Sie sind auf Seite 1von 8

SIMATIC

09.2003

IM 151-7 F-CPU, 6ES7151-7FA00-0AB0, as of Firmware V2.0.2

Produktinformation zum Dokumentationspaket 6ES7988-8FB108AA0 Product Information on Documentation Package 6ES7988-8FB108BA0 Information produit relative la documentation 6ES7988-8FB108CA0

Copyright E Siemens AG 2003 Technische nderungen vorbehalten Technical data subject to change Sous rserve de modifications Siemens Aktiengesellschaft

Copyright Copyright Siemens AG 2003. All Rights Reserved Weitergabe sowie Vervielfltigung dieser Unterlage, Verwertung und Mitteilung ihres Inhalts ist nicht gestattet, soweit nicht ausdrcklich zugestanden. Zuwiderhandlungen verpflichten zu Schadensersatz. Alle Rechte vorbehalten, insbesondere fr den Fall der Patenterteilung oder GM-Eintragung.

Copyright Copyright Siemens AG 2003. All Rights Reserved The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.

Copyright Copyright Siemens AG 2003. Tous droits rservs Toute communication ou reproduction de ce support dinformation, toute exploitation ou communication de son contenu sont interdites, sauf autorisation expresse. Tout manquement cette rgle est illicite et expose son auteur au versement de dommages et intrts. Tous nos droits sont rservs, notamment pour le cas de la dlivrance dun brevet ou celui de lenregistrement dun modle dutilit.

Copyright E Siemens AG 2003 Technische nderungen vorbehalten Technical data subject to change Sous rserve de modifications Siemens Aktiengesellschaft A5E00169369-02

Product Information on
09.2003

IM 151-7 F-CPU, 6ES7151-7FA00-0AB0, as of Firmware V2.0.2

Deutsch
Diese Produktinformation enthlt wichtige Informationen zu 6ES7151-7FA00-0AB0. Sie ist als separater Bestandteil aufzufassen und in Zweifelsfllen in der Verbindlichkeit anderen Aussagen in Handbchern und Katalogen bergeordnet.

Gltigkeitsbereich dieser Produktinformation


In dieser Produktinformation beschreiben wir Ihnen die Spezifika der IM 151-7 F-CPU im Vergleich zur IM 151-7 CPU mit der Bestellnummer 6ES7 151-7AA10-0AB0. Weitere Informationen zu der IM 151-7 CPU finden Sie im zugehrigen Handbuch, Ausgabe 07/2003 im Dokumentationspaket 6ES7151-1AA00-8AA0, welches Sie zustzlich zu dieser Produktinformation bentigen.

Einsatzgebiete
Haupteinsatzgebiete der IM 151-7 F-CPU sind Personen- und Maschinenschutz und Brennersteuerungen. Neben dem Sicherheitsprogramm knnen Sie auch StandardAnwendungen programmieren.

Sie mchten die IM 151-7 F-CPU einsetzen fr Anwendungen der Sicherheitstechnik Standard-Anwendungen

dann bentigen Sie STEP 7 ab Version 5.2 Optionspaket S7 Distributed Safety ab V 5.2 STEP 7 ab Version 5.2

Spezielles Handling bei der Funktion RAMtoROM:


Datenbausteine des Sicherheitsprogramms werden nicht vom Arbeitsspeicher in den Ladespeicher kopiert.

Product Information on IM 151-7 F-CPU A5E00169369-02

SFC 13 DPNRM_DG
Die SFC 13 DPNRM_DG wird nicht untersttzt.

Einschrnkungen bei SFC 22 CREAT_DB, SFC 23 DEL_DB und SFC 82 CREA_DBL


F-DBs knnen weder erzeugt noch gelscht werden.

Einschrnkungen bei SFC 82 CREA_DBL


Der Parameter ATTRIB, Bit NON_RETAIN ist nicht einstellbar.

Einschrnkung bei SFC 83 READ_DBL und SFC 84 WRIT_DBL


Die Zieladresse darf nicht auf einen F-DB zeigen.

Max. Lokaldatengre pro Baustein


Fr die IM 151-7 F-CPU betrgt die maximale Lokaldatengre pro Baustein 510 Byte.

Hardware diagnostizieren bei F-Modulen ET 200S


Die Diagnose in HW Konfig Hardware diagnostizieren ist mglich fr die F-Module 4/8 F-DI DC24V PROFIsafe, 4 F-DO DC24V/2A PROFIsafe und PM-E F DC24V PROFIsafe ab Erzeugnisstand 03 und fr das PM-D F DC24V PROFIsafe ab Erzeugnisstand 04.

DP-Mastermodul
Das DP-Mastermodul wird nicht untersttzt.

Buslngen
Buslngen > 1 m sind nicht erlaubt. Der Parameter Buslnge wird nicht untersttzt.

OBs 55, 56 und 57


Die OBs 55, 56 und 57 werden nicht untersttzt.

Anzahl Verbindungen maximal 12 Verbindungen davon maximal 8 Verbindungen fr S7-Basiskommunikation Routing


Die Kommunikationsfunktion Routing wird nicht untersttzt.

Product Information on IM 151-7 F-CPU A5E00169369-02

Uhrzeitsynchronisation
Uhrzeitsynchronisation wird nicht untersttzt.

English

This Product Information contains additional information about 6ES7151-7FA00-0AB0. It is a separate component and should be considered more up-to-date than the information in the manuals and catalogs if uncertainties arise.

Validity of this Product Information


This product information describes the essentials of IM 151-7 F-CPU compared to IM 151-7 CPU with order number 6ES7 151-7AA10-0AB0. You will find more information on IM 151-7 CPU in the corresponding manual of the 6ES7151-1AA00-8BA0, edition 07/2003, documentation package, which you require in addition to this product information.

Areas of Application
IM 151-7 F-CPU is mainly designed for personal and machine safety and burner controls. In addition to the safety program, you can also program standard applications.

You intend to use IM 151-7 F-CPU for Safety-related systems Standard applications

then you require STEP 7 as of version 5.2 Optional package S7 Distributed Safety as of V 5.2 STEP 7 as of Version 5.2

Special Handling of the RAMtoROM Function:


Data blocks of the safety-related program are not copied to the load memory by the work memory.

SFC 13 DPNRM_DG
SFC 13 DPNRM_DG is not supported.

Restrictions with SFC 22 CREAT_DB, SFC 23 DEL_DB and SFC 82 CREA_DBL


F-DBs can neither be created nor deleted.

Restrictions with SFC 82 CREA_DBL


The parameter ATTRIB, Bit NON_RETAIN cannot be set.

Product Information on IM 151-7 F-CPU A5E00169369-02

Restrictions with SFC 83 READ_DBL and SFC 84 WRIT_DBL


The target address may not point to an F-DB.

Maximum Local Data Size per Block


The maximum local data size for IM 151-7 F-CPU is 510 bytes per block.

Diagnosing Hardware in ET 200S F Modules


The diagnostics in HW Config Diagnose Hardware is possible for the F modules 4/8 F-DI DC24V PROFIsafe, 4 F-DO DC24V/2A PROFIsafe and PM-E F DC24V PROFIsafe as of hardware release 03 and for the PM-D F DC24V PROFIsafe as of hardware release 04.

DP master submodule
The DP-Master submodule is not supported.

Bus length
Bus lengths > 1 m are not permitted. The parameter Bus length is not supported.

OBs 55, 56 and 57


The OBs 55, 56 and 57 are not supported.

Number of connections maximum12 connections of which a maximum 8 connections for S7 basic communication Routing
The communication function Routing is not supported.

Time-of-day synchronization
Time-of-day synchronization is not supported.

Product Information on IM 151-7 F-CPU A5E00169369-02

Franais
Cette Information produit contient des indications importantes concernant 6ES7151-6FA00-0AB0. Elle constitue un document spar et, en cas de doute, elle doit tre considre comme prioritaire par rapport aux indications figurant dans les manuels et catalogues.

Domaine de validit de cette information produit


Cette information produit dcrit les spcificits de lIM 151-7 F-CPU en comparaison de lIM 151-7 CPU ayant comme numro de rfrence 6ES7 151-7AA10-0AB0. Vous trouverez la description de lIM 151-7 CPU dans le manuel correspondant dans le pack de documentation 6ES7151-1AA00-8CA0 dition 07/03 dont vous aurez besoin en plus de cette information produit.

Champs dapplication
Les principaux champs dapplication de lIM 151-7 F-CPU sont la scurit des personnes et des machines ainsi que la commande de brleurs. Outre le programme de scurit, vous pouvez programmer des applications standard.

Pour utiliser la IM 151-7 F-CPU dans des ... applications de scurit

vous avez besoin de STEP 7 partir de la version 5.2 Logiciel optionnel S7 Distributed Safety partir de la version V 5.2

applications standard

STEP 7 partir de la version 5.2

Cas particulier de la fonction RAMtoROM :


Les blocs de donnes du programme de scurit ne sont pas copis de la mmoire de travail vers la mmoire de chargement.

SFC 13 DPNRM_DG
La SFC 13 DPNRM_DG nest pas prise en charge.

Restrictions pour les SFC 22 CREAT_DB, SFC 23 DEL_DB et SFC 82 CREA_DBL


Les blocs de donnes F ne peuvent tre ni gnrs ni effacs.

Restriciton pour la SFC 82 CREA_DBL


Il est impossible de rgler le paramtre ATTRIB, Bit NON_RETAIN.

Restrictions pour les SFC 83 READ_DBL et SFC 84 WRIT_DBL


Ladresse de destination ne peut pas tre celle dun bloc de donnes F.
Product Information on IM 151-7 F-CPU A5E00169369-02

La taille maximale des donnes locales par bloc


La taille maximale des donnes locales par bloc est de 510 octets pour la IM 151-7 F-CPU.

Diagnostic du matriel des modules F du ET 200S


La fonction Diagnostic du matriel de HW Konfig est possible pour les modules F 4/8F-DI DC24V PROFIsafe, 4 F-DO DC24V/2A PROFIsafe et PM-E F DC24V PROFIsafe partir de la version 03 et PM-D F DC24V PROFIsafe partir de la version 04.

Module matre DP
Le module matre DP nest pas pris en charge.

Longueurs de bus
Les longueurs de bus > 1 m ne sont pas autorises. Le paramtre Longueur de bus nest pas pris en charge.

OB 55, 56 et 57
Les OB 55, 56 et 57 ne sont pas pris en charge.

Nombre de connexions 12 connexions max. dont 8 connexions max. pour la communication de base S7 Routage
La fonction de communication Routage nest pas prise en charge.

Synchronisme dhorloge
Le synchronisme dhorloge nest pas pris en charge.

Product Information on IM 151-7 F-CPU A5E00169369-02