519472 Cycle count: 45402 Cycle time: 1 ms Cycle time (min): 1 ms Cycle time (max): 1 ms Cycle time (avg): 1 ms Status: RUN Mode: CONTINUE ---Priority: 10 Interval: 5 ms Event: NONE ---Function pointer: 16#00601584 Function index: 131 Start user program Stop user program Reset user program Reset user program cold Reset user program original Reload boot project from Flash memory Implementation Standard

Command

startprg ABB Stotz-Kontakt Training page - 9 PLC Broeser AC500 stopprg resetprg resetprgcold resetprgorg reload

Standard Standard Standard Standard Standard Standard

AC500 PLC Browser


Command getprgprop

Der PLC Browser Command 3


Meaning Output program properties in the format: getprgprop Name: MODBUS_FBP_Test_BB.pro Title: Test MODBUS Version: V1.0 Author: Brigitte Blei Date: 4213949F Output program status in the format: getprgstat Status: Run Last error: Id 00000000 TimeStamp 000055F3 Parameter 00000000 Text Flags: File command copy File command rename File command delete File command dir Save retain variables to SD card Restore retain variables from SD card Set PLC password (required when logging in!) Delete PLC password Display PLC utilization (system+IEC+tasks+communication) Implementation Standard

getprgstat

Standard

filecopy filerename filedelete ABB Stotz-Kontakt Training page - 10 PLC Broeser AC500 filedir saveretain restoreretain setpwd delpwd plcload

No No No No Specific Specific Standard Standard Specific

AC500 PLC Browser

Der PLC Browser Command 4


Command Meaning Implementation

rtsinfo

Display firmware information (version, driver) in the format: rtsinfo rts version: 2.4.0.4 uses IO driver interface rts api version: 2.404 4 driver(s) loaded driver 1: AC500 CPU driver, device interface version: 2.401 driver 2: AC500 I/O-Bus driver, device interface version: 2.401 driver 3: AC500 COM driver, device interface version: 2.401 driver 4: AC500 Coupler driver, device interface version: 2.401 Display driver V10 AC500 PM581 V1.0 Feb 14 2005 11:15:39 Bootcode V1.18 April 1 2005 Reset the diagnosis system Quit all errors (except errors which have to be quit exclusively) Quit all errors of the class X (with X= 1...4)

Specific

ABB Stotz-Kontakt Training page - 11 PLC Broeser AC500

diagreset diagquit all diagquit X

Specific Specific Specific

AC500 PLC Browser

Der PLC Browser Command 5


diagshow all Show all errors in the format: diagshow all --- All errors --State Class Comp Dev Mod Ch Err 0152502216 active and quitted 4 9 22 31 31 8 1970-01-01 00:00:08 occurred disappeared 1970-01-01 00:00:15 quitted 0152369165 active not quitted 4 9 20 31 0 13 1970-01-01 01:19:12 occurred disappeared quitted --- end --Specific

ABB Stotz-Kontakt Training page - 12 PLC Broeser AC500

time date batt sdappl sdfunc reboot

Display and set the time of the realtime clock Display and set the date of the realtime clock Poll the battery status Save the boot project to the SD card Display and change the function of the SD card Reboot the PLC (CoDeSys logs out)

Specific Specific Specific Specific Specific Specific

Insert image here


ABB Stotz-Kontakt Training page - 13 V1.0

END FIN ENDE

END

STO/ VPS Training

Das könnte Ihnen auch gefallen