Project: ETAP Page: 1

Location: 7.0.0 Date: 26-03-2015


Contract: SN: 12345678
Engineer: Revision: Base
Study Case: SC

Filename: sanjen 42 Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

IEC 60909 Standard


3-Phase, LG, LL, & LLG Fault Currents
Short-Circuit Current Based on User-Defined c Factor

Swing V-Control Load Total

Number of Buses: 1 3 7 11

XFMR2 XFMR3 Reactor Line/Cable Impedance Tie PD


Number of Branches: 6 0 0 1 0 3

Synchronous Power Synchronous Induction Lumped


Grid
Generator Motor Machines Load Total

Number of Machines: 3 1 0 0 0 4

System Frequency: 50 Hz

Unit System: Metric


Project Filename: sanjen 42

Output Filename: E:\hydro\sanjen 42\Untitled.SI2


Adjustments

Apply Individual
Tolerance Adjustments /Global Percent
Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C
Transmission Line Resistance: Yes Individual

Cable Resistance: Yes Individual


Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV
Sub-sys %Mag. Ang.

Bus4 Load 11.000 10.476 1 100.00 -30.00

Bus5 Load 0.400 0.381 1 100.00 -60.00

Bus6 Gen. 11.000 10.476 1 100.00 -30.00

Bus7 Load 135.300 135.300 1 100.00 0.00

Bus11 Load 0.400 0.381 1 100.00 -60.00

Bus12 Load 11.000 10.476 1 100.00 -30.00

Bus13 Gen. 11.000 10.476 1 100.00 -30.00

Bus14 Load 0.400 0.381 1 100.00 -60.00

Bus15 Load 11.000 10.476 1 100.00 -30.00

Bus16 Gen. 11.000 10.476 1 100.00 -30.00

Bus17 SWNG 135.300 135.300 1 100.00 0.00

11 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP.
Line/Cable Input Data

Ohms or Siemens per 1000 m per Conductor (Cable) or per Phase (Line)
Line/Cable Length

ID Library Size Adj. (m)


% Tol. #/Phase T (C) R1 X1 Y1 R0 X0

Line1 356 2000.0 0.0 1 75 1.41045 0.86507

Line / Cable resistances are listed at the specified temperatures.


2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted

ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z

T3 0.300 11.000 0.400 4.00 3.09 0 0 0

T4 17.250 11.000 135.300 8.00 18.60 0 0 0

T7 17.250 11.000 135.300 8.00 18.60 0 0 0

T8 0.300 11.000 0.400 4.00 3.09 0 0 0

T9 17.250 11.000 135.300 8.00 18.60 0 0 0

T10 0.300 11.000 0.400 4.00 3.09 0 0 0

2-Winding Transformer Grounding Input Data

Grounding

Transformer Rating Conn. Primary Secondary


ID MVA Prim. kV Sec. kV Type Type kV Amp Ohm Type

T3
0.300 11.000 0.400 D/Y Solid

T4
17.250 11.000 135.300 D/Y Solid

T7
17.250 11.000 135.300 D/Y Solid

T8
0.300 11.000 0.400 D/Y Solid

T9
17.250 11.000 135.300 D/Y Solid

T10
0.300 11.000 0.400 D/Y Solid
Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb


ID Type From Bus To Bus R X

T3 2W XFMR Bus4 Bus5


441.41 1363.94

T4 2W XFMR Bus6 Bus7


2.74 50.91

T7 2W XFMR Bus13 Bus7


2.74 50.91

T8 2W XFMR Bus12 Bus11


441.41 1363.94

T9 2W XFMR Bus16 Bus7


2.74 50.91

T10 2W XFMR Bus15 Bus14


441.41 1363.94

Line1 Line Bus17 Bus7


1.54 0.95

CB8 Tie Breakr Bus6 Bus4

CB15 Tie Breakr Bus13 Bus12

CB18 Tie Breakr Bus16 Bus15


Power Grid Input Data

% Impedance
Power Grid Connected Bus Rating 100 MVA Base Groundin
g
ID ID MVASC kV R X" R/X" Type

U1 Bus17 1200.000 135.300 1.80775 8.13489 0.22 Wye - Solid

Total Connected Power Grids ( = 1 ): 1200.000 MVA

Synchronous Generator Input Data


% Impedance in Machine Base

Synchronous Generator Rating Xd" Grounding


ID Type MVA kV RPM % PF R Adj. Tol. R/X Xd, sat

Gen2 Hydro w/o Damping 16.847 11.000 600 85.00 1.000 19.00 0.0 0.05 155.00

Gen4 Hydro w/o Damping 16.847 11.000 600 85.00 1.000 19.00 0.0 0.05 155.00

Gen5 Hydro w/o Damping 16.847 11.000 600 85.00 1.000 19.00 0.0 0.05 155.00

Total Connected Synchronous Generators ( = 3.00 ) : 50.541 MVA


SHORT- CIRCUIT REPORT

Fault at bus : Bus7

Nominal kV = 135.30 1.10 (User-Defined)

Line-To-Ground Fault
Contribution % Voltage at From Bus Current at From Bus (kA)

From Bus To Bus Va Vb Vc Ia Ib


ID ID Mag. Ang. Mag. Ang. Mag. Ang. Mag. Ang. Mag. Ang.

Bus7 Total 0.00 0.0 99.34 -116.3 94.47 117.6 5.584 -74.2 0.000 0.0

Bus17 Bus7 20.49 -28.7 95.87 -114.7 94.49 114.8 4.231 -70.6 0.513 99.5
Bus6 Bus7 61.70 -48.2 64.10 -130.5 94.72 89.7 0.462 -85.0 0.171 -80.5
Bus13 Bus7 61.70 -48.2 64.10 -130.5 94.72 89.7 0.462 -85.0 0.171 -80.5
Bus16 Bus7 61.70 -48.2 64.10 -130.5 94.72 89.7 0.462 -85.0 0.171 -80.5

U1 Bus17 100.00 0.0 100.00 -120.0 100.00 120.0 4.231 -70.6 0.513 99.5
Gen2 Bus6 95.24 -30.0 95.24 -150.0 95.24 90.0 2.132 -86.8 2.177 92.3
Bus5 Bus4 84.56 -73.9 47.81 -178.1 86.33 73.6 0.000 0.0 0.000 0.0
Gen4 Bus13 95.24 -30.0 95.24 -150.0 95.24 90.0 2.132 -86.8 2.177 92.3
Bus11 Bus12 84.56 -73.9 47.81 -178.1 86.33 73.6 0.000 0.0 0.000 0.0
Gen5 Bus16 95.24 -30.0 95.24 -150.0 95.24 90.0 2.132 -86.8 2.177 92.3
Bus14 Bus15 84.56 -73.9 47.81 -178.1 86.33 73.6 0.000 0.0 0.000 0.0

Bus6 Bus4 61.70 -48.2 64.10 -130.5 94.72 89.7 0.000 0.0 0.000 0.0

Bus13 Bus12 61.70 -48.2 64.10 -130.5 94.72 89.7 0.000 0.0 0.000 0.0

Bus16 Bus15 61.70 -48.2 64.10 -130.5 94.72 89.7 0.000 0.0 0.000 0.0

# Indicates fault current contribution is from three-winding transformers


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta-Y transformer
Short-Circuit Summary Report

3-Phase, LG, LL, LLG Fault Currents

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground


ID kV I"k ip Ik I"k ip Ib Ik I"k ip Ib

Bus7
135.300 5.243 10.642 4.901 5.584 11.335 5.584

All fault currents are in rms kA. Current ip is calculated using Method C.

* LLG fault current is the larger of the two faulted line currents.
Sequence Impedance Summary Report

Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance

Bus7 135.300 4.82684 15.66336 16.39021 4.87082 15.53456


015
678
e

mal

Total
3 10

4
Y0

0.0000055 2.08094 2.90175 0.000003


Phase Shift

Type Angle

0 0 4.0000 Std Pos. Seq. -30.000

0 5.000 8.0000 Std Pos. Seq. 30.000

0 5.000 8.0000 Std Pos. Seq. 30.000

0 0 4.0000 Std Pos. Seq. -30.000

0 5.000 8.0000 Std Pos. Seq. 30.000

0 0 4.0000 Std Pos. Seq. -30.000

Secondary
kV Amp Ohm
nce, Pos. Seq., 100 MVAb
Z Y

1433.59

50.99

50.99

1433.59

50.99

1433.59

1.81 0.2029036
Excitation
Conn. Type Amp Type

Wye 3.00 Sal-pole 160%

Wye 3.00 Sal-pole 160%

Wye 3.00 Sal-pole 160%


Ic Sequence Current (kA)
Mag. Ang. I1 I2 I0

0.000 0.0 1.861 1.861 1.861

0.530 97.8 1.587 1.576 1.071


0.177 -82.2 0.095 0.098 0.270
0.177 -82.2 0.095 0.098 0.270
0.177 -82.2 0.095 0.098 0.270

0.530 97.8 1.587 1.576 1.071


0.057 -125.7 1.227 1.262 0.000
0.000 0.0 0.000 0.000 0.000
0.057 -125.7 1.227 1.262 0.000
0.000 0.0 0.000 0.000 0.000
0.057 -125.7 1.227 1.262 0.000
0.000 0.0 0.000 0.000 0.000

0.000 0.0 0.000 0.000 0.000

0.000 0.0 0.000 0.000 0.000

0.000 0.0 0.000 0.000 0.000


*Line-to-Line-to-Ground
Ik I"k ip Ib Ik

5.584 4.556 9.247 4.556 4.556 5.564 11.294 5.564 5.564


Fault Zf (ohm)
Reactance Impedance

15.53456 16.28028 2.89730 13.21325 13.52717 0.00000 0.00000 0.00000


0.00000