L1 HRSG TRIP NOTIFICATION

Unit : 71

SN KKS Signal Tag Description Setpoint CONDITIONS TRIP REASON SMS MESSAGE
L-HRSG_71_DL_INPUT L1-HRSG_71_STATUS INSERVICE L1- HRSG 71 tripped @ <Steam flow>
L1-71MBR01AA001ZV61 ZV61 HRSG1 TRIP ON
1
L1-71CAD01EE001 ZV81 HRSG1 BOTH FWP STP (FH) ON & BOTH FWP STOPPED t/h on <Date/Time> due to Both
Feed Water Pumps Stopped 2v3.
L1-71LAC11EE001 ZV08 HRSG1 BOTH FEED WATER PUMPS STOPPED ON
L-HRSG_71_DL_INPUT L1-HRSG_71_STATUS INSERVICE L1- HRSG 71 tripped @ <Steam flow>
L1-71MBR01AA001 ZV61 HRSG1 TRIP ON t/h on <Date/Time> due to Duct
DB SCANNER COOLING AIR
2 L1-71CAD01EE001 ZV82 HRSG1 DB SCAN CLG AIR PRS LL (FH) ON & PRESSURE LOW LOW
Burner Flame Scanner Cooling Air
Pressure 2v3 Low Low <150 mbarg Or
HRSG1 DUCT BURNER SCANNER COOLING AIR PRESSURE ON
L1-71HHQ01CP101 ZV02
LO-LO TRIP (30s) 2v3 Channel Fault.
L-HRSG_71_DL_INPUT L1-HRSG_71_STATUS INSERVICE L1- HRSG 71 tripped @ <Steam flow>
L1-71MBR01AA001 ZV61 HRSG1 TRIP ON t/h on <Date/Time> due to High
3
L1-71CAD01EE001 ZV85 HRSG1 HP DRUM LVL HH (FH) ON & HP DRUM LEVEL HIGH HIGH
Pressure Drum Level 2v3 High High ≥
L1-71HAD01CL001 ZV05 HRSG1 HP DRUM LVL HH/QB TRIP ON 225 mm Or 2v3 Channel Fault.
L-HRSG_71_DL_INPUT L1-HRSG_71_STATUS INSERVICE L1- HRSG 71 tripped @ <Steam flow>
L1-71MBR01AA001 ZV61 HRSG1 TRIP ON t/h on <Date/Time> due to High
4
L1-71CAD01EE001 ZV86 HRSG1 HP DRUM LVL LL (FH) ON & HP DRUM LEVEL LOW LOW
Pressure Drum Level 2v3 Low Low ≤ -
L1-71HAD01CL001 ZV02 HRSG1 HP DRUM LVL LL/QB TRIP ON 1370mm Or 2v3 Channel Fault.
L-HRSG_71_DL_INPUT L1-HRSG_71_STATUS INSERVICE L1- HRSG 71 tripped @ <Steam flow>
L1-71MBR01AA001 ZV61 HRSG1 TRIP ON EMERGENCY PUSHBUTTON t/h on <Date/Time> due to CCR
5
L1-71CAD01EE001ZV87 ZV87 HRSG1 S/D PB ON (FH) ON & ACTIVATED Emergency Push Button Activated
L1-71MBR01EE001 XB08 HRSG1 SHUT DOWN PUSH BUTTON ON ON 2v3.
L-HRSG_71_DL_INPUT L1-HRSG_71_STATUS INSERVICE L1- HRSG 71 tripped @ <Steam flow>
L1-71MBR01AA001 ZV61 HRSG1 TRIP ON
6
L1-71CAD01EE001 ZV83 GT1 TRIP (FH) ON & GT 71 TRIPPED t/h on <Date/Time> due to GT 71
Tripped 2v3.
L1-71CAD01EE001 ZV95 GT1 TRIP ON
Note: The HRSG 71 Status will look one (1) minute ago
All must be activated before sending the SMS notification
L1-71LBA11CF002ZQ03SPV - Steam flow tag to be used

L-HRSG_71_DL_INPUT (in service) = GT GCB - CLOSE & Diverter Damper - OPEN & Main steam valve - OPEN & Trip signal – OFF*