MCR-FL-D-U-I-2SP-230 28 64 228-03
Prozess-Steuergerät
deutsch
für Strom-/Spannungssignale,
mit Totalisator und 2 Grenzwerten
Process Controller
for Current / Voltage signals,
english
with Adding Counter
and 2 Limits
Contrôleur de process
français
pour signaux de courant/de tension,
avec totalisateur et 2 valeurs limite
español
Controlador de proceso
para señales de corriente y tensión,
con totalizador y dos valores límite
Werkeinstellung
factory preset
réglage usine
1 Sicherheits- und Warnhinweise
1.1 Bestimmungsgemäßer Gebrauch ................................................................... 4
2. Technische Daten
2.1 Allgemeine Angaben ........................................................................................................ 5
2.2 Elektrische Daten ............................................................................................................. 5
2.2.1 Stromversorgung ............................................................................................... 5
2.2.2 Eingänge .............................................................................................................. 5
2.2.3 Ausgänge ............................................................................................................ 6
2.3 Mechanische Daten ......................................................................................................... 7
2.4 Umgebungsbedingungen ................................................................................................ 7
2.5 Lieferumfang ..................................................................................................................... 7
2.6 Bestellschlüssel ............................................................................................................... 7
3. Einbau ................................................................................................................................ 8
4. Elektrische Anschlüsse
4.1 Messeingänge .................................................................................................................. 8
4.2 Steuereingänge und Hilfsspannungen ......................................................................... 9
4.3 Spannungsversorgung und Grenzwert-Ausgänge .................................................... 9
5. Parametrieren
5.1 Parametriermodus ...........................................................................................................10
5.2 Eingangsparameter für Momentanwert .......................................................................11
5.2.1 Bereich für Mess-Signal wählen ....................................................................11
5.2.2 Dezimalpunkt für Momentanwert einstellen .................................................11
5.2.3 Bereichsgrenzen ändern ..................................................................................12
5.2.4 Kennlinie ändern ................................................................................................13
5.3 Anzeigekennlinie parametrieren
5.3.1 Anzahl der Stützstellen eingeben ...................................................................14
5.3.2 Erste Stützstelle definieren ..............................................................................15
5.3.3 Zweite Stützstelle definieren ...........................................................................15
5.3.4 Weitere Stützstellen definieren .......................................................................15
5.4 Totalisator
5.4.1 Eingangsschwelle für den Totalisator einstellen .........................................15
5.4.2 Totalisator parametrieren ................................................................................16
5.4.2.1 Dezimalpunkt für Totalisatorwert einstellen ...............................18
5.4.2.2 Gesamtskalierung für Totalisatorwert .........................................18
5.4.3 Rückstellung des Totalisatorwert ...................................................................19
5.5 Grenzwerte / Grenzwert-Ausgänge
5.5.1 Grenzwert 1/Grenzwert-Ausgang 1 ................................................................20
5.5.1.1 Grenzwert 1 aus-/einschalten .......................................................20
5.5.1.2 Grenzwert 1 zuordnen ....................................................................20
5.5.1.3 Mode für Grenzwert-Ausgang 1 wählen .....................................20
5.5.1.4 Hysterese für Grenzwert 1 .............................................................21
5.5.1.5 Latch-Signal auf Grenzwert-Ausgang 1 rücksetzen .................22
5.5.1.6 Signalform für Grenzwert-Ausgang 1 wählen ...........................23
Seite 2
5.5.2 Grenzwert 2/Grenzwert-Ausgang 2 ............................................................... 23
5.5.2.1 Grenzwert 2 aus-/einschalten ...................................................... 23
5.5.2.2 Grenzwert 2 zuordnen .................................................................... 23
5.5.2.3 Mode für Grenzwert-Ausgang 2 wählen .................................... 23
5.5.2.4 Hysterese für Grenzwert 2 ............................................................ 24
5.5.2.5 Latch-Signal auf Ausgang 2 rücksetzen .....................................24
5.5.2.6 Signalform für Ausgang 2 wählen ............................................... 25
deutsch
5.6 MIN/MAX-Erfassung .......................................................................................................25
5.6.1 Maximalwert überwachen ....................................................................................25
5.6.1.1 Maximalwert rücksetzbar ............................................................. 25
5.6.2 MIN-Wert überwachen ....................................................................................25
5.6.2.1 MIN-Wert rücksetzbar ...................................................................26
5.6.3 Auswirkung überschreiten der Messbereichsgrenzen oder
Overflow/Underflow auf MIN/MAX ............................................................... 26
5.7 Netzbrummfilter ............................................................................................................... 26
5.8 Defaultwerteinstellung ................................................................................................... 27
5.9 Ende der Parametrierung ...............................................................................................27
5.10 Parametrierung überprüfen/ändern ............................................................................. 28
6. Betrieb ............................................................................................................................... 28
6.1 Anzeige im Betrieb umschalten .................................................................................... 29
6.2 Grenzwerte im Betrieb einstellen ................................................................................. 30
6.3 Rücksetzen der MIN/MAX-Werte ................................................................................ 30
6.4 Rücksetzen des Totalisators .......................................................................................... 32
6.5 Display-Hold ..................................................................................................................... 32
Seite 3
1 Sicherheits- und Warnhinweise
!
– bestimmungsgemäß
– in technisch einwandfreiem
Zustand
– unter Beachtung der Bedien-
ungsanleitung und den allgemei-
nen Sicherheitsbestimmungen.
1. Vor Durchführung von Installations- oder 6. Die Digitalanzeige ist nicht geeingent für
Wartungsarbeiten stellen Sie bitte si- den explosionsgeschützten Bereich und
cher, dass die Digitalanzeige von der den Einsatzbereichen, die in EN 61010
Versorgungsspannung getrennt ist. Teil 1 ausgeschlossen sind.
2. Setzen Sie die Digitalanzeige nur bestim- 7. Die Digitalanzeige darf nur im ordnungs-
mungsgemäß ein. gemäß eingebautem Zustand entspre-
3. In technisch einwandfreiem Zustand. chend dem Kapitel
4. Unter Beachtung der Bedienungsanlei- “allgemeine technische Daten” betrie-
tung und den allgemeinen Sicherheits- ben werden.
bestimmungen.
5. Beachten Sie länder- und anwendungs-
spezifische Bestimmungen
Seite 4
2. Technische Daten
deutsch
signalisierung
Datensicherung EEPROM, 1 Mio. Speicherzyklen oder 10 Jahre
Prüfspannungen EN61010-1 für Verschmutzungsgrad 2 und Überspan-
nungskategorie 2
EMV Störabstrahlung EN 55011 Klasse B
Störfestigkeit EN61000-6-2
2.2.2 Eingänge
Messeingänge
Stromeingang (DC)
Bereiche 0 ... 20 mA, 4 ... 20 mA
Auflösung 2 µA
Spannungsabfall max. 2 V bei 20 mA
Max. Strom 50 mA
Spannungseingang (DC)
Bereiche 0 ... 10 V, 2 ... 10 V, ±10 V
Auflösung 1 mV
Eingangswiderstand > 2 MΩ
Max. Spannung ± 30 V
A/D-Wandler Dual-Slope
Messgeschwindigkeit ca. 2 Messungen/sec
Linearität < 0,1% ±1 Digit über den gesamten
Messbereich bei 20°C Umgebungstemperatur
Nullabgleich automatisch
Temperaturdrift 100 ppm/K
Seite 5
Digitale Eingänge
Eingang MPI* Funktion des Eingangs abhängig von Parametrierung
1. Funktion Display-Hold zum Anhalten der Momentanwert
2. Funktion Reset- Rücksetzen der Grenzwert-Ausgänge
Grenzwert-Latch
3. Funktion Reset-Totalisator Rücksetzen des Totalisators
*MPI: Multi Purpose Input
2.2.3 Ausgänge
Grenzwert-Ausgang 1/Grenzwert-Ausgang 2
Relais mit potentialfreiem Wechselkontakt
Programmierbar als Öffner oder Schließer
Schaltspannung 250 V AC/300 V DC
Schaltstrom max. 3 A AC/DC, min. 30 mA DC
Schaltleistung 2000 VA / 50 W
oder NPN-Optokoppler mit offenem Kollektor und offenem Emitter
Schaltleistung 30 V DC/15 mA
UCEsat bei Ic = 15 mA max. 2,0 V DC
UCEsat bei Ic = 5 mA max. 0,4 V DC
Seite 6
2.3 Mechanische Daten
Gehäuse Schalttafelgehäuse 96 x 48 mm nach DIN 43 700,
RAL 7021
Abmesungen (B x H x T) 96 x 48 x 90 mm
Schalttafelausschnitt (B x H) 92+0,8 x 45+0,6 mm
Einbautiefe ca. 83 mm
Gewicht ca. 220 g
deutsch
Schutzart IP 65 (frontseitig)
Anschluss
Stromversorgung und Ausgänge: 1 x Schraubklemme, 8-polig, RM 5.08
Mess- und Steuereingänge: 1 x Schraubklemme, 11-polig, RM 3.81
Reinigung Die Frontseite des Gerät darf nur mit einem weichen,
mit Wasser angefeuchteteten Tuch gereinigt
werden.
2.4 Umgebungsbedingungen
Umgebungstemperatur –20°C ... +65°C
Lagertemperatur –40°C ... +85°C
Klimafestigkeit < 75% rel. Feuchte, nicht kondensierend
2.5 Lieferumfang
Prozessgerät
Schraubklemme, 8-polig, RM 5.08
Schraubklemme, 11-polig, RM 3.81
Spannbügel
Dichtung
Bedienungsanleitung multilingual
1 Blatt selbstklebende Symbole
2.6 Bestellschlüssel
Seite 7
3. Einbau
Schalttafelausschnitt
4. Elektrische Anschlüsse
Ansicht auf Rückseite
4.1 Messeingänge
Stromeingang Spannungseingang
X2 X2
+ - - +
1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11
1 Stromeingang (I) 2 GND1 (Analog)
0 ... 20 mA / 4 ... 20 mA 3 Spannungseingang (U)
2 GND1 (Analog) 0 ... 10 V, 2 ... 10 V, -10 ... +10 V
Seite 8
4.2 Steuereingänge und Hilfsspannungen (Uout)
deutsch
X2
Display-Hold/Reset Totalisator"
1 2 3 4 5 6 7 8 9 10 11 7 GND2 (KEY/MPI)
6 Tastenverriegelung "Key"
Seite 9
5 Parametrieren – Grenzwerte
Die Parameter müssen vor Inbetriebnah- Es können entweder keiner, einer oder
me eingestellt werden. zwei der Grenzwerte aktiv sein. Hysterse
– Eingangsparameter und Ausgangsparameter werden einge-
Die Kennlinie des Geräts muss entspre- stellt. Bei Überschreiten der Grenzwerte
chend dem eingesetzten Sensor parame- wird ein Signal auf dem zugeordnetetn
triert werden. Ausgang ausgegeben und die zugehörige
LED eingeschaltet.
– Kennlinie
Der Grenzwert selbst wird im Betriebs-
Die Zuordnung der Eingangssignale zu
modus eingestellt!
den Anzeigewerten erfolgt über Kennli-
nien. Diese Kennlinie ist über Wertepaare
einzugeben. – Netzbrummfilter
– Totalisator Zur Verminderung von netzseitigen und
umgebungsbedingten Störungen kann die
Für die Anzeige der Totalisator-Werte, die
lokale Netzfrequenz ausgewählt werden.
im Gerät gebildet werden, sind der Dezi-
malpunkt, der Faktor für die Maßeinheit
und die Skalierung einzustellen.
5.1 Parametriermodus
Sie bringen das Gerät in den Parametrier- Einstieg in den Menüpunkt:
modus, indem Sie Entweder ist eine Auswahl zu treffen oder
1. die gedrückt halten. ein Wert ist einzustellen.
2. das Gerät mit der Stromversorgung ver- Taste drücken. Das Wechseln in der
binden. Anzeige stoppt.
3. Wenn in der Anzeige – Eine Auswahl treffen:
erscheint, die Taste loslassen. Mit der Taste werden alle Möglich-
Anzeige und Tasten kennen lernen keiten nacheinander angezeigt.
Durch das rollierende Prinzip kann die – Auswahl übernehmen:
Auswahl bzw. Einstellung beliebig oft Taste drücken. Der ausgewählte Pa-
durchlaufen werden. rameter wird gespeichert. Der nächste
Menüpunkt: Menüpunkt erscheint.
Die Anzeige wechselt alle 2• s zwischen – Einen Wert einstellen:
Menüpunkt und Auswahl. Die blinkende Stelle zeigt an,
Menü <–> Auswahl dass sie für die Einstellung
freigegeben ist.
Taste drücken, Ziffer wird erhöht.
Seite 10
Wenn negative Werte zugelassen sind, gilt Wert übernehmen: Taste drücken,
bei der höchsten Dekade: Nach „9“ folgt der Wert wird gespeichert. Der nächste
„–“ , danach „–1“ und dann erst „0“. Menüpunkt erscheint.
Taste drücken, zur nächsten Ziffer
wird weitergeschaltet.
deutsch
5.2 Eingangsparameter für Momentanwert
Hier werden alle Einstellungen vorgenom- Die Anzeigewerte erhält man über eine
men, die das Eingangssignal und die Kennlinie aus dem Eingangssignal.
zugehörigen Anzeigewerte betreffen.
Seite 11
5.2.3Bereichsgrenzen ändern
Die vorgegebenen Grenzen für die ver- entweder übernommen oder angepasst
schiedenen Eingangsbereiche können werden.
Parameter Parameter
Möglicher Wertebereich Möglicher Wertebereich
0 .. 10 V –0.500 ... 10.500 –0.500 ... 10.500
2 .. 10 V 01.500 ... 10.500 01.500 ... 10.500
-10 .. +10 V –10.500 ... 10.500 –10.500 ... 10.500
0 .. 20 mA –1.000 ... 21.000 –1.000 ... 21.000
4 .. 20 mA 03.000 ... 21.000 03.000 ... 21.000
Unterschreitet oder überschreitet das Einstellungen außerhalb der Werteberei-
Mess-Signal den programmierten Wert, che sind nicht möglich. Eine Fortsetzung
wechselt die Anzeige zwischen Warnmel- der Programmierung mit der Taste ist
dung und dem Messwert erst möglich, wenn die Einstellung korrekt
bzw. zwischen der Warnmeldung ist.
und dem Messwert.
Untere Bereichsgrenze
Menü <–> Auswahl
Unterschreitet das Meßsignal den hier
Bsp.: –5,000 eingestellten Wert wird im
Stelle wählen Wechsel mit dem aktuellen Messwert an-
gezeigt.
Ziffer einstellen
Underflow: Ist das Mess-Signal kleiner als
Stelle wählen –13,60 V bzw wird dies in der Anzeige
Ziffer einstellen durch signalisiert. Ströme
< 0,0 mA werden nicht gemessen.
mit übernehmen
Obere Bereichsgrenze
Menü <–> Auswahl
Seite 12
5.2.4 Kennlinie ändern
deutsch
Kennlinie eingeben/ändern ➱ Kap. 5.3, 13
mit übernehmen
Anzeigebereich
Seite 13
Eingangsbereich –10 ... + 10 V
Anzeigebereich
Seite 14
5.3.2 Die erste Stützstelle definieren
Menü <–> Auswahl
Zuerst wird der Eingangswert in der je- Beispiel:•–5,000
weiligen Einheit (z.B. V, mA) für den Be-
Stelle wählen
ginn der Kennlinie eingestellt.
Ziffer einstellen
deutsch
mit übernehmen
Danach wird der Anzeigewert für den Be- Menü <–> Auswahl
ginn der Kennlinie eingestellt.
Beispiel:•–250,0
Stelle wählen
Ziffer einstellen
mit übernehmen
5.3.3 Die zweite Stützstelle definieren
Eingangswert einstellen Menü <–> Auswahl
Beispiel: 2,000
mit übernehmen
mit übernehmen
mit übernehmen
5.4.2Totalisator parametrieren
Der Totalisator addiert die Momentanwer- Der angezeigte Totalisatorwert wird aus
te mit einer Abtastrate von 1 Sekunde. dem Ergebnis im Totalisator gebildet,
Aufsummiert ergeben diese aktuellen indem der Dezimalpunkt in der Anzeige
Messwerte als Ergebnis einen sehr viel nach Bedarf gesetzt wird.
größeren Zahlenwert, der den Anzeigeum- Beachte: Zur Optimierung der Genauigkeit
fang in der Regel übersteigt. Also muss so empfielt es sich, den Anzeigeumfang für
umgerechnet werden, dass das Ergebnis den Totalisatorwert voll zu nutzen. Beim
wieder in den Anzeigeumfang passt. Dies Momentanwert gilt dies ebenfalls, wenn
erfolgt mittels Faktor und Skalierung. sich die Gesamtskalierung mit einer ver-
Erläuterung: Wenn die Anzeige den Mo- tretbaren Stellenzahl darstellen lässt
mentanwert 12 345 anzeigt und dieser 1 (möglichst geringer Rundungseffekt).
Stunde lang addiert wird, entsteht mit Der Totalisator kann elektrisch über den
3• 600 Werten à 12 345 als Ergebnis MP-Eingang oder/und manuell über die
4 442 000. Dieser Wert kann erst angezeigt rote Taste rückgesetzt werden.
werden, nachdem er durch 1 000 geteilt
wurde. D.h. in der Anzeige steht der Zah-
lenwert 44 442.
Seite 16
Beispiel 1:
Ein leerer Behälter wird mit durchschnitt- entleert und der Summenwert auf 0 ge-
lich 10 l/s gefüllt, bis ein Volumen von 2 m3 stellt (Reset).
erreicht ist. Danach wird der Behälter
deutsch
Momentanwerte
Summenwerte
Faktor x Skalierung
Möglichkeiten zur Einstellung
0,1000 x 10
der Gesamtskalierung
1,0000 x 1
usw.
Hinweis:
Falls der Totalisatorwert als Gewicht an-
gezeigt werden soll, ist das spezifische
Gewicht über den Faktor zu berücksichti-
gen.
Seite 17
Beispiel 2:
Wird ein Reifen 1 Stunde lang bei einer Geschwindigkeit von 180 km/h getestet,
legt er 180 km zurück.
Hinweis: Da jede Sekunde 1 Wert überge- Zahlenwert von 18• 000 am Ausgang des
ben wird, werden in 1 Stunde 3• 600 Werte Totalisators
aufsummiert. Die Gesamtskalierung von
Um den Anzeigeumfang für den Totalisa- 648 000.0 : 18 000 = 0,027777...wird durch
torwert voll zu nutzen, wird das erwartete die Einstellungen von Faktor = 2,7778 (ge-
Ergebnis mit zwei Dezimalstellen darge- rundeter Wert) und Skalierung = 0,01 ge-
stellt. Die 180,00 km entsprechen einem bildet.
mit übernehmen
Seite 18
Skalierung einstellen
deutsch
1
0,1
0,01
0,001
mit übernehmen
5.4.3 Rückstellung des Totalisatorwertes
Diese Einstellung beeinflusst die Funktion des MP-Eingang ➱ Kapitel 4.2, 9,
Kapitel 5.5.1.5, 22, Kapitel 5.5.2.5, 24 , Kapitel 6.4, 32 und Kapitel 6.5, 32
Der Totalisatorwert kann nur manuell über die rote Taste auf 0 zu-
rückgesetzt werden.
Hinweis: Am MP-Eingang kann ein Display-Hold-Signal angelegt
werden. Die Grenzwert-Ausgänge können im Latch-Mode nur
elektrisch zurückgesetzt werden.
Seite 19
5.5 Grenzwerte/Grenzwertausgänge
Es können kein, ein oder zwei Grenzwerte
aktiv sein.
deutsch
Bei positvem Grenzwert:
Einschalthysterese Ausschalthysterese
Messwert
Grenzwert
positiv
Ausgang
Grenzwert
negativ
Einschalt- Ausschalthysterese
hysterese
Ausgang
Positives Ausgangssingnal
Arbeitskontakt ist geschlossen, wenn der
deutsch
Messwert > Grenzwert 1 ist
Negatives Ausgangssignal
Arbeitskontakt ist geöffnet, wenn der
Messwert > Grenzwert 1 ist
mit übernehmen
5.5.2 Grenzwert 2/Grenzwert-Ausgang 2
5.5.2.1 Grenzwert 2 aus-/einschalten
Menü <–> Auswahl
Beispiel: on
Totalisator
Auto-Mode
mit übernehmen
Seite 23
5.5.2.4 Hysterese für Grenzwert 2
Einschalthysterese Δa für Grenzwert 2 einstellen
Menü <–> Auswahl
mit übernehmen
Positives Ausgangssingnal
deutsch
Arbeitskontakt ist geschlossen, wenn der
aktuelle Messwert > Grenzwert 2 ist
Negatives Ausgangssignal
Arbeitskontakt ist geöffnet, wenn der
mit übernehmen
aktuelle Messwert > Grenzwert 2 ist
5.6 MIN/MAX-Erfassung
Auftretende Extremwerte können erkannt, gespeichert und während des Betriebs auf
Tastendruck angezeigt werden.
5.6.1 Maximalwert überwachen
Menü <–> Auswahl
Beispiel: Yes
nicht rücksetzbar
mit übernehmen
Seite 25
5.6.2.1 MIN-Wert rücksetzbar
nicht rücksetzbar
5.7 Netzbrummfilter
Zur Verminderung von netzseitigen und umgebungsbedingten Störungen (Netzbrumm)
muß das Gerät auf die lokale Netzfrequenz eingestellt werden.
Menü <–> Auswahl
Seite 26
5.8 Defaultwerteinstellung
Über den Parameter hat der An- meter weitergeschaltet werden alle Para-
wender die Möglichkeit alle Parameter auf meter auf den voreingestellten Wert zu-
voreingestellte Werte zurückzusetzen. Im rückgesetzt. Die Programmierung muß
Parameter muß der Wert nicht beendet werden, es kann sofort ein
=07049 programmiert werden. neuer Programmierdurchlauf stattfinden.
deutsch
Wird über die Tasten zum nächsten Para-
Stelle wählen
Seite 27
5.11 Parametrierung überprüfen/ändern
6 Betrieb
Beim Einschalten der Spannungsversor- zustand. Im Betrieb kann die Anzeige die
gung oder nach Beenden der Parametrie- folgenden Meldungen anzeigen.
rung befindet sich das Gerät im Betriebs-
Das Mess-Signal ist kleiner als die dem aktuellen Messwert oder mit
untere Messbereichsgrenze. Diese dem Totalisatorwert.
Meldung erscheint im Wechsel mit
Das Mess-Signal ist größer als die dem aktuellen Messwert oder mit
obere Messbereichsgrenze. Diese dem Totalisatorwert.
Meldung erscheint im Wechsel mit
Seite 28
6.1 Anzeige im Betrieb umschalten
deutsch
Taste Meldung Anzeige
1
aktueller Messwert
1
MIN-Wert (wenn aktiviert)
1 total
1Nach Betätigung bleibt der entsprechen- 2Nach 4 s kehrt die Anzeige automatisch
de Wert der angewählten Funktion in der zum aktuellen Messwert zurück und die
Anzeige. Bei einem PowerOff wird die ak- LED-Anzeige ´Pr1` bzw. `Pr2` werden ge-
tuell angewählte Funktion gespeichert. löscht.
Beim nächsten PowerOn wird der ent-
sprechende Wert dieser Funktion wieder
im Display angezeigt.
Hinweis
Befindet sich ein Grenzwert in der Anzei- Dies kann verhindert werden, indem die
ge, kann dessen eingestellter Wert verän- Tastenverriegelung „Key“ aktiviert wird.
dert werden!
Seite 29
6.2 Grenzwert im Betrieb einstellen
Beispiel 300,0
Beispiel 800,0
mit übernehmen
Rücksetzen ist nur möglich, wenn dies in MIN- oder MAX-Wert in die Anzeige brin-
der Parametrierung aktivert wurde. gen.
• Rote Taste drücken.
• Der gespeicherte Werte wird ge-
löscht.
Seite 30
6.4 Rücksetzen des Totalisators
deutsch
zen manuell mit der roten Taste und/oder
elektrisch mit einem High-Impuls (> 4 V,
> 5 ms) am MP-Eingang.
6.5 Display-Hold
Parameter Einstellungen
Seite 31
1 Safety instructions and warnings ................................................................................. 3
1.1 Use according to the intended purpose ........................................................ 4
2. Technical Data
2.1 Miscellaneous Data ......................................................................................................... 5
2.2 Electrical Data .................................................................................................................. 5
2.2.1 Power Supply ..................................................................................................... 5
2.2.2 Inputs ................................................................................................................... 5
2.2.3 Outputs
2.3 Mechanical Data .............................................................................................................. 7
2.4 Environmental conditions ................................................................................................ 7
2.5 Delivery .............................................................................................................................. 7
2.6 Order Code ........................................................................................................................ 7
3. Mounting ........................................................................................................................... 8
4. Electrical Connections
4.1 Measuring inputs ............................................................................................................. 8
4.2 Control Inputs and Auxiliary Power Supply ................................................................. 9
4.3 Power Supply and Alarm Outputs ................................................................................ 9
5. Parameter Setup
5.1 Parameter mode ..............................................................................................................10
5.2 Parameter input for Instantaneous Value ....................................................................11
5.2.1 Select range for the input signal ....................................................................11
5.2.2 Set the decimal point for the actual value ....................................................11
5.2.3 Change the range limits ....................................................................................12
5.2.4 Scaling Slope ......................................................................................................13
5.3 Setting the Scaling Slope
5.3.1 Enter the number of Scaling points ................................................................14
5.3.2 Define first Scaling point ..................................................................................15
5.3.3 Define second Scaling point ...........................................................................15
5.3.4 Define further Scaling points ...........................................................................15
5.4 Totalizer
5.4.1 Setting the Input Threshold for the Totalizer ................................................15
5.4.2 Totalizer Setup ...................................................................................................16
5.4.2.1 Setting the decimal point for the totalizer ..................................18
5.4.2.2 Overall scaling for the total value ...................................................18
5.4.3 Resetting the Total value ..................................................................................19
5.5 Alarms/Alarm Outputs
5.5.1 Alarm 1/Output 1 ................................................................................................20
5.5.1.1 Alarm 1 off/on ..................................................................................20
5.5.1.2 Select threshold 1 .......................................................................... 20
5.5.1.3 Select mode for output threshold 1 ..............................................20
5.5.1.4 Hysteresis for threshold 1 ..............................................................21
5.5.1.5 Reset Latch signal at output 1 ......................................................22
5.5.1.6 Select signal form for output threshold 1 ...................................23
Page 2
5.5.2 Alarms 2/Output 2 ............................................................................................. 23
5.5.2.1 Alarm 2 off/on .................................................................................. 23
5.5.2.2 Select threshold 2 ........................................................................... 23
5.5.2.3 Select mode for output threshold 2 ............................................. 23
5.5.2.4 Reset Latch signal at output 2 ......................................................24
5.5.2.5 Reset Latch signal at output 2 ...................................................... 24
5.5.2.6 Select signal form for output threshold 2 ...................................25
english
5.7 Mains Hum Filter ............................................................................................................. 26
5.9 Setting default value ....................................................................................................... 27
5.10 End of setup ...................................................................................................................... 27
5.11 Check/alter parameters ................................................................................................. 28
6. Operation .......................................................................................................................... 28
6.1 Switching over the display during operation ............................................................. 29
6.2 Setting the limits during operation ............................................................................... 30
6.3 Resetting the MIN/MAX value ...................................................................................... 30
6.4 Resetting the Totalizer .................................................................................................... 32
6.5 Display Hold ..................................................................................................................... 32
Page 3
1 Safety instructions and warnings
!
– in a way according to its intended
purpose
– if its technical condition is perfect
– adhering to the operating
instructions and the general
safety instructions.
1. Before carrying out any installation or 6. The digital display is not intended for use
maintenance work, make sure that the in areas with risks of explosion and in
power supply of the digital display is the branches excluded by the standard
switched off. EN 61010 Part 1.
2. Only use this digital display in a way ac- 7. The digital display shall only operated if
cording to its intended purpose. it has been correctly mounted in a
3. If its technical condition is perfect. panel, in accordance with the chapter
4. Adhering to the operating instructions “Main technical features”.
and the general safety instructions.
5. Adhere to country or user specific regu-
lations.
Page 4
2. Technical Data
english
2.2.1 Power supply
AC power supply 90 ... 260 V AC/max. 6 VA
external fuse 100 mA/T
DC power supply 10 ... 30 V DC, max. 2 W,
galvanically isolated with inverse polarity protection
external fuse 250 mA/T
Mains Hum Filter digital filter 50 Hz or 60 Hz, programmable
2.2.2 Inputs
Measurement ranges
Current input (DC)
Ranges 0 ... 20 mA, 4 ... 20 mA
Resolution 2 µA
Voltage drop max. 2 V bei 20 mA
Max. current 50 mA
Voltage input(DC)
Ranges 0 ... 10 V, 2 ... 10 V, ±10 V
Resolution 1 mV
Input resitance > 2 MΩ
Max. voltage ± 30 V
Page 5
Digital inputs
Input MPI* Function of the inputs depending on set up
1. Function Display-Hold to stop the instantaneous value
2. Function Reset Reset the alarm value
Alarm Latch
3. Function Reset-Totalizer Resetting the Totalizer
*MPI: Multi Purpose Input
2.2.3 Outputs
Alarm 1/Alarm output 2
Relay output with volt-free changeover contacts
can be setup as normally closed or normally open
Switching voltage 250 V AC/300 V DC
Switching current max. 3 A AC/DC, min. 30 mA DC
Switching power 2000 VA / 50 W
or NPN-optocoupler with open collector and open emitter
Switching power 30 V DC/15 mA
UCEsat at Ic = 15 mA max. 2.0 V DC
UCEsat at Ic = 5 mA max. 0.4 V DC
Page 6
2.3 Mechanical Data
Housing Housing for control panel 96 x 48 mm according to
DIN 43 700, RAL 7021
Dimensions (W x H x D) 96 x 48 x 90 mm
Panel cut-out (B x H) 92+0,8 x 45+0,6 mm
Mounting depth approx. 83 mm
Weight approx. 220 g
Protection IP 65 (on the front side)
Connections
Power supply and output: 1 x screw terminal, 8-pole, RM 5.08
Measurement and control input: 1 x screw terminal, 11-pole, RM 3.81
Interfaces: (*) 1 x screw terminal, 5-pole, RM 3.81
english
Cleaning: The front of the unit is only to be cleaned
with a soft wet (water !) cloth.
2.4 Environmental Conditions
Ambient temperature –20°C ... +65°C
Storage temperature –40°C ... +85°C
Climatic stability relative humidity < 75%, without condensation
Page 7
3. Mounting
4. Electrical connections
View of rear of unit
X2 X2
+ - - +
1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11
1 Current input (I) 2 GND1 (Analogue)
0 ... 20 mA / 4 ... 20 mA 3 Voltage input (U)
2 GND1 (Analogue) 0 ... 10 V, 2 ... 10 V, -10 ... +10 V
Page 8
4.2 Control inputs and auxiliary power supply (Uout)
english
4.3 Power supply and alarm outputs
DC voltage AC voltage
Relay output 7 10 ... 30 V DC 90 ... 260 V AC (N~)
OUT 2 OUT 1 8 GND4 (0 V DC) 90 ... 260 V AC (L~)
X1
1 2 3 4 5 6 7 8 Warning: at 90 ... 260 V AC version.
Please apply the power supply
after the complete installation.
Danger of Death! Please check
unit label before applying the power supply.
Page 9
5 Parameter setup – Alarms/outputs
The parameters have to be set up before Either none, one or two alarm values can
putting the unit into operation. be active. Hysteresis and output parame-
– Input parameter ters are also set up. If the set-point is ex-
The parameters of the scaling slope must ceeded, a signal will be sent out at the
be set up depending on the sensor used. corresponding output and the correspon-
ding LED will be switched on.
– Scaling scope
The alarms themselve are set up in the
The correspondence between the input
operating mode!
signal and the displayed value is given by
the scaling slope. The scaling slope is set
up by entering pairs of values. – Mains Hum Filter
– Totalizer To reduce operational interference
The decimal point, the factor of the meas- caused by the 50/60 Hz mains supply you
uring unit, and the scaling of displaying can choose the local mains frequency.
the total value calculated by the unit must
be set up.
Page 10
Where negative values are permitted, the Enter value: Press the key, the
highest digit will switch from “9” to”–” value will be stored. The next menu item
and only then to “0”. appears.
Press the key to switch to the next
digit.
english
Menu <–> Selection Display range
(–0,500 ... 10,500)
2 ... 10 V (01,500 ... 10,500)
-10 ... +10 V (–10,500 ... 10,500)
0 ... 20 mA (–01,000 ... 21,000)
4 ... 20 mA (03,000 ... 21,000)
0 ... 10 V (–0,500 ... 10,500)
press key to accept the selection
Page 11
5.2.3Changing the Range Limits
Parameter Parameter
Possible range of values Possible range of values
0 .. 10 V –0.500 ... 10.500 –0.500 ... 10.500
2 .. 10 V 01.500 ... 10.500 01.500 ... 10.500
-10 .. +10 V –10.500 ... 10.500 –10.500 ... 10.500
0 .. 20 mA –1.000 ... 21.000 –1.000 ... 21.000
4 .. 20 mA 03.000 ... 21.000 03.000 ... 21.000
If the measured signal falls below or ex- Setting values out of the range is not pos-
ceeds the programmed value, then the sible. It is only possible to continue with
display alternates between and the set-up, using the key, when the
the measured value or between settings are correct.
and the the measured value.
Lower limit
Menu <–> Selection
When the signal drops below the value
Example: –5.000 set here, then the signal alternates with
Select digit the message
Under-range: if the signal is less then
Set digit
–13,60 V than appears in the
Select digit display.
Set digit Current values < 0.0 mA will not be
measured.
press the key to accept the selection
Upper limit
Menu <–> Selection When the signal exceeds the value set
here, then the signal alternates with the
Example: 9,000 message
Select digit
Over-range if the signal is higher than
Set digit 11.00 V or 21.5 mA, then
press the key to accept the selection appears in the display..
Page 12
5.2.4 Changing the Scaling Slope
english
At least two points (2 pairs of value) for the However it should be noted that in all
starting and the end points respectively of cases, whether the slope rises or falls, the
the characteristic curve are reqquiered. values that are inputted (Inp.01 … InP.24)
The curve can be ascending or descend- must increase sequentially.
ing.
At least two points (2 pairs of values) are The scaling slope must lie within the limits
required for the start point and end point of of the input and display ranges. The first
the scaling slope. This slope can be rising and last points can lie on the limits.
or falling. A maximum of 24 scaling points
can be used.
Display range
Page 13
Input range –10 ... + 10 V
Display range
Page 14
5.3.2 Define first Scaling point
Menu <–> Selection
Firstly set the input value for the start of Example:•–5.000
the slope using the respective unit (mA, V)
Select digit
Set digit
english
press the key to accept
5.3.3 Define the second scaling point
Set input value Menu <–> Selection
Example: 2.000
5.4.2Totalizer Setup
The totalizer adds up the instantaneous The displayed total value will be derived
values with a sampling rate of 1 per sec- from the result in the totalizer, leaving the
ond. These values, when added together, decimal point free to be set as required.
give a very large resulting number which
normally exceeds the display range. Note: To optimize the accuracy, it is
Hence, it is necessary to apply a conver- recommended to make use of the full
sion to bring the result within the display totalizer display range. This is also valid
range. This is carried out with the help of for the instantaneous value so far as it is
factors and scaling. possible to display the total scaling with a
Explanation: If the display shows a value reasonable number of decimal digits (least
of 12.345 and this is totalled over an hour, possible rounding effects).
then 3.600 values of 12.345 each give a re- The totalizer value can be reset (set to 0)
sult of 44.442,000. This value can be dis- either via an electrical signal or manually
played only if it has been divided by 1.000. using the red key.
Thus the display shows 44.442.
Page 16
Example 1:
An empty container is filled at an average emptied and the total value set (reset) to 0.
rate of 10 l/s until a volume of 2 m3 is
reached. After this the container is
Instantaneous value
english
Totalizer value
Factor x Scaling
Possibilities for setting the
0,1000 x 10
overall scaling
1,0000 x 1
etc.
Note:
In case it is required to output the totalizer
value as weight, the weight per unit volume
(specific gravity) can taken into considera-
tion by setting the factor correspondingly.
Page 17
Example 2:
If a tyre is tested for 1 hour at a speed of 180• km/h, the total distance travelled is
180 km.
Hint:
Since one value is transferred each a number of 18 000 at the output of the to-
second, 3600 values are totalled in an talizer.
hour. In order to make full use of the dis- The total scaling of
play range of the totalizer, the expected 648 000.0 : 18 000 = 0.027777...
result will be displayed with two decimal Is carried out by setting the factor = 2.7778
digits. The 180.00 km corresponds to (rounded) and the scale = 0.01.
english
Chapter 5.5.1.5, 22, Chapter 5.5.2.5, 24 , Chapter 6.4, 32 and Chapter 6.5, 32
Manual Reset with the red key and/or with an electrical pulse at
the MP input.
Note: The Display Hold function is off. If the display function
is selected, the alarm outputs can be reset
electrically.
Page 19
5.5 Alarms/Alarm outputs
One, two or no alarms can be active.
english
Current
value Positive
alarm
Output
Current Negative
value alarm
Output
Page 22
5.5.1.6 Select Signal Form for Output 1
english
5.5.2 Alarm 2/Alarm output 2
5.5.2.1 Alarm2 on / off
Menu <–> Selection
Example: on
Totalizer
Auto mode
press the key to accept the selection
Page 23
5.5.2.4 Hysteresis for Alarm 2
Set switching on hysteresis Δa for Alarm 2
Menu <–> Selection
Select digit
Set digit
press the key to accept the selection
Set switching off hysteresis Δb for Alarm 2
Menu <–> Selection
Select digit
Set digit ➱ Chapter 5.5.2.6 select signal for output 2
Page 24
5.5.2.6 Select signal form for output 2
english
5.6 MIN/MAX value acquisition
The maximum value may be captured, saved and consulted during operation
by pressing a key.
5.6.1 Capture of MIN/MAX Values
Menu <–> Selection
Example: Yes
not resettable
Page 25
5.6.2.1 Reset Minimum value
not resettable
Page 26
5.8 Setting Default Values
The user has the possibility to set all pa- the keys, then all parameters are reset to
rameters back to their default values by their default values. It is not necessary to
using the parameter . This pa- finish the programming; a new program-
rameter must be programmed ming cycle can take place immediately.
with the value =07049 If you
then proceed to the next parameter using
Select digit
english
Set digit 07049
press the key to accept the selection
Page 27
5.10 Check/Alter Parameters
6 Operation
The unit is in the operating mode, when One of the following will be displayed dur-
the power supply is switched on or at the ing operation.
end of the set-up.
326.81 The measuring signal has measured value, the totalizer value,
been applied and lies within the the MAX value or the MIN value.
limits of the measuring range. The
display will show either the current
The input value is below the lower current measured value or with the
limit of the measuring range. This value of the totalizer.
message alternates with the
˜ The input value is higher than the current measured value or with the
upper limit of the measuring range. value of the totalizer.
This message alternates with the
Page 28
6.1 Changing the Display during Operation
Pressing the P key once for 2 sec will the next display function. The new identi-
identify the function currently selected. If fication will be displayed for 2 sec to con-
within these 2 sec the P key is pressed firm this. After 2 sec the corresponding
again, then the display will proceed to value of the selected function will be dis-
played.
english
1 MAX value (when activated)
2
LED Pr1 ein Alarm 1 (when activated)
2
LED Pr2 ein Alarm 2 (when activated)
1 Total
Note:
When an alarm value is shown in the dis- This can be prevented by disabling the
play, its set value can be changed. panel keys using the "Key" lock.
Page 29
6.2 Setting the Alarms during Operation
When an alarm value is shown in the dis- Note: the “key-lock” should not
play, its set value can be changed. be enabled.
Set Alarm
Display Action
Example: 300.0
Set Alarm
Display Action
Example 800.0
Resetting is only possible if this has been Select Min/Max value display
enabled in the parameter mode. • press the red key.
• the stored value is cleared
Page 30
6.4 Resetting the Totalizer
english
The Display Hold function is only available then the display is "frozen".
for use with the current measured value
and for the totalizer value. The MIN/MAX capture, alarm monitoring
For as long as a high level signal and totalizer functions continue in the
( > 4 V DC ) is present at the MP input, background.
Parameter Settings
Page 31
1 Instructions de sécurité et avertissements
1.1 Utilisation conforme ........................................................................................... 4
2. Caractéristiques techniques générales
2.1 Informations générales ................................................................................................... 5
2.2 Caractéristiques électriques ......................................................................................... 5
2.2.1 Tension d’alimentation ..................................................................................... 5
2.2.2 Entrées ................................................................................................................. 5
2.2.3 Sorties ................................................................................................................. 6
2.3 Caractéristiques mécaniques ......................................................................................... 7
2.4 Conditions d'environnement ........................................................................................... 7
2.5 Pièces livrées..................................................................................................................... 7
2.6 Référence de commande ................................................................................................ 7
3. Montage ............................................................................................................................ 8
4. Raccordements électriques
4.1 Entrées de mesure ........................................................................................................... 8
4.2 Entrées de commande et tensions auxiliaires ............................................................ 9
4.3 Tension d’alimentation et sorties de valeurs limite ................................................... 9
5. Paramétrage
5.1 Mode de paramétrage ....................................................................................................10
5.2 Paramètres d’entrée pour la valeur instantanée .......................................................11
5.2.1 Choix de la plage du signal d’entrée ..............................................................11
5.2.2 Point décimal pour la valeur instantanée ......................................................11
5.2.3 Modification des limites de la plage ..............................................................12
5.2.4 Modification de la courbe de fonctionnement .............................................13
5.3 Paramétrage de la courbe de fonctionnement de l’affichage
5.3.1 Détermination du nombre de points caractéristiques ................................14
5.3.2 Définition du premier point caractéristique ..................................................15
5.3.3 Définition du deuxième point caractéristique ...............................................15
5.3.4 Définition des points caractéristiques supplémentaires ............................15
5.4 Totalisateur
5.4.1 Réglage du seuil d’entrée du totalisateur ......................................................15
5.4.2 Paramétrage du totalisateur ...........................................................................16
5.4.2.1 Réglage du point décimal pour le totalisateur ...........................18
5.4.2.2 Utilisation de la plage d’affichage entière
pour la valeur du totalisateur ........................................................18
5.4.3 Remise à zéro de la valeur du totalisateur ...................................................19
5.5 Valeurs limite / Sorties des valeurs limite
5.5.1 Valeur limite 1/Sortie de valeur limite1 ..........................................................20
5.5.1.1 Activation / désactivation de la valeur limite 1 ..........................20
5.5.1.2 Affectation de la valeur limite 1 ...................................................20
5.5.1.3 Sélection du mode pour la sortie de valeur limite 1 .................20
5.5.1.4 Hystérésis pour la valeur limite 1 .................................................21
5.5.1.5 Réinitialisation du signal Latch sur la sortie de valeur limite 1 ..22
5.5.1.6 Choix de la forme du signal pour la sortie de valeur limite 1 ...23
Page 2
5.5.2 Valeur limite 2/Sortie de valeur limite 2 ......................................................... 23
5.5.2.1 Activation / désactivation de la valeur limite 2 ......................... 23
5.5.2.2 Affectation de la valeur limite 2 ................................................... 23
5.5.2.3 Sélection du mode pour la sortie de valeur limite 2 .................23
5.5.2.4 Hystérésis pour la valeur limite 2 ................................................ 24
5.5.2.5 Réinitialisation du signal Latch sur la sortie de valeur limite 2 ... 24
5.5.2.6 Choix de la forme du signal pour la sortie de valeur limite 2 .. 25
5.6 Acquisition MIN/MAX .....................................................................................................25
5.6.1 Surveillance de la valeur maximale ...............................................................25
5.6.1.1 Réinitialisation de la valeur maximale ........................................ 25
5.6.2 Surveillance de la valeur minimale ............................................................... 25
5.6.2.1 Réinitialisation de la valeur minimale ......................................... 26
5.6.3 Effet du dépassement des limites de la plage de mesure ou
du dépassement par le haut (Overflow)/par le bas (Underflow)
sur MIN/MAX .....................................................................................................26
5.7 Filtre antironflement ........................................................................................................26
5.8 Rétablissement des valeurs de réglage par défaut .................................................. 27
5.9 Fin du paramétrage ......................................................................................................... 27
5.10 Vérification/modification du paramétrage .................................................................. 28
6. Fonctionnement ............................................................................................................... 28
français
6.1 Modification de l’affichage pendant le fonctionnement .......................................... 29
6.2 Réglage des valeurs limite pendant le fonctionnement ........................................... 30
6.3 Réinitialisation des valeurs MIN/MAX ........................................................................ 30
6.4 Remise à zéro du totalisateur......................................................................................... 31
6.5 Mise en mémoire (Display-Hold) .................................................................................. 31
Page 3
1 Instructions de sécurité et avertissements
!
– de manière conforme à leur
destination
– s’ils sont techniquement en
parfait état
– en respectant les instructions
d’utilisation et les instructions
générales de sécurité.
L’afficheur digital ne peut être utilisé Si l’afficheur digital est mis en oeuvre
qu’en tant qu’appareil encastré. Ce pour la surveillance de machines ou
produit trouve son application dans les de process où, en cas de panne ou
process industriels et les commandes, d’une erreur de manipulation de l’ap-
dans le domaine des chaînes de fabri- pareil, peuvent apparaître des risques
cation des industries du métal, du de dommages à la machine ou d’acci-
bois, des matières plastiques, du pa- dents pour les opérateurs, il vous ap-
pier, du verre, du textile, etc. partient de prendre les mesures de sé-
Les surtensions aux bornes de l’affi- curité appropriées.
cheur digital doivent être limitées aux
valeurs de la catégorie de surtension II.
Page 4
2. Caractéristiques techniques
français
avec protection contre les inversions de polarité,
fusible externe 250 mA à action retardée
Filtre anti-ronflement filtre digital, programmable 50 Hz ou 60 Hz
2.2.2 Entrées
Plages de mesure
Entrée de mesure de courant (CC)
Plages 0 ... 20 mA, 4 ... 20 mA
Résolution 2 µA
Chute de tension max. 2 V pour 20 mA
Courant max. 50 mA
Entrée de mesure de tension (CC)
Plages 0 ... 10 V, 2 ... 10 V, ±10 V
Résolution 1 mV
Résistance d’entrée > 2 MΩ
Tension max. ± 30 V
Page 5
Entrées digitales
Entrée MPI* La fonction de l’entrée dépend du paramétrage
1. Fonction Display-Hold fige l’affichage de la valeur instantanée
2. Fonction Réinitialisation réinitialise les sorties des valeurs limite
Latch des valeurs limite
3. Fonction RAZ totalisateur remise à zéro du totalisateur
*MPI : Multi Purpose Input
2.2.3 Sorties
Sortie de valeur limite 1/sortie de valeur limite 2
Relais à contact inverseur sec
Programmable à l’ouverture ou à la fermeture
Tension commutable 250 V CA/300 V CC
Courant commutable max. 3 A CA/CC, min. 30 mA CC
Puissance commutable 2000 VA / 50 W
ou optocoupleur NPN à collecteur et émetteur ouverts
Puissance commutable 30 V CC/15 mA
UCEsat pour Ic = 15 mA max. 2,0 V CC
UCEsat pour Ic = 5 mA max. 0,4 V CC
Page 6
2.3 Caractéristiques mécaniques
Boîter A encastrer dans panneau 96 x 48 mm
suivant DIN 43 700, couleur RAL 7021
Dimensions (L x H x P) 96 x 48 x 90 mm
Découpe d’encastrement (L x H) 92+0,8 x 45+0,6 mm
Profondeur de montage env. 83 mm
Poids env. 220 g
Indice de protection IP 65 (sur la face avant)
Raccordement
Tension d’alimentation et sorties: 1 bornier, 8 bornes à visser au pas de 5.08
Entrées de mesure et de commande: 1 bornier, 11 bornes à visser au pas de 3.81
Interfaces: (*) 1 bornier, 5 bornes à visser au pas de 3.81
Nettoyage: La face avant de l’appareil ne doit être
nettoyée qu’avec un chiffon doux humide.
2.4 Conditions d’environnement
Température de fonctionnement –20°C ... +65°C
Température de stockage –40°C ... +85°C
Résistance climatique < 75% d’humidité relative, sans condensation
français
Contrôleur de process
Bornier, 8 bornes à visser au pas de 5.08
Bornier, 11 bornes à visser au pas de 3.81
Étrier de montage
Joint
Instructions d’utilisation multilingues
1 jeu de symboles autocollants
Page 7
3. Montage
Découpe d’encastrement
4. Raccordements électriques
Vue de l’arrière
X2 X2
+ - - +
1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11
1 Entrée de courant (I) 2 GND1 (Analogique)
0 ... 20 mA / 4 ... 20 mA 3 Entrée de tension (U)
2 GND1 (Analogique) 0 ... 10 V, 2 ... 10 V, -10 ... +10 V
Page 8
4.2 Entrées de commande et tensions auxiliaires (Uout)
français
7 10 ... 30 V CC 90 ... 260 V CA (N~)
OUT 2 OUT 1 8 GND4 (0 V CC) 90 ... 260 V CA (L~)
X1
1 2 3 4 5 6 7 8 Attention : pour les modèles CA,
ne brancher la tension d’alimenta-
tion qu’après achèvement com-
plet de l’installation. Danger de
mort ! Comparez la tension d’alimentation
avec les indications de la plaquette signa-
létique.
Page 9
5 Paramétrage – Valeurs limite
Les paramètres doivent être réglés avant Il est possible d’activer une, deux ou au-
la mise en service. cune des valeurs limite. Il faut régler
– Paramètres d’entrée l’hystérésis et les paramètres de sortie. En
cas de dépassement d’une valeur limite,
Paramétrez la courbe de fonctionnement
un signal est émis par la sortie définie et
de l’appareil en fonction du capteur utlilisé. la LED correspondante s’allume.
– Courbe de fonctionnement Le réglage des valeurs limite se fait en
L’attribution des signaux d’entrée aux va- mode fonctionnement !
leurs affichées s’effectue à l’aide d’une
courbe de fonctionnement. Cette courbe – Filtre antironflement
de fonctionnement est définie à l’aide de Il est possible de sélectionner la fréquen-
couples de valeurs. ce du réseau local pour réduire les para-
sites dus au réseau et à l’environnement.
– Totalisateur
Pour l'affichage des totaux calculés par
l'appareil, il faut régler le point décimal, le
multiplicateur d'unité et l'échelle.
Page 10
Au cas où des valeurs négatives sont au chiffre suivant
prévues, le „9“ de la décade la plus
élevée est suivi par „-“, puis „-1“, et seu- Confirmer une valuer : appuyer sur la tou-
lement après par „0“. che la valeur est mise en mémoire et
Appuyer sur la touche pour passer le paramètre suivant s’affiche.
français
4 ... 20 mA (03,000 ... 21,000)
0 ... 10 V (–0,500 ... 10,500)
Confirmer avec
Page 11
5.2.3 Modification des limites de la plage
Paramètre Paramètre
Plage de valeurs possible Plage de valeurs possible
0 .. 10 V –0.500 ... 10.500 –0.500 ... 10.500
2 .. 10 V 01.500 ... 10.500 01.500 ... 10.500
-10 .. +10 V –10.500 ... 10.500 –10.500 ... 10.500
0 .. 20 mA –1.000 ... 21.000 –1.000 ... 21.000
4 .. 20 mA 03.000 ... 21.000 03.000 ... 21.000
Si le signal de mesure dépasse la valeur Les réglages à l’extérieur des plages de
programmée par le bas ou par le haut, l’af- mesure ne sont pas possibles. Il n’est
fichage indique alternativement le messa- possible de continuer la programmation à
ge d’avertissement et la valeur l’aide de la touche que lorsque le
mesurée, ou le message d’avertissement réglage est cor-
et la valeur mesurée. rect.
Page 12
5.2.4 Modification de la courbe de fonctionnement
Confirmer avec
français
Il faut tenir compte du fait qu’en cas de
courbe de fonctionnement croissante,
comme en cas de courbe de fonctionne-
ment décroissante, les valeurs d’entrée
(InP.01 .. InP.24) sont croissantes.
Plage d’affichage
Page 13
Plage d’entrée –10 ... + 10 V
Plage d’affichage
Page 14
5.3.2 Définition du premier point caractéristique
Menu <–> Choix
Définir en premier lieu la valeur d’entrée Exemple :•–5,000
dans l’unité correspondante (ex. V, mA) Choisir la décade
pour le début de la courbe de fonction-
Régler le chiffre
nement.
Confirmer avec
Régler ensuite la valeur d’affichage pour le Menu <–> Choix
début de la courbe de fonctionnement. Exemple :•–250,0
Choisir la décade
Régler le chiffre
Confirmer avec
5.3.3 Définition du deuxième point caractéristique
Régler la valeur d’entrée Menu <–> Choix
Exemple : 2,000
français
Confirmer avec
Confirmer avec
5.4.2Paramétrage du totalisateur
Le totalisateur additionne les valeurs in- La valeur affichée du totalisateur se cal-
stantanées à la vitesse d’une mesure par cule à partir de la somme calculée par le
seconde. totalisateur, en définissant la position du
Le résultat de l’addition de ces valeurs est point décimal selon les besoins.
un nombre beaucoup plus grand qui dé- N.B.: Pour optimiser la précision, il est
passe en général la plage d’affichage. Par conseillé d’utiliser toute la plage d’afficha-
conséquent, il faut le convertir de façon à ge pour représenter la valeur du totalisa-
l’adapter à la plage d’affichage. Cette opé- teur. Ceci est aussi le cas pour la valeur
ration s’effectue au moyen du multiplica- instantanée tant que l’affichage sur l’en-
teur d’unité et de l’échelle. semble de la plage est possible avec une
Explication : Si l’affichage indique la va- précision acceptable (avec une erreur
leur 12 345 et si celle-ci est additionnée d’arrondi aussi faible que possible).
pendant une heure, les 3 600 valeurs de La remise à zéro du totalisateur se fait soit
12 345 donnent un résultat de 44 442 000. par un signal sur l’entrée MPI soit manuel-
Cette valeur ne peut être affichée qu’a- lement à l’aide de la touche rouge.
près sa division par 1 000. Ceci signifie que
l’affichage indique le nombre 44 442.
Page 16
Exemple 1 : valeur du totalisateur est remise à zéro.
Un récipient vide est rempli à la vitesse
moyenne de 10 l/s, jusqu’à un volume de
2 m3. Ensuite, le récipient est vidé et la
Valeurs instantanées
Valeur du totalisateur
français
Valeur Valeur numérique Nombre de Somme interne au
instantanée à l’entrée du valeurs totalisateur sans
affichée totalisateur mise à l’échelle
10 000 X 200 2 000 000
multiplicateur x échelle
Possibilités dd’utilisation de
0,1000 x 10
la plage entière (mise à
1,0000 x 1
l’échelle complète)
etc.
Remarque:
Pour afficher le poids, il suffit de prendre
en compte le poids spécifique dans le
multiplicateur.
Page 17
Exemple 2 :
Si un pneu est soumis à un test à 180 km/h pendant une heure, il parcourt une distan-
ce de 180 km.
Confirmer avec
Page 18
Réglage de l’échelle
français
mode Latch, les sorties de valeur limite ne peuvent être réinitiali-
sées que manuellement.
Confirmer avec
Page 19
5.5 Valeurs limite/sorties de valeur limite
Il est possible d’activer une, deux ou au-
cune de valeurs limite.
valeur
instantanée valeur limite
positive
sortie
français
valeur pour le déclenchement = valeur limite + hystérésis de déclenchement Δa
valeur pour l'arrêt = valeur limite – hystérésis d'arrêt Δb
La valeur de déclenchement doit être supérieure à la valeur d’arrêt.
valeur limite
hystérésis de négative
déclenchement
hystérésis d’arrêt
sortie
Choisir la décade
Régler le chiffre, puis la forme du signal pour la sortie 1
Confirmer avec ➱ chapitre 5.5.1.6 23
français
La valeur limite 2 est active, confirmer avec
Totalisateur
Mode Auto
Confirmer avec
Page 23
5.5.2.4 Hystérésis pour la valeur limite 2
Réglage de l’hystérésis de déclenchement Δa pour la valeur limite 2
Menu <–> Choix
Choisir la décade
Régler le chiffre
Confirmer avec
Réglage de l’hystérésis d’arrêt Δb pour la valeur limite 2
Menu <–> Choix
Choisir la décade
Régler le chiffre ➱ chapitre 5.5.2.6 Choix de la forme de signal pour
la sortie de valeur limite 2
Confirmer avec
français
La valeur n’est pas surveillée chapitre 5.6.2 , 25
Confirmer avec
Page 25
5.6.2.1 Réinitialisation de la valeur minimale
Réseau local à 60 Hz
Réseau local à 50 Hz
Confirmer avec
Page 26
5.9 Rétablissement des valeurs de réglage par défaut
Le paramètre permet à l’utilisa- paramètres sont rétablis à leur valeur pré-
teur de rétablir la valeur par défaut pour réglée par défaut. Il n’est pas nécessaire
tous les paramètres. Il faut programmer la de terminer la programmation, il est possi-
valeur =07049 dans le paramètre ble d’effectuer immédiatement un nouveau
. Si, à l’aide des touches, l’utilisa- cycle de programmation.
teur passe au paramètre suivant, tous les
Choisir la décade
français
5.9 Paramétrage terminé oui /non ?
Menu <–> Choix
Page 27
5.10 Vérification/modification du paramétrage
6 Fonctionnement
L’appareil est en état de fonctionnement L’affichage peut alors donner les indica-
après sa mise sous tension ou à la fin de tions suivantes :
son paramétrage.
Page 28
6.1 Modification de l’affichage pendant le condes pour passer à la fonction d'affi-
fonctionnement chage suivante.•Ce changement est con-
firmé par l’affichage pendant 2 secondes
Appuyer une fois sur la touche P pour du nom de la nouvelle fonction active.
faire apparaître pendant 2 secondes le Après 2 secondes, l’appareil affiche la va-
nom de la fonction active. Presser la tou- leur correspondant à la fonction sélection-
che P une seconde fois pendant ces 2 se- née.
français
1 Total
Attention!
Quand une valeur limite est affichée, la va- Pour empêcher toute modification involon-
leur prédéfinie de celle-ci peut être modi- taire, il est conseillé d’activer le verrouilla-
fiée ! ge des touches „KEY“.
Page 29
6.2 Réglage des valeurs limite pendant
le fonctionnement
Quand une valeur limite est affichée, il est N.B.: Le verrouillage des touches „KEY“
possible de modifier la valeur prédéfinie ne doit pas être actif.
de celle-ci !
Choisir la décade
Régler le chiffre.
Exemple : 300,0
Choisir la décade et
Régler le chiffre.
Exemple : 800,0
Confirmer avec
Page 30
6.4 Remise à zéro du totalisateur
français
La fonction Display-Hold n’est active que
pour les réglages des paramètres suivants :
Paramètres Réglages
Page 31
1. Instrucciones de seguridad y de advertencia
1.1 Empleo normal .................................................................................................... 4
2. Información técnica
2.1 Datos generales................................................................................................................. 5
2.2 Información eléctrica ..................................................................................................... 5
2.2.1 Alimentación de corriente ............................................................................... 5
2.2.2 Entradas .............................................................................................................. 5
2.2.3 Salidas ................................................................................................................. 6
2.3 Información mecánica..................................................................................................... 7
2.4 Condiciones ambientales ............................................................................................... 7
2.5 Contenido a entregar........................................................................................................ 7
2.6 Clave de pedido................................................................................................................ 7
3. Montaje.............................................................................................................................. 8
4. Conexiones eléctricas
4.1 Entradas de medición ..................................................................................................... 8
4.2 Entradas de control y tensiones auxiliares (Uout) ..................................................... 9
4.3 Tensión de alimentación y salidas de valores límite................................................. 9
5. Parametraje
5.1 Modo de parametraje .....................................................................................................10
5.2 Parámetros de entrada para valor momentáneo .......................................................11
5.2.1 Seleccionar la escala para la señal de entrada ..........................................11
5.2.2 Ajustar la coma decimal para el valor momentáneo ..................................11
5.2.3 Modificar los límites de escala .......................................................................12
5.2.4 Modificar la curva característica ...................................................................13
5.3 Parametraje de la curva característica del indicador
5.3.1 Introducir el número de puntos básicos ........................................................14
5.3.2 Definir el primer punto básico .........................................................................15
5.3.3 Definir el segundo punto básico .....................................................................15
5.3.4 Definir otros puntos básicos ............................................................................15
5.4 Totalizador
5.4.1 Ajustar el umbral de entrada para el totalizador .........................................15
5.4.2 Parametrar el totalizador .................................................................................16
5.4.2.1 Ajustar la coma decimal para el valor del totalizador ..............18
5.4.2.2 Escala total para el valor del totalizador .....................................18
5.4.3 Restablecimiento del valor del totalizador ....................................................19
5.5 Valores límite/Salidas de valores límite
5.5.1 Valor límite 1/Salida de valores límite ............................................................20
5.5.1.1 Activar o desactivar el valor límite 1 ...........................................20
5.5.1.2 Asignar el valor límite 1 .................................................................20
5.5.1.3 Seleccionar el modo para la salida de valor límite 1 ................20
5.5.1.4 Histéresis para el valor límite 1 .....................................................21
5.5.1.5 Reiniciar la señal Latch en la salida de valor límite 1 ..............22
5.5.1.6 Seleccionar la forma del señal para la salida de valor límite 1 ..23
Página 2
5.5.2 Valor límite 2/Salida de valor límite 2 ............................................................ 23
5.5.2.1 Activar o desactivar el valor límite 2 ...........................................23
5.5.2.2 Asignar el valor límite 2 ................................................................. 23
5.5.2.3 Seleccionar el modo para la salida de valor límite 2 ............... 23
5.5.2.4 Histéresis para el valor límite 2 ....................................................24
5.5.2.5 Reiniciar la señal Latch en la salida de valor límite 2 ..............24
5.5.2.6 Seleccionar la forma del señal para la salida de valor límite 2 ..25
5.6 Detección MÍN/MÁX ...................................................................................................... 25
5.6.1 Vigilar el valor MÁX ............................................................................................... 25
5.6.1.1 Valor MÁX restablecible ............................................................... 25
5.6.2 Vigilar el valor MÍN ...........................................................................................25
5.6.2.1 Valor MÍN restablecible ................................................................ 26
5.6.3 Efecto de sobrepasar los límite de las escalas de medición o
Overflow/Underflow en MÍN/MÁX ................................................................ 26
5.7 Filtro contra zumbidos en la red ................................................................................... 26
5.8 Ajustar el valor por defecto ...........................................................................................27
5.9 Finalización del parametraje sí/no ................................................................................27
5.10 Revisar/Modificar el parametraje .................................................................................28
6. Funcionamiento ............................................................................................................... 28
6.1 Conmutar el indicador en funcionamiento ..................................................................29
6.2 Ajustar los valores límite en funcionamiento ............................................................ 30
6.3 Reiniciar los valores MÍN/MÁX..................................................................................... 30
6.4 Reiniciar el totalizador ....................................................................................................32
6.5 Display-Hold ..................................................................................................................... 32
español
Página 3
1 Instrucciones de Seguridad y de Advertencia
!
– según las instrucciones
– en condiciones técnicas correctas
– según el manual de instrucciones y las
advertencias de seguridad generales.
Página 4
2. Información técnica
2.2.2 Entradas
Entradas de medición
Entrada de corriente (DC)
Escalas 0 ... 20 mA, 4 ... 20 mA
español
Resolución 2 µA
Caída de tensión máx. 2V en 20 mA
Corriente máx. 50 mA
Entrada de tensión (DC)
Escalas 0 ... 10 V, 2 ... 10 V, ±10 V
Resolución 1 mV
Resistencia de entrada > 2 MΩ
Tensión máx. ± 30 V
Página 5
Entradas digitales 2
Entrada MPI* Función de la entrada que depende del parametraje C
1. Función Display-Hold Para detener el valor momentáneo
2. .Función Reset Reiniciar las salidas de valor límite D
Latch Valor límite R
3. Función Reset Totalizador Reiniciar el totalizador (
*MPI: Multi Purpose Input P
P
Entrada KEY Bloqueo de teclado para ajuste de valores límite T
Nivel de conmutación Lógico 0 0 ... 2 V DC
Lógico 1 4 ... 30 V DC C
Duración de impulso mín > 5 ms A
La entrada MPI y la entrada KEY están aislados galvánicamente del resto de la electróni- E
ca del aparato por el optoacoplador. I
L
2.2.3 Salidas
Salida de valor límite 1/ Salida de valor límite 2 2
Relé con contacto inversor sin tensión T
Programable como contacto de reposo o de trabajo T
Tensión de activación AC 250V/DC 300 V R
Corriente de conmutación AC/DC 3 A máx., DC 30 mA mín
Capacidad de conmutación 2000 VA / 50 W 2
u Optoacoplador NPN con colector y emisor abiertos
Potencia de conmutación DC 30 V /15 mA
UCEsat en IC =15 mA DC 2,0V máx
UCEsat en Ic =5 mA DC 0,4 V máx
Página 6
2.3 Información mecánica
Caja Caja para encastrado en un panel 96 x 48 mm
según DIN 43 700, RAL 7021
Dimensión (An x Al x P) 96 x 48 x 90 mm
Recorte de cuadro de mando
(Anchura x Altura) 92+0,8 x 45+0,6 mm
Profundidad de montaje aprox. 83 mm
Peso aprox. 220 g
Tipo de protección IP 65 (cara frontal)
Conexión
Alimentación de corriente y salidas 1 x bornera roscada con paso de 5,08 mm, de 8 bornes
Entradas de medidas y de control 1 x bornera roscada con paso de 3,81 mm, de 11 bornes
Interfaces (*) 1 x bornera roscada con paso de 3.81 mm, de 5 bornes
Limpieza: La cara frontal del aparato sólo debe limpiarse
con un paño suave y húmedo.
2.4 Condiciones ambientales
Temperatura ambiente –20°C ... +65°C
Temperatura de almacenamiento –40°C ... +85°C
Resistencia climática 75% de humedad relativa, no condensadora
español
1 hoja con símbolos pegables
Página 7
3. Montaje
4.Conexiones eléctricas
Vista del panel trasero
X2 X2
+ - - +
1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11
1 Entrada de corriente (I) 2 GND1 (Analógico)
0 ... 20 mA / 4 ... 20 mA 3 Entrada de tensión (U)
2 GND1 (Analógico) 0 ... 10 V, 2 ... 10 V, -10 ... +10 V
Página 8
4.2 Entradas de control y tensiones auxiliares (Uout)
español
Página 9
5 Parametraje
Los parámetros deben ajustarse antes de – Valores límite
la puesta en marcha. Pueden estar activos uno o dos valores lí-
– Parámetros de entrada mite, o bien ninguno. Se ajustarán la hi-
La curva característica del aparato debe stéresis y los parámetros de salida. Si se
parametrarse según el sensor utilizado. sobrepasan estos valores límite se emite
– Curva característica una señal en la salida asignada y se en-
cenderá el LED correspondiente.
La asignación de las señales de entrada a
los valores indicados se produce con El valor límite se ajustará en modo de fun-
ayuda de una curva característica. Esta cionamiento.
curva se debe introducir mediante pares
de valores. – Filtro contra zumbido de red
– Totalizador Para disminuir las interferencias de red y
Para la visualización de los valores del to- de entorno se puede seleccionar la fre-
talizador, calculados por el aparato, se cuencia de red local.
deben ajustar la coma decimal, el factor
multiplicador para la unidad de medición
y el desplazamiento de la coma decimal.
Página 10
Si se admiten valores negativos, el final de Guardar el valor: pulsando la tecla
la decena será: tras el "9" sigue el (-), de- se registrará el valor. Se visualiza la si-
spués el (-1) y por último el "0". guiente opción de menú.
Pulsando la tecla se pasará a la si-
guiente cifra.
español
Menú <–> Selección Escala de indicación
–19999 ... 99999 El ajuste de la coma deci-
0,0 –1999,9 ... 9999,9 mal no influye en la exacti-
tud de medición. El valor de
0,00 –199,99 ... 999,99 indicación máximo debe
0,000 –19,999 ... 99,999 permanecer dentro de la
escala de indicación.
0,0000 –1,9999 ... 9,9999 Tras el ajuste de la coma
Guardar con decimal se suprimirán los
ceros en cabeza.
Página 11
5.2.3Modificar los límites de escala
Parámetro: Parámetro
Posible escala de valor Posible escala de valor
0 .. 10 V –0.500 ... 10.500 –0.500 ... 10.500
2 .. 10 V 01.500 ... 10.500 01.500 ... 10.500
-10 .. +10 V –10.500 ... 10.500 –10.500 ... 10.500
0 .. 20 mA –1.000 ... 21.000 –1.000 ... 21.000
4 .. 20 mA 03.000 ... 21.000 03.000 ... 21.000
Si la señal de medición sobrepasa o está valor de medición.
por debajo del valor programado, cambia Los ajustes fuera de las escalas de valor
la indicación entre el aviso de peligro no son posibles. La continuación de la
y el valor de medición, o bien programación con la tecla es sólo
posible, cuando el ajuste
entre el aviso de peligro y el es correcto.
Página 12
5.2.4 Modificar la curva característica
Menú <–> Selección
Ejemplo:•Yes
utilizar la curva característica introducida, ➱ cap. 5.4,
15
Introducir/modificar la curva ➱ cap. 5.3, 13
Guardar con
español
Escala de entrada 0 ... 10 V, 2 ... 10 V, 0 ... 20 mA, 4 ... 20 mA
Escala de indicación
Página 13
Escala de entrada –10 ... + 10 V
Escala de indicación
Ejemplo:•2
Pulsando la tecla se
aumenta el valor en una cifra.
Tras el número 24 el indicador
regresa a 2.
Guardar con
Página 14
5.3.2 Definir el primer punto básico
Menú <–> Selección
En primer lugar se ajustará el valor de Ejemplo:•–5,000
entrada en la correspondiente unidad
Seleccionar el dígito
(por ej. V, mA) para el comienzo de la
curva. Ajustar la cifra
Guardar con
A continuación se ajustará el valor del in- Menú <–> Selección
dicador para el comienzo de la curva.
Ejemplo:•–250,0
Seleccionar el dígito
Ajustar la cifra
Guardar con
5.3.3 Definir el segundo punto básico
Ajustar el valor de entrada Menú <–> Selección
Ejemplo: 2,000
Guardar con
español
Guardar con
5.3.4 Definir otros puntos básicos
Si en el capítulo 5.3.1 se introdujeron otros
puntos básicos, serán solicitados.
5.4 Totalizador
El totalizador añade los valores de medi- registrador de totalizador se sumará en
ción actuales con una velocidad de lectu- adelante con el valor de medición actual.
ra de 1 segundo. Si la señal de medición Si la señal de medición se encuentra en
se encuentra fuera de los límites de las Overflow ó Underflow, es decir,
escalas de medición ó ó se señalará mediante un
,será señalizado mediante un cambio y ó
cambio de indicación y y . Ya no se produce
ó y . El una suma en la memoria del totalizador.
Página 15
Si el valor del totalizador sobrepasa el ta- Indicación: el valor del totalizador perman-
maño del indicador 99999, la indicación ece registrado también en caso de cortes
parpadea a un ritmo de 1 segundo. de corriente.
Guardar con
5.4.2Parametrar el totalizador
Valores momentáneos
Valores sumados
español
Resultado no desplazado Desplazamiento Valor numérico Indicación del
en el totalizador total en salida del valor del totalizador
totalizador
2 000 000 X 1 2 000
Factor x Desplazamiento
Posibilidades de ajuste del
0,1000 x 10
desplazamiento total
1,0000 x 1
etc.
Indicación:
Si el valor del totalizador debe ser visuali-
zado como unidad de peso, se tendrá que
tener en cuenta el peso específico a tra-
vés del factor multiplicador.
Página 17
Ejemplo 2:
Si se realiza una prueba con un neumático 180 km/h, repondrá un valor de 180 km.
durante una hora a una velocidad de
Indicación: ya que cada segundo se trans- mérico de 18 000 en la salida del totaliza-
mite un valor, en una hora se suman 3 600 dor.
valores. La escala total de
Para utilizar completamente el tamaño del 648 000.0 : 18 000 = 0,027777...se formará
indicador, el resultado esperado estará re- mediante ajustes del factor multiplicador =
presentado con dos dígitos de decimal. 2,7778 (Valor redondeado) y del desplaza-
Los 180,00 km corresponden a un valor nu- miento = 0,01.
Guardar con
Página 18
Ajustar el desplazamiento
español
Las salidas de valores límite sólo pueden ser restablecidas manual-
mente en modo Latch.
Página 19
5.5 Valores límite /Salidas de valores límite
Pueden estar activos uno, dos o bien ningún valor
límite.
Valor de
medición Valor límite
positivo
Salida
español
Con valor límite negativo:
Valor límite
negativo
Histéresis de Histéresis de desactivación
activación
Salida
Guardar con
➱ capítulo 5.5.1.6 23
español
Totalizador
Modo-Auto
Guardar con
Página 23
5.5.2.4 Histéresis para el valor límite 2
Ajustar la histéresis de activación Δa para el valor límite 2
Menú <–> Selección
Seleccionar el dígito
y ajustar la cifra
Guardar con
Ajustar la histéresis de desactivación Δb para el valor límite 2
Menú <–> Selección
Seleccionar el dígito
y ajustar la cifra
Guardar con ➱ capítulo 5.5.2.6 Seleccionar señal para la salida 2.
5.5.2.5 Reiniciar la señal Latch en la salida 2
Menú <–> Selección
español
Ejemplo: Yes
no restablecible
Guardar con
Página 25
5.6.2.1 Valor MÍN restablecible
no restablecible
Página 26
5.8 Ajustar el valor por defecto
Mediante el parámetro el usua- al siguiente parámetro, todos los paráme-
rio tiene la posibilidad de restablecer tros se restablecen al valor preajustado.
todos los parámetros en los valores prea- La programación no tiene que finalizarse,
justados. En el parámetro el puede ejecutarse otro ciclo de programa-
valor =07049 debe ser progra- ción inmediatamente.
mado. Si con ayuda de las teclas se pasa
Seleccionar dígito
español
Página 27
5.10 Revisar/Modificar el parametraje
6 Funcionamiento
Al activar la alimentación de tensión o tras en funcionamiento, el indicador puede mo-
finalizar el parametraje el aparato se en- strar los siguientes avisos.
cuentra en funcionamiento. Cuando está
Página 28
6.1 Conmutar indicador en funcionamiento
Con una sola pulsación de la tecla P se función del indicador. Para confirmación
mostrará durante 2 seg.la denominación aparecerá una indicación con la nueva
de la función momentánea seleccionada. denominación durante 2 seg. Tras los 2
Si dentro de estos 2 seg. se pulsa la tecla seg. se visualizará el valor correspondien-
P una vez más, se pasará a la siguiente te a la función seleccionada.
LED Pr1 on 2
Valor límite 1 (si está activada)
2
LED Pr2 on Valor límite 2 (si está activada)
1 total
español
trará la función actual seleccionada. Al apagan.
encender, se mostrará otra vez en el Dis-
play el valor correspondiente a esta fun-
ción.
Indicación
Si aparece un valor límite en el indicador, Esto puede evitarse si se activa el bloqueo
el valor ajustado de esta última puede ser de teclado "Key".
modificado.
Página 29
6.2 Ajustar un valor límite en Observación: El bloqueo de teclado „Key“
funcionamiento no debe estar activado.
Ajustar valores límite en funcionamiento.
Si aparece un valor límite en el indicador,
el valor ajustado de este último puede ser
modificado.
Seleccionar el dígito y
ajustar la cifra.
Ejemplo 300,0
Seleccionar un dígito y
ajustar la cifra.
Ejemplo 800,0
Guardar con
El reinicio sólo es posible si fue activado Seleccionar el valor MÍN ó MÁX en la in-
en el parametraje. dicación.
• pulsar la tecla roja
• el valor registrado se eliminará
Página 30
6.4 Reiniciar el totalizador
6.5 Display-Hold
Parámetros Ajustes
español
Reinicio del valor del totalizador ó
y
de los valores límite /
Modo de salida /
Página 31
GmbH & Co. KG
32825 Blomberg
Phoenix Contact
Flachsmarktstraße 8
Telefon: 0 52 35 - 3 00
Telefax: 0 52 35 - 34 12 0
www.phoenixcontact.com
TNR 9009083-02/07.09 Art.: 28 64 215-03/28 64 228-03
- Technische Änderungen vorbehalten - Subject to change without prior notice - Sous réserve de modifications