MULTIPLES OF CURRENT SENSOR TAP (X)

.1 .2 .4 .6 .8 1 .1 .2 .4 .6 .8 1
.1 .2 .4 .6 .8 1 .1 .2 .4 .6 .8 1
1000 1000
900 900
800 800
700 700
600 600
500 500

400 400

300 300

200 200

100 100
90 Ground Fault Ground Fault Ground Fault Ground Fault 90
80 80
70 Pickup Points Pickup Points Pickup Points Pickup Points 70
60 AKT-50 AK-75 AKR-75 AK-100 60
AKRT-50 AKR-100
TIME IN SECONDS

TIME IN SECONDS
50 50

40 40

30 30

20 20

.18X
.2X

.2X

.2X
.22X

.2X
.22X
.25X

10 10

.25X

.22X
9 9
.25X

8 8
.3X

.25X
7

.3X
7
.3X

6 6
.4X

.35X

.27X
.35X

5 5
.5X

.37X
4
.6X

.3X
.4X

3 3

2 2

1 1
.9 .9
.8 .8
.7 .7
GES-6035B

GES-6035B
.6 .6
.5 .5
.4 .4
Maximum
.3 .3

.2
Intermediate .2
Ground Fault
Delay Bands

.1 Minimum .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05

.04 .04

.03 .03

.02 .02

.01 .01
.1 .2 .4 .6 .8 1 .1 .2 .4 .6 .8 1
.1 .2 .4 .6 .8 1 .1 .2 .4 .6 .8 1

MULTIPLES OF CURRENT SENSOR TAP (X)

GE Consumer & Industrial -


Electrical Distribution Low-Voltage Power Circuit Breakers
GES-6035B
Current Sensor Taps (Amperes) Type AK/AKR Programmer Set Points
AKT/AKRT-50 800, 1200, 1600, 2000 SST Solid-state Overcurrent Trip Device Ground Fault Pickup:
AK/AKRT-50 .2x, .25x, .3x, .4x, .5x, & 6x
AK-75 1200, 1600, 2000, 3000 Ground Trip Time-current Curves
AKR-75 .2x, .22x, .25x, .3x, .35x, & 4x
AKR-75 1200, 1600, 2000, 3200 AKRT-75 .2x, .22x, .25x, .3x, .35x, & .37x
AK/AKR-100 1600, 2000, 3000, 4000 Curves apply at 50/60 Hertz. AK/AKR-100 .18x, .2x, .22x, .25x, .27x, & .3x
From -20C to 70C Programmer Ambient. Where X = Sensor tap setting
Ground Fault Delay Bands:
Maximum, Intermediate & Minimum
10.84 1M